Design Rules🔧 Building Services

Residential Connected Load — per Sqft

Electrical connected load estimation for residential buildings
See also📖 NBC 2016🔗 NBC 2016🔗 IS 732🧮 RCC Design📒 Handbook Topic
1.0
W / sqft
range 0.8 – 1.2 W/sqft of built-up area
1.0W / sqftcompact 0.8 · standard 1.0 · all-AC 1.5–2.0 · diversity 0.5–0.6RESIDENTIAL LOAD
Primary value1.0 W / sqft (range 0.8 – 1.2 W/sqft of built-up area)
Applies toApartment, bungalow and group housing electrical sizing · Pre-tender estimation of total connected load · Service connection sizing and DG sizing
ExceptionsCompact apartment (< 600 sqft)0.8 W/sqft
Standard apartment (600 – 1500 sqft)1.0 W/sqft
Premium apartment / villa (> 1500 sqft)1.2 – 1.5 W/sqft
All-AC household1.5 – 2.0 W/sqft
Diversity factor (apartment block)0.5 – 0.6
Per-flat connected load (typical)5 – 8 kW
Measured asSum of nameplate ratings of all loads (lights, fans, AC, geyser, kitchen, sockets) ÷ built-up area in sqft. Apply diversity factor at the building level for service-connection sizing.
SourceNBC 2016Part 8, Section 2, Cl. 5.2
📚 Cross-referenced

Related on InfraLens

16 related items across IS codes, knowledge articles, design rules, maps and tools

Related IS / IRC Codes· 2

Related Handbook Entries· 2

Related Knowledge Articles· 6 of 12

Why this matters

Connected-load per sqft is the first input every electrical consultant uses to size the service connection, transformer and DG set. 1 W/sqft ≈ 100 W per 10 × 10 ft room — covers 2 fans, lights and one socket per room. Going below this implies under-loaded design that will trip on day-1 of an AC install.

Typical practice

MEP consultants budget 1.0 – 1.2 W/sqft for residential and apply a diversity factor of 0.5 – 0.6 at the substation level — so a 200-flat building with 1000 sqft each lands at 200 × 1000 × 1.0 × 0.55 ≈ 110 kW connected demand, sized as a 200 kVA transformer.

← All Thumbrules