InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel
InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel

IS 732 : 1989Code of practice for electrical wiring installations

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
IEC 60364 series · BS 7671 · NFPA 70, 2023 Edition
CurrentEssentialCode of PracticeBIMMEP · Electrical Installations
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues7InternationalEngineer's NotesTablesFAQ4Related

IS 732:1989 is the Indian Standard (BIS) for electrical wiring installations. IS 732 is the fundamental code of practice for electrical wiring installations in buildings. It provides essential guidelines for the design, selection of equipment, erection, and testing of electrical wiring systems to ensure safety from fire and electric shock.

Provides general requirements for electrical wiring installations in buildings, covering design, selection of equipment, erection, inspection, and testing.

Quick Reference — Top IS 732:1989 Values

Key limits for circuit design, installation clearances, conductor identification, and testing criteria for electrical wiring installations.

✓ Verified 2026-04-27
ReferenceValueClause
Voltage Classification - Low— Between phase and neutral, or between phases for non-earthed systems.≤ 250 VCl. 3.1.1
Voltage Classification - Medium— Exceeding 250 V but not exceeding 650 V.≤ 650 VCl. 3.1.2
Permissible Voltage Drop— At any point on the supply terminals of the consumer.≤ 3% of supply voltageCl. 3.2.1
Light/Fan Sub-Circuit - Max Load800 WCl. 7.3.1
Light/Fan Sub-Circuit - Max Outlets10 pointsCl. 7.3.1
Power Sub-Circuit - Max Load3000 WCl. 7.3.2
Power Sub-Circuit - Max Outlets2 pointsCl. 7.3.2
Fixed Wiring Colour - PhaseRed, Yellow, BlueCl. 5.1.1
Fixed Wiring Colour - NeutralBlackCl. 5.1.1
Fixed Wiring Colour - EarthGreenCl. 5.1.1
Flexible Cable Colour - PhaseBrownCl. 5.1.2
Flexible Cable Colour - NeutralBlueCl. 5.1.2
Switch Mounting Height— Above floor level, for convenient operation.1.3 mCl. 5.2.1
Conduit in Plaster - Min Cover1.5 cmCl. 8.8.1.1
Conduit Saddle Spacing (Horizontal)≤ 1.0 mCl. 8.2.3
Conduit Saddle Spacing (Vertical)≤ 1.5 mCl. 8.2.3
Clearance Above Building (Vertical)— For low and medium voltage lines.2.5 mCl. 6.2.4.1
Clearance From Building (Horizontal)— For low and medium voltage lines.1.2 mCl. 6.2.4.1
Insulation Resistance (Min)— Between conductors and earth for the entire installation.1 MΩCl. 9.1.1
Earth Continuity Resistance (Max)— From earth connection to any point in the conductor.1.0 ΩCl. 9.2
Max Earth Resistance (General)— For general installations not covered by other categories.8.0 ΩCl. 10.2.2 (Table 4)
Max Earth Resistance (Major Sub-station)1.0 ΩCl. 10.2.2 (Table 4)
⚠ Verify against the latest BIS/IRC publication and project specifications. Amendment Slips may modify values.

Overview

Status
Current
Usage level
Essential
Domain
MEP — Electrical Installations
Type
Code of Practice
International equivalents
IEC 60364 series · IEC (International)BS 7671:2018+A2:2022 · BSI / IET (UK)NFPA 70, 2023 Edition · NFPA (US)AS/NZS 3000:2018 · Standards Australia / Standards New Zealand (Australia/NZ)
Typically used with
IS 3043IS 5216IS 694IS 1554IS 9537
Also on InfraLens for IS 732
7Key values3Tables4FAQs

BIM-relevant code. See the BIM Hub for ISO 19650, IFC, and LOD/LOIN frameworks used alongside it.

