| S.No. | Field / Checkpoint | Reference | Status |
|---|---|---|---|
| A. CABLE IDENTIFICATION | |||
| A1 | Cable tag no. + from + to + length Acceptance: Per drawing | Per drawing | OK NC NA |
| A2 | Cable size + type (PVC / XLPE / FRLS) + cores Acceptance: Per design | Per current + voltage drop calculation | OK NC NA |
| A3 | Voltage rating (1100V / 3.3kV / 11kV) Acceptance: Per spec | Per system voltage | OK NC NA |
| B. INSTALLATION + TESTING | |||
| B1 | Route — tray / conduit / direct buried / through wall Acceptance: Verified | Per drawing | OK NC NA |
| B2 | Insulation Resistance (IR) test — pass / fail Acceptance: Megger test logged | ≥ 1 MΩ at 500/1000V megger per IS 732 | OK NC NA |
| B3 | Continuity test Acceptance: Logged | Open / short / earth fault test | OK NC NA |
| B4 | HV test (for MV/HV cables) — voltage withstand Acceptance: Per cable class | Per IS 7098 | OK NC NA |
| C. TERMINATION | |||
| C1 | Termination quality — lugs, glands, ferrules, labels Acceptance: Inspected | Per IS 9000 | OK NC NA |
| C2 | Earthing — armour to earth at one end (per IS 3043) Acceptance: Per spec | Per code | OK NC NA |