Test-report · QC-ROF-TST-003
Roof Load/Pull-Out Test Report
18 checkpoints across 7 sections. After roof sheet installation to verify fastener grip and load-carrying capacity before handover
18 Checkpoints
7 Sections
Once per project or per 2000 m² of roofing area
QC Engineer, Site Engineer

Checklist Preview

S.No.CheckpointIS RequirementStatus
A. TEST SETUP & EQUIPMENT
A1Pull-out test apparatus (portable pull tester or hydraulic jack) with load cell capacity ≥5 kN
Acceptance: Load cell capacity ≥5 kN; Calibrated within 12 months; Accuracy ±2% of reading
Cl. 3 — Equipment specification
OK
NC
NA
HOLD
A2Load cell / force gauge calibrated within last 12 months per ISO/IEC 17025; certificate provided
Acceptance: Valid calibration cert provided; Traceability documented; Uncertainty <±2%
Cl. 3.1 — Calibration requirement
OK
NC
NA
HOLD
A3Pull test fixture suitable for sheet type; designed to apply tensile load perpendicular to sheet
Acceptance: Fixture applies perpendicular load; Prevents sheet slipping; Load applied at fastener center
Cl. 4 — Fixture design
OK
NC
NA
HOLD
B. TEST POINT SELECTION & IDENTIFICATION
B1Minimum 5 test points selected from installed roof (random selection, different areas)
Acceptance: ≥5 test points; Randomly selected from different roof zones; Locations documented
Cl. 5 — Sample size
OK
NC
NA
HOLD
B2Test locations marked and photographed showing fastener location, test apparatus, and reference
Acceptance: Locations marked clearly; Photos taken pre and post-test; Coordinates recorded if applicable
Cl. 5.1 — Documentation
OK
NC
NA
HOLD
C. PULL-OUT TEST EXECUTION
C1Pull apparatus aligned perpendicular to roof sheet surface; load applied gradually at constant rate (5 kN/min typical)
Acceptance: Load rate 5±1 kN/min; Load applied smoothly; No jerking or sudden application
Cl. 6 — Load application rate
OK
NC
NA
HOLD
C2Load increased until fastener pull-out failure occurs; maximum load recorded and noted
Acceptance: Load increased to failure; Peak load recorded; Failure observed (washering, slip, pull-out)
Cl. 6.1 — Failure criterion
OK
NC
NA
HOLD
C3Pull-out load for each test point recorded; mode of failure documented (pull-out vs. sheet tear vs. fastener bend)
Acceptance: Load value recorded in kN; Failure mode noted; Visual observation documented
Cl. 6.2 — Result recording
OK
NC
NA
HOLD
Showing 8 of 18 checkpoints ·
A. TEST SETUP & EQUIPMENT
A1Pull-out test apparatus (portable pull tester or hydraulic jack) with load cell capacity ≥5 kN
Cl. 3 — Equipment specification (IS 13592)
Load cell capacity ≥5 kN; Calibrated within 12 months; Accuracy ±2% of reading
OKNCNAHOLD
A2Load cell / force gauge calibrated within last 12 months per ISO/IEC 17025; certificate provided
Cl. 3.1 — Calibration requirement (IS 1608)
Valid calibration cert provided; Traceability documented; Uncertainty <±2%
OKNCNAHOLD
A3Pull test fixture suitable for sheet type; designed to apply tensile load perpendicular to sheet
Cl. 4 — Fixture design (IS 13592)
Fixture applies perpendicular load; Prevents sheet slipping; Load applied at fastener center
OKNCNAHOLD
B. TEST POINT SELECTION & IDENTIFICATION
B1Minimum 5 test points selected from installed roof (random selection, different areas)
Cl. 5 — Sample size (IS 13592)
≥5 test points; Randomly selected from different roof zones; Locations documented
OKNCNAHOLD
B2Test locations marked and photographed showing fastener location, test apparatus, and reference
Cl. 5.1 — Documentation (IS 13592)
Locations marked clearly; Photos taken pre and post-test; Coordinates recorded if applicable
OKNCNAHOLD
C. PULL-OUT TEST EXECUTION
C1Pull apparatus aligned perpendicular to roof sheet surface; load applied gradually at constant rate (5 kN/min typical)
Cl. 6 — Load application rate (IS 1608)
Load rate 5±1 kN/min; Load applied smoothly; No jerking or sudden application
OKNCNAHOLD
C2Load increased until fastener pull-out failure occurs; maximum load recorded and noted
Cl. 6.1 — Failure criterion (IS 13592)
Load increased to failure; Peak load recorded; Failure observed (washering, slip, pull-out)
OKNCNAHOLD
C3Pull-out load for each test point recorded; mode of failure documented (pull-out vs. sheet tear vs. fastener bend)
Cl. 6.2 — Result recording (IS 13592)
Load value recorded in kN; Failure mode noted; Visual observation documented
OKNCNAHOLD
Showing 8 of 18 ·
Inspection Sign-Off
PASS - ROOF LOAD CAPACITY VERIFIED
FAIL - INADEQUATE CAPACITY
CONDITIONAL - REMEDIATION REQUIRED
Average Pull-Out Load (kN)
Name / Sign / Date
Minimum Pull-Out Load (kN)
Name / Sign / Date
Design Load (kN/m²)
Name / Sign / Date
Capacity / Design Ratio
Name / Sign / Date
Remarks
Name / Sign / Date
Tested By
Name / Sign / Date
Reviewed By
Name / Sign / Date