Practical Notes
! Always coordinate wiring installations with IS 3043 for proper earthing. The earth continuity path is as critical as the phase wiring.
! Do not overfill conduits. Strict adherence to the maximum number of cables per conduit size is required to allow heat dissipation and prevent insulation damage during pulling.
! Aluminum conductors are prone to terminal oxidation and loosening; use proper bimetallic lugs or prefer copper conductors for internal wiring sub-circuits.
Frequently referenced clauses
Cl. 4Design of InstallationCl. 4.2Estimation of LoadCl. 5Selection of Electrical EquipmentCl. 6.2Insulation Resistance TestCl. 6.3Earth Continuity Path
Pulled from IS 732:1989. Browse the full clause & table index below in Tables & Referenced Sections.
electrical wiringcablesconduitsswitchgeardistribution boards

Engineer's Notes

In Practice — Editorial Commentary
When IS 732 is your governing code

IS 732 is the code of practice for electrical wiring installations — the foundational electrical code in India for low-voltage (LV) installations in buildings. It governs the design, selection, installation, inspection, testing, and maintenance of building electrical systems up to 1100 V (1.1 kV) AC.

Use IS 732 for any electrical installation in: - Residential buildings (single houses, apartments, gated communities) - Commercial buildings (offices, retail, hotels) - Institutional buildings (schools, hospitals, government) - Light industrial premises (workshops, MSME units) - Outdoor installations within building plots (compound lighting, gate motors)

Latest revision: IS 732:2019 is the current edition (the page you searched for was IS 732:1989 — that is the older but heavily-cited revision). The 2019 revision aligns with IEC 60364 international practice. For new installations, always reference IS 732:2019; the 1989 version is largely superseded.

IS 732 is enforced by: - Central Electricity Authority (CEA) Regulations, 2010 — make IS 732 / IS 5572 / IS 3043 the mandatory standards for LV installations - State Electrical Inspectorate — pre-energisation inspection per IS 732 + Indian Electricity Rules - BIS marking (ISI) on electrical accessories required for IS 732 compliance - Bank loan / occupancy certificate requirements in many municipalities

Does NOT cover: - High voltage (above 1.1 kV) — see IS 8478, IS 1255 for HV cables and installation - Specific hazardous-area installations (petrochemical, mining) — see IS/IEC 60079 - Solar PV, EV charging — separate codes (IEC 62548, IS 17017 series)

Scope: what IS 732 specifies

Wiring systems and methods (Section 5): - PVC-insulated copper conductors as the default (IS 694:2010) — single-core or multi-core - Aluminium permitted for sub-mains in larger sections (≥ 16 mm²) - Wiring methods: surface conduit (PVC or steel), recessed conduit (in walls/slabs), underground armoured cable for outdoor / sub-circuits - Cable trays for commercial / industrial racks

Earthing (cross-references IS 3043): - All metallic equipment / non-current-carrying parts must be earthed - TT, TN-S, TN-C-S earthing systems described - Earth electrode resistance: ≤ 5 Ω for residential; ≤ 1 Ω for industrial/sensitive electronic loads

Protection (Section 6): - Overcurrent protection: MCB/MCCB per IS 8828 and IS 13947 - Earth-fault / leakage protection: RCD/RCCB per IS 12640 (≤ 30 mA for human protection in wet areas; ≤ 100-300 mA for fire protection) - Surge protection devices (SPDs) per IS 16121 (recommended)

Distribution (Section 7): - Main distribution board (MDB), sub-distribution boards (SDB), final circuits - Conductor sizing by current-carrying capacity, voltage drop (≤ 3 %), short-circuit withstand - Diversity factor for total connected load vs maximum demand

Specific room types (Section 8 / Annexes): - Bathrooms / wet zones: Zone-based protection (IP44 fittings within 0.6 m of water; RCD ≤ 30 mA) - Kitchens: dedicated 16 A circuit per heavy appliance (oven, geyser, AC) - Outdoor: IP65 fittings; armoured cable in conduit

Reference values you'll actually use

Conductor sizing thumb-rules for residential:

| Circuit | Conductor size | Protection | Maximum length (typical) | |---|---|---|---| | Lighting (5 A) | 1.5 mm² Cu | 6 A MCB | 30 m | | 5 A socket outlet | 1.5 mm² Cu | 6-10 A MCB | 25 m | | 16 A power outlet (AC, geyser) | 4 mm² Cu | 16 A MCB + 30 mA RCBO | 20 m | | 20 A heavy outlet (split AC, oven) | 6 mm² Cu | 20 A MCB | 20 m | | Sub-main to flat (5 kW load) | 6-10 mm² Cu | 32 A MCB at MDB | 30 m | | Sub-main to floor (15 kW load) | 16-25 mm² Cu | 63 A MCCB | 50 m |

