QA/QC  › Electrical Installations  › Conduit & Wiring
Checklist · QC-ELC-CHK-001
Conduit & Wiring Installation Checklist
28 checkpoints across 5 sections. During conduit routing, cable laying, and pre-commissioning of wiring installation
28 Checkpoints
5 Sections
Per building section or phase
QC Engineer, Site Engineer

Checklist Preview

S.No.CheckpointIS RequirementStatus
A. CONDUIT INSTALLATION
A1Conduit is properly secured at intervals not exceeding 1.5 m for horizontal runs
Acceptance: Support spacing ≤ 1.5 m, no sagging observed
Cl. 7.2.1 — Conduit support spacing
OK
NC
NA
HOLD
A2Conduit bends have minimum bend radius of 6 times conduit diameter
Acceptance: All bends: radius ≥ 6D, no flattening or cracking
Cl. 7.2.2 — Bend radius
OK
NC
NA
HOLD
A3Conduit is grounded/bonded at both ends and intermediate boxes
Acceptance: Earth resistance ≤ 1 Ω measured between boxes
Cl. 8.3.1 — Earth continuity
OK
NC
NA
HOLD
A4Conduit routing avoids sharp edges; cable glands or sleeves fitted where required
Acceptance: All cable entry points protected, no sharp edges, glands fitted
Cl. 7.1.3 — Mechanical protection
OK
NC
NA
HOLD
A5Conduit fill ratio does not exceed 40% of conduit cross-sectional area
Acceptance: Cable bundle diameter ≤ 0.4 × conduit ID
Cl. 7.2.3 — Conduit fill
OK
NC
NA
HOLD
A6Conduit boxes are accessible and properly sized for number of cables
Acceptance: Box volume adequate, all cables accessible, no cramping
Cl. 7.3.1 — Box sizing
OK
NC
NA
HOLD
B. CABLE SELECTION & MARKING
B1Cables are IS-marked (ISI mark or equivalent) for voltage and temperature rating
Acceptance: ISI mark visible, voltage ≥ rated circuit voltage, temperature rating ≥ ambient + 10°C
Cl. 6.1.1 — Cable certification
OK
NC
NA
HOLD
B2Cable size is appropriate for load current and is not corroded or damaged
Acceptance: Cable area per design, insulation intact, no burn marks or moisture
Cl. 6.3.1 — Cable sizing
OK
NC
NA
HOLD
B3Each cable is properly labeled at source and distribution points (circuit ID)
Acceptance: Labels legible, match circuit drawings, permanent marking used
Cl. 8.1.2 — Cable identification
OK
NC
NA
HOLD
B4Cable color-coding follows standard (Brown/Red: Phase, Black: Neutral, Green: Earth)
Acceptance: All phase, neutral, earth wires correctly identified by color
Cl. 6.2.1 — Color identification
OK
NC
NA
HOLD
B5Cable insulation resistance tested before energization
Acceptance: Megger reading ≥ 1 MΩ, recorded and documented
Cl. 11.1 — Pre-commissioning test
OK
NC
NA
HOLD
C. CABLE ROUTING & SPACING
C1Power cables are segregated from control/signal cables by minimum 300 mm
Acceptance: Separation distance ≥ 300 mm measured center-to-center
Cl. 7.4.1 — EMI prevention
OK
NC
NA
HOLD
C2Cables routed away from water sources, high-temperature pipes (min. 300 mm clearance)
Acceptance: Minimum 300 mm clearance from pipes/heat sources, above water level in trenches
Cl. 7.1.1 — Environmental protection
OK
NC
NA
HOLD
C3Cable trays are properly supported and not overloaded
Acceptance: Support spacing ≤ 1.5 m, cable bundle weight within tray capacity
Cl. 7.5.2 — Cable tray design
OK
NC
NA
HOLD
C4Cables are not pinched or under mechanical stress at connection points
Acceptance: No visible stress marks, cables lay flat and relaxed at terminations
Cl. 8.2.2 — Termination method
OK
NC
NA
HOLD
C5Cables in wet areas (bathrooms, kitchens) are routed at height ≥ 1.3 m from floor
Acceptance: Minimum height 1.3 m from floor in wet areas, conduit properly sealed
Cl. 7.6.2 — Wet location protection
OK
NC
NA
HOLD
C6Cable entries at panels/boxes have proper grommet or bushing to prevent abrasion
Acceptance: Grommets in place, no exposed edges, cable jacket intact
Cl. 8.2.1 — Cable protection
OK
NC
NA
HOLD
C7Loose or excess cable is coiled and secured; no kinks or twisted sections
Acceptance: Coil radius ≥ 6 × cable diameter, no kinks, secured with cable ties every 0.5 m
Cl. 7.2.4 — Cable storage
OK
NC
NA
HOLD
C8Conduit/tray routing does not interfere with structural elements or other services
