Test-report · QC-HVC-TST-001
Air Flow Measurement Test Report
6 checkpoints across 5 sections. Post-duct installation and system commissioning; TAB (Testing, Adjusting, Balancing) verification
6 Checkpoints
5 Sections
During commissioning; annual verification
QC Engineer, HVAC Commissioning Specialist

Checklist Preview

S.No.CheckpointIS RequirementStatus
A. SUPPLY AIR FLOW MEASUREMENT
A1Supply air flow measured at main outlet or supply plenum; flow meter or anemometer readings recorded
Acceptance: Flow measured in m³/s or CFM; ≥95% of design flow rate acceptable; measurement method and meter calibration documented
Cl. 4.1 — Main supply flow
OK
NC
NA
HOLD
A2Static pressure drop measured from plenum to room outlets (differential pressure gauge)
Acceptance: Pressure drop measured in Pa; acceptable range typically 50-200 Pa depending on duct design; documented
Cl. 4.2 — Pressure drop assessment
OK
NC
NA
HOLD
B. RETURN AIR FLOW MEASUREMENT
B1Return air flow measured at return plenum or main return duct; values recorded and compared with supply flow
Acceptance: Return flow ≈ Supply flow (within ±5% tolerance); if exhaust present, return + exhaust = supply ±5%
Cl. 5.1 — Return flow measurement
OK
NC
NA
HOLD
C. EXHAUST AIR FLOW MEASUREMENT
C1Exhaust air flow measured at exhaust outlet (if applicable); flow rate recorded
Acceptance: Exhaust flow ≥ minimum required per design (typically 10-30% of supply); measurement documented
Cl. 6.1 — Exhaust flow measurement
OK
NC
NA
HOLD
Showing 4 of 6 checkpoints ·
A. SUPPLY AIR FLOW MEASUREMENT
A1Supply air flow measured at main outlet or supply plenum; flow meter or anemometer readings recorded
Cl. 4.1 — Main supply flow (IS 3103:2017)
Flow measured in m³/s or CFM; ≥95% of design flow rate acceptable; measurement method and meter calibration documented
OKNCNAHOLD
A2Static pressure drop measured from plenum to room outlets (differential pressure gauge)
Cl. 4.2 — Pressure drop assessment (IS 3103:2017)
Pressure drop measured in Pa; acceptable range typically 50-200 Pa depending on duct design; documented
OKNCNAHOLD
B. RETURN AIR FLOW MEASUREMENT
B1Return air flow measured at return plenum or main return duct; values recorded and compared with supply flow
Cl. 5.1 — Return flow measurement (IS 3103:2017)
Return flow ≈ Supply flow (within ±5% tolerance); if exhaust present, return + exhaust = supply ±5%
OKNCNAHOLD
C. EXHAUST AIR FLOW MEASUREMENT
C1Exhaust air flow measured at exhaust outlet (if applicable); flow rate recorded
Cl. 6.1 — Exhaust flow measurement (IS 3103:2017)
Exhaust flow ≥ minimum required per design (typically 10-30% of supply); measurement documented
OKNCNAHOLD
Showing 4 of 6 ·
Inspection Sign-Off
PASS
FAIL
PASS WITH ADJUSTMENTS
Test Summary
Name / Sign / Date
Tested By
Name / Sign / Date
Reviewed By
Name / Sign / Date