Voltage drop limit: ≤ 3 % from supply intake to farthest fixture (IS 732 Clause 7.7)

Earthing electrode resistance (IS 3043): - General (no electronic equipment): ≤ 5 Ω - Buildings with computers / electronic equipment: ≤ 1 Ω - Lightning protection (separate electrode): ≤ 10 Ω

RCD trip current ratings: - 30 mA — human protection in bathrooms, swimming pool areas, outdoor sockets - 100 mA — sub-distribution boards (general) - 300 mA — MDB upstream (fire protection)

MCB curves: - Curve B (3-5 In trip): general lighting, resistive loads - Curve C (5-10 In trip): mixed loads, motor circuits, household default - Curve D (10-20 In trip): high-inrush motors, transformers

Cable colour coding (IS 11353): - Phase: red, yellow, blue (3-phase) - Neutral: black - Earth: green / yellow-green stripe

Number of points per circuit (residential thumb-rule): - Lighting: 800-1000 W per circuit - 5 A sockets: ≤ 8 points per circuit - 16 A sockets: 1 point per circuit (dedicated) - AC, geyser: 1 dedicated circuit each

Companion codes (must pair with)
  • IS 3043:2018 — code of practice for earthing (the mandatory companion).
  • IS 5572:2009 — classification of hazardous areas (for electrical installations in petrol pumps, paint stores, etc.).
  • IS 694:2010 — PVC insulated copper conductors (the cable specification).
  • IS 1554 Part 1:1988 — PVC insulated armoured cables for working voltages up to 1.1 kV.
  • IS 7098 Part 1:1988 — XLPE insulated cables.
  • IS 8828:1996 — miniature circuit breakers (MCB).
  • IS 13947 (multi-part) — low-voltage switchgear and controlgear (MCCB, contactors).
  • IS 12640 — residual current operated circuit breakers (RCCB / RCBO).
  • IS 5908 — house service connections.
  • IS 11353 — colour identification of conductors.
  • IS 16121 — surge protection devices.
  • IS 2309 — protection of buildings and allied structures against lightning.
  • NBC 2016 Part 8 Section 2 — electrical installations (the broader building code framework).
  • CEA (Measures relating to Safety and Electric Supply) Regulations, 2010 — statutory authority that mandates IS 732 compliance.
  • Indian Electricity Rules 1956 (legacy framework, partly superseded by CEA 2010).
Common pitfalls / what reviewers flag

1. Reference IS 732:1989 instead of IS 732:2019. The 1989 version predates RCD requirements, modern earthing systems, and RCD protection in wet areas. New installations must use the 2019 revision. 2. Missing RCD on bathroom and outdoor circuits. Mandatory per current revision; even in old installations, a 30 mA RCBO retrofit is cheap insurance. 3. Single conductor size for entire flat sub-main. 4 mm² for 5 kW load that grows to 8 kW (with split ACs added later) blows up at MCB. Size for design + 30 % future growth. 4. No voltage-drop calculation. End-of-line LED bulbs flicker, motors run hot, geysers underperform. Always check drop ≤ 3 %. 5. Earth pit not maintained / measured. Earth pit dries out over years; resistance climbs from 5 Ω to 50 Ω. Annual earth resistance test mandatory; pour water and salt every 6 months in dry climates. 6. Common neutral for two phases (in 3-phase residential). Neutral overload, conductor heating, equipment failure. Each phase needs its own neutral. 7. Cable in conduit oversized count. IS 732 limits cables per conduit (de-rating from heat). Stuffing 8 cables in a 25 mm conduit reduces ampacity 30 %. 8. Surface mounting in wet zones without IP rating. Bathroom switches and sockets must be IP44 minimum; outdoor IP65. Many residential installations use indoor-rated accessories. 9. No labelling at distribution boards. After 5 years, no one knows which MCB serves what. Mandatory: every breaker labelled with circuit name and load. 10. Earthing of refrigerator / washing machine via 2-pin plug. The third pin is for earth; many old houses still have 2-pin sockets. Replace with 3-pin sockets and verify earth continuity at every receptacle (mandatory at testing per IS 732). 11. No RCBO in solar PV grid-tie installations. Bidirectional current and DC injection require special-grade RCDs (Type B); standard Type A may not trip. 12. DIY work by uncertified electricians. State electrical inspectorate requires licensed electrical contractor for installation; non-compliance is a statutory offence.

