| S.No. | Field / Checkpoint | Reference | Status |
|---|---|---|---|
| A. PANEL IDENTIFICATION | |||
| A1 | Panel name + location + voltage rating + main breaker rating (A) Acceptance: Per drawing | Per single-line diagram (SLD) | OK NC NA |
| A2 | Incoming source (transformer / DG bus) + cable size Acceptance: Per design | Per fault current + load | OK NC NA |
| A3 | Earthing — system + equipment Acceptance: Per IS 3043 | TT / TN / IT system | OK NC NA |
| B. OUTGOING CIRCUITS | |||
| B1 | Circuit no. + load name + rated A + MCB / MCCB type Acceptance: Per drawing | Per design | OK NC NA |
| B2 | Cable size + length + insulation + termination Acceptance: Per IS 732 | Per current rating + voltage drop | OK NC NA |
| B3 | Phase allocation (R / Y / B) + neutral balance Acceptance: Computed | Phase balance ± 10% | OK NC NA |
| C. PROTECTION + METERING | |||
| C1 | Earth leakage protection (RCD / ELCB) per circuit Acceptance: Per code | 30 mA for socket circuits per IS 732 | OK NC NA |
| C2 | Energy meter + CT/PT class + display Acceptance: Per drawing | Per spec | OK NC NA |
| C3 | Surge protection device (SPD) Acceptance: Per spec | Per IS 16942 | OK NC NA |