QA/QC  › Plumbing & Water Supply  › Plumbing Fixture Installation
Checklist · QC-PLB-CHK-003
Plumbing Fixture Installation Checklist
19 checkpoints across 6 sections. After fixture installation; before building handover
19 Checkpoints
6 Sections
Per unit/zone
QC Engineer, Plumbing Supervisor

Checklist Preview

S.No.CheckpointIS RequirementStatus
A. FIXTURE MOUNTING & INSTALLATION
A1Washbasin/sink/bathtub securely mounted to wall/floor; no movement when pushed or loaded (20 kg force)
Acceptance: Fixture does not shift under hand pressure, bolts/fasteners tight, no cracks on fixture or mounting surface
Cl. 15.1 — Installation security
OK
NC
NA
HOLD
A2WC pan properly seated on floor; sealant applied around base to prevent water seepage into subfloor
Acceptance: WC bolted to floor, sealant (silicone/tile adhesive) applied around perimeter, cured before use
Cl. 15.2 — WC base sealing
OK
NC
NA
HOLD
A3Fixture surface is free from chips, cracks, or manufacturing defects; glaze intact and smooth
Acceptance: Visual inspection for damage, no chips or cracks, surface glaze uniform, minor wear acceptable
Cl. 15.3 — Physical condition
OK
NC
NA
HOLD
B. WATER INLET CONNECTIONS
B1Cold water inlet connected to dedicated cold water line (not mixed with hot water incorrectly routed)
Acceptance: Inlet traced to cold water supply, not connected to wrong source, valve operation verified
Cl. 16.1 — Source verification
OK
NC
NA
HOLD
B2Hot water inlet (if dual inlet) connected to hot water supply; temperature check conducted (40-50°C at outlet)
Acceptance: Hot water supply verified, temperature measured at outlet ≥40°C, thermostat valve present if required
Cl. 16.2 — Hot water verification
OK
NC
NA
HOLD
B3Inlet pipes properly connected; unions/compression fittings tight, no leakage when water turned on
Acceptance: Connections tight, tested at operating pressure, zero seepage at union/fitting, dry interface after 5 min
Cl. 16.3 — Connection integrity
OK
NC
NA
HOLD
B4Isolating valve (stop cock) provided on each inlet line; accessible and operable
Acceptance: Stop valve present and accessible, operation tested (ON/OFF smooth), handle/knob not obstructed
Cl. 16.4 — Isolation provision
OK
NC
NA
HOLD
C. DRAINAGE OUTLET CONNECTIONS
C1Drainage outlet properly connected to trap or P-bend; pipe diameter ≥32 mm for washbasin, ≥40 mm for bathtub
Acceptance: Drain pipe size adequate for fixture type, trap installed immediately after outlet, diameter matches fixture requirement
Cl. 17.1 — Drain sizing
OK
NC
NA
HOLD
C2P-bend or S-bend trap properly installed; water seal maintained (min. 50 mm seal depth per design)
Acceptance: Water seal depth ≥50 mm visually confirmed, trap not siphoned, scent seal present if required
Cl. 17.2 — Trap sealing
OK
NC
NA
HOLD
C3Drain flows freely; no blockage or backflow observed during flow test
Acceptance: Drain empties within 10 seconds, no gurgling or slow drain, no backflow into fixture
Cl. 17.3 — Drainage functionality
OK
NC
NA
HOLD
C4Overflow provision (if applicable): connected to drain system, not blocked
Acceptance: Overflow outlet clear, directed to drain system, not exposed to floor, prevents water damage
Cl. 17.4 — Overflow safety
OK
NC
NA
HOLD
Showing 11 of 19 checkpoints ·
A. FIXTURE MOUNTING & INSTALLATION
A1Washbasin/sink/bathtub securely mounted to wall/floor; no movement when pushed or loaded (20 kg force)
Cl. 15.1 — Installation security (IS 2065)
Fixture does not shift under hand pressure, bolts/fasteners tight, no cracks on fixture or mounting surface
OKNCNAHOLD
A2WC pan properly seated on floor; sealant applied around base to prevent water seepage into subfloor
Cl. 15.2 — WC base sealing (IS 2065)
WC bolted to floor, sealant (silicone/tile adhesive) applied around perimeter, cured before use
OKNCNAHOLD
A3Fixture surface is free from chips, cracks, or manufacturing defects; glaze intact and smooth
Cl. 15.3 — Physical condition (IS 2065)
Visual inspection for damage, no chips or cracks, surface glaze uniform, minor wear acceptable
OKNCNAHOLD
B. WATER INLET CONNECTIONS
B1Cold water inlet connected to dedicated cold water line (not mixed with hot water incorrectly routed)
Cl. 16.1 — Source verification (IS 2065)
Inlet traced to cold water supply, not connected to wrong source, valve operation verified
OKNCNAHOLD
B2Hot water inlet (if dual inlet) connected to hot water supply; temperature check conducted (40-50°C at outlet)
Cl. 16.2 — Hot water verification (IS 10500)
Hot water supply verified, temperature measured at outlet ≥40°C, thermostat valve present if required
OKNCNAHOLD
B3Inlet pipes properly connected; unions/compression fittings tight, no leakage when water turned on
Cl. 16.3 — Connection integrity (IS 2065)
Connections tight, tested at operating pressure, zero seepage at union/fitting, dry interface after 5 min
OKNCNAHOLD
B4Isolating valve (stop cock) provided on each inlet line; accessible and operable
Cl. 16.4 — Isolation provision (IS 2065)
Stop valve present and accessible, operation tested (ON/OFF smooth), handle/knob not obstructed
OKNCNAHOLD
C. DRAINAGE OUTLET CONNECTIONS
C1Drainage outlet properly connected to trap or P-bend; pipe diameter ≥32 mm for washbasin, ≥40 mm for bathtub
Cl. 17.1 — Drain sizing (IS 2065)
Drain pipe size adequate for fixture type, trap installed immediately after outlet, diameter matches fixture requirement
OKNCNAHOLD
C2P-bend or S-bend trap properly installed; water seal maintained (min. 50 mm seal depth per design)
Cl. 17.2 — Trap sealing (IS 2065)
Water seal depth ≥50 mm visually confirmed, trap not siphoned, scent seal present if required
OKNCNAHOLD
C3Drain flows freely; no blockage or backflow observed during flow test
Cl. 17.3 — Drainage functionality (IS 2065)
Drain empties within 10 seconds, no gurgling or slow drain, no backflow into fixture
OKNCNAHOLD
C4Overflow provision (if applicable): connected to drain system, not blocked
Cl. 17.4 — Overflow safety (IS 2065)
Overflow outlet clear, directed to drain system, not exposed to floor, prevents water damage
OKNCNAHOLD
Showing 11 of 19 ·
Inspection Sign-Off
APPROVED FOR HANDOVER
APPROVED WITH REMEDIAL WORK
REJECTED — MAJOR DEFECTS
Remarks
Name / Sign / Date
Inspected By
Name / Sign / Date
Reviewed By
Name / Sign / Date