Where it sits in building services design

Standard MEP design cascade for a residential project:

1. Load calculation — by room/area, demand × diversity factor → total connected load and maximum demand. 2. Single-line diagram (SLD) — supply intake, MDB, sub-DBs, distribution circuits. 3. Cable sizing — per current capacity, voltage drop ≤ 3 %, short-circuit withstand. 4. Protection coordination — main MCCB > sub MCCB > circuit MCB; selectivity to avoid main trip on branch fault. 5. Earthing system — TN-S or TT; pit design per IS 3043; at least 2 pits in parallel for redundancy. 6. Lightning protection — air terminal, down conductor, earth electrode per IS 2309 (not strictly part of IS 732 but companion). 7. Distribution boards layout — accessible, labelled, future-expansion 20 % spare ways. 8. Wiring details — conduit routing, switch heights (1.4 m typical), socket heights (0.3 m wall sockets, 1.4 m kitchen counter, etc.). 9. Specifications (BOQ): - Cables: `PVC insulated copper conductor, 1.5 mm² to IS 694:2010, FRLS grade for confined spaces` - MCB: `IS 8828:1996, Curve C, 6 kA breaking capacity, ISI marked` - RCBO: `IS 12640, 30 mA sensitivity, Type A` - Switches/sockets: `Modular, ISI marked, 16 A 3-pin for power, 6 A 5-pin for general` 10. Pre-commissioning testing (mandatory per IS 732 Section 9): - Insulation resistance (≥ 1 MΩ per circuit at 500 V DC megger) - Earth continuity (≤ 0.5 Ω from accessory earth pin to earth pit) - Earth electrode resistance (≤ 5 Ω) - RCD trip test (manual button + actual trip-current verification) - Polarity check at every socket 11. Inspector approval — state electrical inspectorate inspection before energisation. 12. As-built drawings — handed over to owner with circuit-to-MCB mapping.

IS 732 sets the baseline; for high-end residential and commercial, add: BMS integration, smart-home control, energy meters per circuit, solar PV / inverter hybrid, EV charging.

