Minimum nominal concrete cover protects reinforcement from corrosion and fire. Cover depends on exposure condition (Table 16) and required fire resistance (Table 16A). Always use the larger of the two.
Quick Lookup โ By Exposure
Mild Moderate Severe Very Severe Extreme
30 mm Min M25
Sheltered from severe rain, indoor RCC
Cover for Fire Resistance (Table 16A of IS 456)
Fire rating in hours โ use the larger of durability cover and fire cover
Member 0.5h 1h 1.5h 2h 3h 4h Slab (simply supported) 20 20 25 35 45 55 Slab (continuous) 20 20 20 25 35 45 Beam (simply supported) 20 20 20 40 60 70 Beam (continuous) 20 20 20 30 40 50 Column 40 40 40 40 40 40 Wall (load-bearing) 20 20 25 25 25 25
Practical Notes
โข Nominal cover = clear cover to nearest surface of the outermost reinforcement (including stirrups)
โข Cover to main bar โฅ bar diameter (Clause 26.4.1)
โข For bundled bars, cover โฅ equivalent diameter of the bundle
โข Cover blocks (spacers): use PCC cover blocks, NOT stone/brick pieces
โข Maximum cover should not exceed 75mm unless designed for fire resistance
โข In aggressive environments (coastal, industrial), consider additional 10mm beyond code minimum
โข For precast elements, cover may be reduced by 5mm per IS 456 Clause 26.4.2
โข Tolerance on cover: +10mm, โ0mm (cover must never be less than specified)
โข Always check both durability and fire requirements โ use the LARGER value