QA/QC  › Masonry & Bricks  › Brick Compressive Strength
Test-report · QC-MAS-TST-001
Brick Compressive Strength Test Report
7 checkpoints across 4 sections. At brick delivery; periodic verification
7 Checkpoints
4 Sections
Per delivery
Testing Laboratory, QC Engineer

Checklist Preview

S.No.CheckpointIS RequirementStatus
A. SAMPLE PREPARATION
A1Representative bricks selected; minimum 5 bricks tested per batch
Acceptance: Random selection; quality range verified; measurements taken
Cl. 3 — Sampling
OK
NC
NA
HOLD
A2Brick surfaces prepared: bedded in 10-12 mm cement mortar on compression plates
Acceptance: Mortar 1:3 cement:sand; surfaces level; cured 24 hours before testing
Cl. 4.1 — Specimen preparation
OK
NC
NA
HOLD
B. COMPRESSION TESTING
B1Testing machine calibrated per ASTM/ISO standards; accuracy ±1%
Acceptance: Machine certified; load rate 14±2 N/mm²/min; centered loading
Cl. 5 — Equipment
OK
NC
NA
HOLD
B2Load applied uniformly until brick fails; failure load recorded in kN
Acceptance: Constant rate; no shock; failure point noted; load measured to 0.1 kN
Cl. 5.1 — Loading procedure
OK
NC
NA
HOLD
C. STRENGTH CALCULATION & RESULTS
C1Compressive strength calculated: Strength (N/mm²) = Ultimate Load (N) / Bearing Area (mm²)
Acceptance: Strength in MPa; average of 5 bricks; standard deviation calculated
Cl. 6 — Calculation
OK
NC
NA
HOLD
C2Results compared with IS 1077 classification (Class A: min 15 MPa, Class B: min 10 MPa)
Acceptance: Class A: ≥15 MPa; Class B: ≥10 MPa; results meet specification
Cl. 6.1 — Classification
OK
NC
NA
HOLD
Showing 6 of 7 checkpoints ·
A. SAMPLE PREPARATION
A1Representative bricks selected; minimum 5 bricks tested per batch
Cl. 3 — Sampling (IS 3495)
Random selection; quality range verified; measurements taken
OKNCNAHOLD
A2Brick surfaces prepared: bedded in 10-12 mm cement mortar on compression plates
Cl. 4.1 — Specimen preparation (IS 3495)
Mortar 1:3 cement:sand; surfaces level; cured 24 hours before testing
OKNCNAHOLD
B. COMPRESSION TESTING
B1Testing machine calibrated per ASTM/ISO standards; accuracy ±1%
Cl. 5 — Equipment (IS 3495)
Machine certified; load rate 14±2 N/mm²/min; centered loading
OKNCNAHOLD
B2Load applied uniformly until brick fails; failure load recorded in kN
Cl. 5.1 — Loading procedure (IS 3495)
Constant rate; no shock; failure point noted; load measured to 0.1 kN
OKNCNAHOLD
C. STRENGTH CALCULATION & RESULTS
C1Compressive strength calculated: Strength (N/mm²) = Ultimate Load (N) / Bearing Area (mm²)
Cl. 6 — Calculation (IS 3495)
Strength in MPa; average of 5 bricks; standard deviation calculated
OKNCNAHOLD
C2Results compared with IS 1077 classification (Class A: min 15 MPa, Class B: min 10 MPa)
Cl. 6.1 — Classification (IS 1077)
Class A: ≥15 MPa; Class B: ≥10 MPa; results meet specification
OKNCNAHOLD
Showing 6 of 7 ·
Inspection Sign-Off
APPROVED
REJECTED
Remarks
Name / Sign / Date
Tested By
Name / Sign / Date
Reviewed By
Name / Sign / Date