Formats  › MEP Testing & Commissioning  › Fire Alarm System
Test-report · FMT-MEP-005
Fire Alarm System (FAS) T&C Protocol
14 fields across 4 sections. FAS commissioning — fire NOC + occupancy depend on this; thorough zone-wise test critical.
14 Fields
4 Sections
Pre-occupancy + annual
MEP Engineer, FAS Vendor

Format Preview

S.No.Field / CheckpointReferenceStatus
A. INSTALLATION VERIFICATION
A1FAS panel + detectors + MCPs + sounders + cabling per drawing
Acceptance: Drawing-conformity
Per NBC 2016 Part 4
OK
NC
NA
A2Detector types per zone — smoke / heat / multi-criteria / aspirating
Acceptance: Per design
Per occupancy + risk
OK
NC
NA
A3Cable type (FRLS / FRLSH) + segregation from power
Acceptance: Per code
IS 2189 Cl. 9
OK
NC
NA
A4Battery backup — 24 hrs standby + 30 min alarm
Acceptance: Per spec
Per IS 2189
OK
NC
NA
B. ZONE-WISE FUNCTIONAL TEST
B1Detector test (smoke / heat) — each zone
Acceptance: Tested + logged
All detectors trigger alarm
OK
NC
NA
B2MCP (Manual Call Point) test — each zone
Acceptance: Tested
Activation → panel + sounders
OK
NC
NA
B3Sounder + visual alarm test — each zone
Acceptance: Sound level meter test
Audible 65 dBA at far point
OK
NC
NA
B4Public address voice evacuation (if integrated)
Acceptance: Tested
Per spec
OK
NC
NA
C. INTERFACES + EMERGENCY ACTIONS
C1AHU shutdown on fire alarm (smoke control)
Acceptance: Tested
Per fire strategy
OK
NC
NA
C2Lift recall to ground floor
Acceptance: Tested
Per fire strategy
OK
NC
NA
C3Door release (mag locks) on fire alarm
Acceptance: Tested
Per spec
OK
NC
NA
C4Hooter + strobe in all common areas
Acceptance: Tested
Per spec
OK
NC
NA
Showing 12 of 14 fields ·
A. INSTALLATION VERIFICATION
A1FAS panel + detectors + MCPs + sounders + cabling per drawing
Per NBC 2016 Part 4
Drawing-conformity
OKNCNA
A2Detector types per zone — smoke / heat / multi-criteria / aspirating
Per occupancy + risk
Per design
OKNCNA
A3Cable type (FRLS / FRLSH) + segregation from power
IS 2189 Cl. 9
Per code
OKNCNA
A4Battery backup — 24 hrs standby + 30 min alarm
Per IS 2189
Per spec
OKNCNA
B. ZONE-WISE FUNCTIONAL TEST
B1Detector test (smoke / heat) — each zone
All detectors trigger alarm
Tested + logged
OKNCNA
B2MCP (Manual Call Point) test — each zone
Activation → panel + sounders
Tested
OKNCNA
B3Sounder + visual alarm test — each zone
Audible 65 dBA at far point
Sound level meter test
OKNCNA
B4Public address voice evacuation (if integrated)
Per spec
Tested
OKNCNA
C. INTERFACES + EMERGENCY ACTIONS
C1AHU shutdown on fire alarm (smoke control)
Per fire strategy
Tested
OKNCNA
C2Lift recall to ground floor
Per fire strategy
Tested
OKNCNA
C3Door release (mag locks) on fire alarm
Per spec
Tested
OKNCNA
C4Hooter + strobe in all common areas
Per spec
Tested
OKNCNA
Showing 12 of 14 ·
Approval / Sign-Off
APPROVED
HOLD — REVISIONS REQUIRED
REJECTED
Overall Verdict
Name / Sign / Date
Prepared By — Name / Sign
Name / Sign / Date
Reviewed By — Name / Sign
Name / Sign / Date
Approved By — Name / Sign
Name / Sign / Date
Date & Time
Name / Sign / Date
Remarks
Name / Sign / Date