QA/QC  › Roads & Pavement  › Bitumen Property Tests
Test-report · QC-ROD-TST-002
Bitumen Property Tests Report
18 checkpoints across 6 sections. For every bitumen consignment; source quality assurance before placement
18 Checkpoints
6 Sections
Per bitumen lot/batch delivery; minimum once per project phase
Testing Laboratory, QC Engineer

Checklist Preview

S.No.CheckpointIS RequirementStatus
A. PENETRATION TEST (IS 1203)
A1Penetration test conducted per IS 1203; 100g standard needle, 25°C, 5 sec loading
Acceptance: Test at 25°C ±0.5°C; 5 sec loading; needle 100g ±0.5g; result in 0.1mm units
Cl. 501 — Test procedure
A2Penetration value measured (0.1mm units); result documented
Acceptance: 60/70 grade: 60-70; 80/100: 80-100; 100/120: 100-120; 150/200: 150-200 (dmm)
Cl. 501 — Measurement recording
A3Three test specimens prepared and measured; average and standard deviation calculated
Acceptance: Three measurements; standard deviation <2 dmm; result = average of three
Cl. 501 — Statistical analysis
B. SOFTENING POINT TEST (IS 1205)
B1Softening point test conducted per IS 1205 (Ring and Ball method); test at atmospheric pressure
Acceptance: Ring and ball apparatus; heating rate 5°C/min; end point when ball passes through ring
Cl. 501 — Test procedure
B2Softening point temperature recorded (°C); two test samples prepared
Acceptance: 60/70 grade: 46-56°C; 80/100: 47-57°C; measured at ±0.5°C precision
Cl. 501 — Temperature measurement
B3Average softening point calculated from two samples; result documented
Acceptance: Average of two tests; difference <2°C between samples; if >2°C, repeat test
Cl. 501 — Result calculation
C. DUCTILITY TEST (IS 1208)
C1Ductility test conducted per IS 1208; briquette mold, constant extension rate 5 cm/min, 25°C
Acceptance: Test at 25°C; extension rate 5 cm/min; temperature maintained ±0.5°C
Cl. 501 — Test procedure
C2Ductility measured as elongation (cm) before thread breaks; result recorded
Acceptance: 60/70 & 80/100 grade: ≥75 cm at 25°C minimum; measured to 0.1cm precision
Cl. 501 — Measurement recording
C3Two specimens tested; elongation values recorded separately; result = lower value reported
Acceptance: Two samples minimum; report lower value; if <75 cm, batch rejected for poor ductility
Cl. 501 — Sample testing
Showing 9 of 18 checkpoints ·
A. PENETRATION TEST (IS 1203)
A1Penetration test conducted per IS 1203; 100g standard needle, 25°C, 5 sec loading
Cl. 501 — Test procedure (IS 1203)
Test at 25°C ±0.5°C; 5 sec loading; needle 100g ±0.5g; result in 0.1mm units
A2Penetration value measured (0.1mm units); result documented
Cl. 501 — Measurement recording (IS 1203)
60/70 grade: 60-70; 80/100: 80-100; 100/120: 100-120; 150/200: 150-200 (dmm)
A3Three test specimens prepared and measured; average and standard deviation calculated
Cl. 501 — Statistical analysis (IS 1203)
Three measurements; standard deviation <2 dmm; result = average of three
B. SOFTENING POINT TEST (IS 1205)
B1Softening point test conducted per IS 1205 (Ring and Ball method); test at atmospheric pressure
Cl. 501 — Test procedure (IS 1205)
Ring and ball apparatus; heating rate 5°C/min; end point when ball passes through ring
B2Softening point temperature recorded (°C); two test samples prepared
Cl. 501 — Temperature measurement (IS 1205)
60/70 grade: 46-56°C; 80/100: 47-57°C; measured at ±0.5°C precision
B3Average softening point calculated from two samples; result documented
Cl. 501 — Result calculation (IS 1205)
Average of two tests; difference <2°C between samples; if >2°C, repeat test
C. DUCTILITY TEST (IS 1208)
C1Ductility test conducted per IS 1208; briquette mold, constant extension rate 5 cm/min, 25°C
Cl. 501 — Test procedure (IS 1208)
Test at 25°C; extension rate 5 cm/min; temperature maintained ±0.5°C
C2Ductility measured as elongation (cm) before thread breaks; result recorded
Cl. 501 — Measurement recording (IS 1208)
60/70 & 80/100 grade: ≥75 cm at 25°C minimum; measured to 0.1cm precision
C3Two specimens tested; elongation values recorded separately; result = lower value reported
Cl. 501 — Sample testing (IS 1208)
Two samples minimum; report lower value; if <75 cm, batch rejected for poor ductility
Showing 9 of 18 ·
Inspection Sign-Off
ACCEPTED
ACCEPTED WITH CONDITIONS
REJECTED
Test Conducted By
Name / Sign / Date
Reviewed By
Name / Sign / Date
Lab Head
Name / Sign / Date