International Equivalents

Similar International Standards
IEC 60364 seriesIEC (International)
HighCurrent
Low-voltage electrical installations
Forms the fundamental basis for most national wiring codes worldwide, including principles adopted by IS 732.
BS 7671:2018+A2:2022BSI / IET (UK)
HighCurrent
Requirements for Electrical Installations, IET Wiring Regulations
A direct national equivalent, based on IEC 60364, covering design and installation of low-voltage systems in buildings.
NFPA 70, 2023 EditionNFPA (US)
MediumCurrent
National Electrical Code (NEC)
Covers the same subject of safe electrical installation but with a different structure, terminology, and emphasis on conduit systems.
AS/NZS 3000:2018Standards Australia / Standards New Zealand (Australia/NZ)
HighCurrent
Electrical installations (known as the Australian/New Zealand Wiring Rules)
A comprehensive set of rules for electrical wiring in domestic and commercial installations, aligned with IEC principles.
Key Differences
≠RCD/RCCB Protection: IS 732:1989 recommends Earth Leakage Circuit Breakers (ELCBs) in certain situations but lacks the mandatory, widespread requirement for 30mA Residual Current Device (RCD) protection on most socket outlets, lighting circuits in dwellings, and concealed cables, which is a core safety feature of modern standards like BS 7671.
≠Wiring Colours: IS 732:1989 specifies an older colour code (e.g., Red/Yellow/Blue for phases, Black for neutral, Green for earth). Modern harmonized standards (e.g., BS 7671) use Brown/Black/Grey for phases, Blue for neutral, and Green-and-Yellow for the protective conductor.
≠Special Locations: Modern international standards provide highly detailed requirements and defined safety zones (e.g., Zones 0, 1, 2 for bathrooms) for special locations like bathrooms, swimming pools, and medical facilities. IS 732:1989 offers general guidance but is far less granular and prescriptive for these high-risk environments.
≠Periodic Inspection & Testing: While IS 732 requires initial testing, it is less comprehensive regarding mandatory, detailed periodic inspection and testing compared to standards like BS 7671, which has a formalised regime for producing Electrical Installation Condition Reports (EICRs) at set intervals.
≠Earthing Systems: IS 732 describes TT and TN systems, but modern standards like IEC 60364 and BS 7671 provide more rigorous and detailed requirements for the design, installation, and verification of specific earthing arrangements like TN-C-S (PME), TN-S, and TT, including specific calculations for earth fault loop impedance.
Key Similarities
≈Fundamental Safety Principles: Both IS 732 and its international counterparts are founded on the same core principles of protecting persons and property from electric shock (direct and indirect contact), thermal effects (fire), and overcurrent.
≈Overcurrent Protection: The use of fuses and circuit breakers (like MCBs) for overload and short-circuit protection is a fundamental concept in all the standards. The principle of selecting a protective device based on conductor size and load is consistent.
≈Earthing/Grounding for Safety: All standards mandate the connection of exposed-conductive-parts of electrical equipment to earth (ground) to provide a low-impedance path for fault currents, enabling a protective device to operate and prevent electric shock.
≈Basic Circuit Design: The concepts of final circuits (e.g., radial, ring circuits) for supplying lighting and socket outlets, and the need for adequate conductor sizing to prevent overheating, are common to all the codes.
Parameter Comparison
ParameterIS ValueInternationalSource
Wire Colour - Neutral ConductorBlackBlueBS 7671 / IEC 60445
Wire Colour - Protective Earth ConductorGreenGreen-and-Yellow bicolourBS 7671 / IEC 60445
Wire Colour - Single Phase LineRedBrownBS 7671 / IEC 60445
Nominal Single-Phase Voltage240 V230 V (+10% / -6%)BS 7671 (CENELEC Harmonization)
RCD Protection for General Socket OutletsRecommended for specific high-risk applications (e.g., wet areas). Not mandatory for all general-purpose outlets.Mandatory 30mA RCD protection for virtually all socket outlets (≤32A) used by ordinary persons.BS 7671:2018+A2:2022
Minimum Copper Conductor Size for Power Circuits1.5 sq mm for socket outlets.2.5 sq mm for general purpose socket outlets (ring or 20A radial).BS 7671 (common UK practice)
Definition of Bathroom Safety ZonesGeneral guidance provided without specific numbered zones.Specifies detailed Zones 0, 1, and 2 with strict rules on IP ratings and equipment.IEC 60364-7-701 / BS 7671
⚠ Verify details from original standards before use

Key Values7

Quick Reference Values
minimum copper area lighting1.0 sq mm
minimum aluminum area lighting1.5 sq mm
minimum copper area power2.5 sq mm
insulation resistance test voltage500 V DC
minimum insulation resistance1 Megaohm
max points per light subcircuit10 points (or 800 W)
max points per power subcircuit2 points (or 3000 W)

Tables & Referenced Sections

Key Tables
Table 1 - Minimum Cross-Sectional Area of Conductors
Table 2 - Current Rating for Single Core Cables
Table 3 - Maximum Number of Single-Core Cables in Rigid Steel Conduits
Key Clauses
Clause 4 - Design of Installation
Clause 4.2 - Estimation of Load
Clause 5 - Selection of Electrical Equipment
Clause 6.2 - Insulation Resistance Test
Clause 6.3 - Earth Continuity Path

Related Resources on InfraLens

Cross-Referenced Codes
IS 3043:1987Code of practice for earthing
→
IS 5216:1982Guide for safety procedures and practices in ...
→
IS 694:1990PVC insulated cables for working voltages up ...
→
IS 1554:1988PVC insulated (heavy duty) electric cables fo...
→
IS 9537:1980Conduits for electrical installations - Part ...
→

Frequently Asked Questions4

What is the minimum wire size for lighting and fan circuits?+
1.0 sq mm for copper and 1.5 sq mm for aluminum conductors.
What is the minimum wire size for power circuits (15A/16A sockets)?+
2.5 sq mm for copper conductors.
How many points are allowed in a single lighting sub-circuit?+
A maximum of 10 points or a total load of 800 W, whichever is less.
What is the required test voltage and minimum insulation resistance for a new installation?+
Tested at 500 V DC, the insulation resistance should not be less than 1 Megaohm.

QA/QC Inspection Templates

📋
QA/QC templates coming soon for this code.
Browse all 300 templates →