Acceptance: No clashing with HVAC, plumbing, or structural members confirmed against drawings
Cl. 7.1.2 — Co-location rules
OK
NC
NA
HOLD
Showing 19 of 28 checkpoints ·
A. CONDUIT INSTALLATION
A1Conduit is properly secured at intervals not exceeding 1.5 m for horizontal runs
Cl. 7.2.1 — Conduit support spacing (IS 732)
Support spacing ≤ 1.5 m, no sagging observed
OKNCNAHOLD
A2Conduit bends have minimum bend radius of 6 times conduit diameter
Cl. 7.2.2 — Bend radius (IS 732)
All bends: radius ≥ 6D, no flattening or cracking
OKNCNAHOLD
A3Conduit is grounded/bonded at both ends and intermediate boxes
Cl. 8.3.1 — Earth continuity (IS 732)
Earth resistance ≤ 1 Ω measured between boxes
OKNCNAHOLD
A4Conduit routing avoids sharp edges; cable glands or sleeves fitted where required
Cl. 7.1.3 — Mechanical protection (IS 732)
All cable entry points protected, no sharp edges, glands fitted
OKNCNAHOLD
A5Conduit fill ratio does not exceed 40% of conduit cross-sectional area
Cl. 7.2.3 — Conduit fill (IS 732)
Cable bundle diameter ≤ 0.4 × conduit ID
OKNCNAHOLD
A6Conduit boxes are accessible and properly sized for number of cables
Cl. 7.3.1 — Box sizing (IS 732)
Box volume adequate, all cables accessible, no cramping
OKNCNAHOLD
B. CABLE SELECTION & MARKING
B1Cables are IS-marked (ISI mark or equivalent) for voltage and temperature rating
Cl. 6.1.1 — Cable certification (IS 694, IS 1554)
ISI mark visible, voltage ≥ rated circuit voltage, temperature rating ≥ ambient + 10°C
OKNCNAHOLD
B2Cable size is appropriate for load current and is not corroded or damaged
Cl. 6.3.1 — Cable sizing (IS 732)
Cable area per design, insulation intact, no burn marks or moisture
OKNCNAHOLD
B3Each cable is properly labeled at source and distribution points (circuit ID)
Cl. 8.1.2 — Cable identification (IS 732)
Labels legible, match circuit drawings, permanent marking used
OKNCNAHOLD
B4Cable color-coding follows standard (Brown/Red: Phase, Black: Neutral, Green: Earth)
Cl. 6.2.1 — Color identification (IS 732)
All phase, neutral, earth wires correctly identified by color
OKNCNAHOLD
B5Cable insulation resistance tested before energization
Cl. 11.1 — Pre-commissioning test (IS 732)
Megger reading ≥ 1 MΩ, recorded and documented
OKNCNAHOLD
C. CABLE ROUTING & SPACING
C1Power cables are segregated from control/signal cables by minimum 300 mm
Cl. 7.4.1 — EMI prevention (IS 732)
Separation distance ≥ 300 mm measured center-to-center
OKNCNAHOLD
C2Cables routed away from water sources, high-temperature pipes (min. 300 mm clearance)
Cl. 7.1.1 — Environmental protection (IS 732)
Minimum 300 mm clearance from pipes/heat sources, above water level in trenches
OKNCNAHOLD
C3Cable trays are properly supported and not overloaded
Cl. 7.5.2 — Cable tray design (IS 732)
Support spacing ≤ 1.5 m, cable bundle weight within tray capacity
OKNCNAHOLD
C4Cables are not pinched or under mechanical stress at connection points
Cl. 8.2.2 — Termination method (IS 732)
No visible stress marks, cables lay flat and relaxed at terminations
OKNCNAHOLD
C5Cables in wet areas (bathrooms, kitchens) are routed at height ≥ 1.3 m from floor
Cl. 7.6.2 — Wet location protection (IS 732)
Minimum height 1.3 m from floor in wet areas, conduit properly sealed
OKNCNAHOLD
C6Cable entries at panels/boxes have proper grommet or bushing to prevent abrasion
Cl. 8.2.1 — Cable protection (IS 732)
Grommets in place, no exposed edges, cable jacket intact
OKNCNAHOLD
C7Loose or excess cable is coiled and secured; no kinks or twisted sections
Cl. 7.2.4 — Cable storage (IS 732)
Coil radius ≥ 6 × cable diameter, no kinks, secured with cable ties every 0.5 m
OKNCNAHOLD
C8Conduit/tray routing does not interfere with structural elements or other services
Cl. 7.1.2 — Co-location rules (IS 732)
No clashing with HVAC, plumbing, or structural members confirmed against drawings
OKNCNAHOLD
Showing 19 of 28 ·
Inspection Sign-Off
APPROVED
APPROVED WITH CONDITIONS
REJECTED — NCR RAISED
Remarks
Name / Sign / Date
Inspected By
Name / Sign / Date
Reviewed By
Name / Sign / Date