Formats  › MEP Testing & Commissioning  › Lift / Elevator
Test-report · FMT-MEP-004
Lift / Elevator Testing Protocol
15 fields across 4 sections. Lift handover test — Lift Inspector certification mandatory; AMC continues annual checks.
15 Fields
4 Sections
Pre-handover + annual
MEP Engineer, Lift OEM

Format Preview

S.No.Field / CheckpointReferenceStatus
A. EQUIPMENT + INSTALLATION
A1Lift make + model + capacity (Persons / kg) + speed (m/s) + travel (m)
Acceptance: Matches
Per OEM + drawing
OK
NC
NA
A2Machine room + shaft + landings + car installed
Acceptance: Verified
Per drawing + IS 14665
OK
NC
NA
A3Power supply + emergency power + LCT (landing call tableau)
Acceptance: Verified
Per spec
OK
NC
NA
B. SAFETY DEVICES TEST
B1Overspeed governor + safety gear engagement
Acceptance: Tested
Activates at 115% rated speed
OK
NC
NA
B2Buffer (oil or spring) compression test
Acceptance: Within limits
Per IS 14665
OK
NC
NA
B3Door interlocks + door reopen on obstruction
Acceptance: Tested
Per code
OK
NC
NA
B4Overload alarm + door alarm
Acceptance: Tested
Per spec
OK
NC
NA
B5ARD (Automatic Rescue Device) — power cut + auto landing
Acceptance: Tested
Per spec
OK
NC
NA
B6Fire emergency mode — auto landing on fire signal
Acceptance: Tested
Per fire fighting interlock
OK
NC
NA
C. PERFORMANCE
C1Capacity load test (100% + 125%)
Acceptance: Operates correctly
Per code
OK
NC
NA
C2Speed measurement (no-load, full-load) — within ± 5%
Acceptance: Measured
Per OEM
OK
NC
NA
C3Levelling accuracy at each floor — ± 10mm
Acceptance: Per landing
Per spec
OK
NC
NA
C4Door opening + closing time
Acceptance: Within limits
Per OEM spec
OK
NC
NA
Showing 13 of 15 fields ·
A. EQUIPMENT + INSTALLATION
A1Lift make + model + capacity (Persons / kg) + speed (m/s) + travel (m)
Per OEM + drawing
Matches
OKNCNA
A2Machine room + shaft + landings + car installed
Per drawing + IS 14665
Verified
OKNCNA
A3Power supply + emergency power + LCT (landing call tableau)
Per spec
Verified
OKNCNA
B. SAFETY DEVICES TEST
B1Overspeed governor + safety gear engagement
Activates at 115% rated speed
Tested
OKNCNA
B2Buffer (oil or spring) compression test
Per IS 14665
Within limits
OKNCNA
B3Door interlocks + door reopen on obstruction
Per code
Tested
OKNCNA
B4Overload alarm + door alarm
Per spec
Tested
OKNCNA
B5ARD (Automatic Rescue Device) — power cut + auto landing
Per spec
Tested
OKNCNA
B6Fire emergency mode — auto landing on fire signal
Per fire fighting interlock
Tested
OKNCNA
C. PERFORMANCE
C1Capacity load test (100% + 125%)
Per code
Operates correctly
OKNCNA
C2Speed measurement (no-load, full-load) — within ± 5%
Per OEM
Measured
OKNCNA
C3Levelling accuracy at each floor — ± 10mm
Per spec
Per landing
OKNCNA
C4Door opening + closing time
Per OEM spec
Within limits
OKNCNA
Showing 13 of 15 ·
Approval / Sign-Off
APPROVED
HOLD — REVISIONS REQUIRED
REJECTED
Overall Verdict
Name / Sign / Date
Prepared By — Name / Sign
Name / Sign / Date
Reviewed By — Name / Sign
Name / Sign / Date
Approved By — Name / Sign
Name / Sign / Date
Date & Time
Name / Sign / Date
Remarks
Name / Sign / Date