QA/QC  › Flooring & Finishing  › Tile/Stone Laying Inspection
Checklist · QC-FLR-CHK-002
Tile/Stone Laying Inspection Checklist
20 checkpoints across 5 sections. During tile laying work, daily or as sections are completed
20 Checkpoints
5 Sections
Daily or per section completion during laying phase
QC Engineer, Site Inspector

Checklist Preview

S.No.CheckpointIS RequirementStatus
A. ADHESIVE APPLICATION & COVERAGE
A1Adhesive application method (notched trowel, correct angle and pressure)
Acceptance: Notched trowel (6-10 mm) at 45°, continuous coverage >90% of tile back
Cl. 5 — Proper adhesive application technique
OK
NC
NA
HOLD
A2Adhesive coverage on tile back (minimum 90% contact)
Acceptance: Adhesive coverage ≥90% verified by random bond strength tests
Cl. 5.1 — Full adhesive contact to prevent hollow areas
OK
NC
NA
HOLD
A3Adhesive freshness and consistency during application
Acceptance: Adhesive mixed fresh, no skinning, consistent workability
Cl. 5.2 — Use adhesive within pot life
OK
NC
NA
HOLD
A4Adhesive thickness (typically 3-5 mm after pressing tile)
Acceptance: Adhesive bed 3-5 mm thick, uniform across tile surface
Cl. 5.3 — Adequate bed thickness for load distribution
OK
NC
NA
HOLD
B. TILE PLACEMENT & LEVELING
B1Tile alignment and straightness (using straightedge/level)
Acceptance: Variation ≤2 mm in 1 m length, no lippage between adjacent tiles
Cl. 6 — Tiles must be level and aligned
OK
NC
NA
HOLD
B2Joint spacing consistency (uniform gaps between tiles)
Acceptance: Joint width variation ±1 mm from nominal, spacers used
Cl. 6.1 — Regular joint widths for aesthetic and structural integrity
OK
NC
NA
HOLD
B3Tile pressing and embedding (adequate pressure application)
Acceptance: Tiles pressed by hand/beater until adhesive squeezes at joints
Cl. 6.2 — Tiles must be firmly embedded without air gaps
OK
NC
NA
HOLD
B4Vertical levels and slopes (if sloped floor design)
Acceptance: Slope ±1:100 from design, verified with level and straightedge
Cl. 6.3 — Maintain design slope for drainage
OK
NC
NA
HOLD
B5Edge and boundary treatments (cut tiles, trim pieces)
Acceptance: Cut edges smooth, no chipping >2 mm, boundary sealed properly
Cl. 7 — Neat edges and proper perimeter finishing
OK
NC
NA
HOLD
C. TILE QUALITY & CONDITION
C1Visual inspection for cracks, chips, and defects in tiles
Acceptance: No visible cracks, chips >2 mm, or manufacturing defects
Cl. 3 — Defective tiles shall not be laid
OK
NC
NA
HOLD
C2Color and finish matching across batch (no apparent shade variation)
Acceptance: Color variation within acceptable range per approved sample
Cl. 3.1 — Consistent appearance across tiles
OK
NC
NA
HOLD
C3Tile dimensions and sizing (verify against specification)
Acceptance: Dimensions ±1% or per IS code, measured on random samples
Cl. 3.2 — Dimensions within tolerance
OK
NC
NA
HOLD
C4Tile flatness (warping, curvature check)
Acceptance: Flatness variation ≤0.5 mm per tile, verified with straightedge
Cl. 3.3 — Tiles must be flat for proper laying
OK
NC
NA
HOLD
Showing 13 of 20 checkpoints ·
A. ADHESIVE APPLICATION & COVERAGE
A1Adhesive application method (notched trowel, correct angle and pressure)
Cl. 5 — Proper adhesive application technique (IS 1237)
Notched trowel (6-10 mm) at 45°, continuous coverage >90% of tile back
OKNCNAHOLD
A2Adhesive coverage on tile back (minimum 90% contact)
Cl. 5.1 — Full adhesive contact to prevent hollow areas (IS 1237)
Adhesive coverage ≥90% verified by random bond strength tests
OKNCNAHOLD
A3Adhesive freshness and consistency during application
Cl. 5.2 — Use adhesive within pot life (IS 1237)
Adhesive mixed fresh, no skinning, consistent workability
OKNCNAHOLD
A4Adhesive thickness (typically 3-5 mm after pressing tile)
Cl. 5.3 — Adequate bed thickness for load distribution (IS 1237)
Adhesive bed 3-5 mm thick, uniform across tile surface
OKNCNAHOLD
B. TILE PLACEMENT & LEVELING
B1Tile alignment and straightness (using straightedge/level)
Cl. 6 — Tiles must be level and aligned (IS 1237)
Variation ≤2 mm in 1 m length, no lippage between adjacent tiles
OKNCNAHOLD
B2Joint spacing consistency (uniform gaps between tiles)
Cl. 6.1 — Regular joint widths for aesthetic and structural integrity (IS 1237)
Joint width variation ±1 mm from nominal, spacers used
OKNCNAHOLD
B3Tile pressing and embedding (adequate pressure application)
Cl. 6.2 — Tiles must be firmly embedded without air gaps (IS 1237)
Tiles pressed by hand/beater until adhesive squeezes at joints
OKNCNAHOLD
B4Vertical levels and slopes (if sloped floor design)
Cl. 6.3 — Maintain design slope for drainage (IS 1237)
Slope ±1:100 from design, verified with level and straightedge
OKNCNAHOLD
B5Edge and boundary treatments (cut tiles, trim pieces)
Cl. 7 — Neat edges and proper perimeter finishing (IS 1237)
Cut edges smooth, no chipping >2 mm, boundary sealed properly
OKNCNAHOLD
C. TILE QUALITY & CONDITION
C1Visual inspection for cracks, chips, and defects in tiles
Cl. 3 — Defective tiles shall not be laid (IS 1237)
No visible cracks, chips >2 mm, or manufacturing defects
OKNCNAHOLD
C2Color and finish matching across batch (no apparent shade variation)
Cl. 3.1 — Consistent appearance across tiles (IS 1237)
Color variation within acceptable range per approved sample
OKNCNAHOLD
C3Tile dimensions and sizing (verify against specification)
Cl. 3.2 — Dimensions within tolerance (IS 1237)
Dimensions ±1% or per IS code, measured on random samples
OKNCNAHOLD
C4Tile flatness (warping, curvature check)
Cl. 3.3 — Tiles must be flat for proper laying (IS 1237)
Flatness variation ≤0.5 mm per tile, verified with straightedge
OKNCNAHOLD
Showing 13 of 20 ·
Inspection Sign-Off
APPROVED
APPROVED WITH CONDITIONS
REJECTED
Remarks
Name / Sign / Date
Non-Conformances (if any)
Name / Sign / Date
Corrective Actions Required
Name / Sign / Date
Inspected By
Name / Sign / Date
Reviewed By
Name / Sign / Date