🔲Footing Design Calculator

Isolated square RCC footing per IS 456:2000 — size, depth, reinforcement, one-way + punching shear checks.

📍 Mumbai · Zone III · M25 · Fe500D · ⚡ IS 13920
Design context
📍 Mumbai🌍 Zone III · Moderate🧪 Moderate🧱 M25 · Fe500D · 30 mm cover⚡ IS 13920
💡Pre-filled with a typical example — change any value to recompute instantly.
⚖️Column & Loading
Soil
🧱Materials (from Design Context)
Materials (from context)🧱 M25Fe500D📏 30 mm⚡ IS 13920
Edit ↑
Safe ✓
Utilization -4383% · 1-way: OK · 2-way: OK
Footing Size
0.10m × 0.10m
Total Depth
240 mm
Soil Pressure
80000.0 kN/m²
Reinforcement
16φ @ 75mm B.W.
One-Way Shear
τv=-120.00 ✓
Punching Shear
τv=-54.78 ✓
InfraLens · Reinforcement Drawing
RCC Isolated Footing 100 × 100 × 240 mm
PROJECT: Untitled project
DATE: 24 Apr 2026
MATERIALS: M25 · Fe500D · Cover 30 mm · SBC 150 kN/m²
LEGEND:ConcreteMain rebar (dot in section)Main rebar (line in elevation)Top / distribution rebar (dashed)Stirrup / tieASection cut marker
PLAN
Showing bottom reinforcement mesh
ColAA100100300F1 · 16φ @ 75 c/c B.W.300×450 COL
Scale 1:40
SECTION A-A
Through column centre-line
Column stub100240F1 · 16φ @ 75 c/c B.W.GLCOLUMN
Scale 1:30
GENERAL NOTES
  1. All dimensions in millimetres unless noted.
  2. Concrete grade: M25. Reinforcement: Fe500D. Clear cover: 30 mm.
  3. Safe bearing capacity (SBC) assumed = 150 kN/m² at founding depth.
  4. Factored soil pressure = 80000.0 kN/m².
  5. One-way shear: τv = -120.00 N/mm² — OK.
  6. Two-way (punching) shear: τv = -54.78 N/mm² — OK.
  7. Provide 75 mm PCC (M10 mix) below footing as levelling layer.
  8. Founding level to be decided after verifying bearing stratum in pit.
  9. Column starter bars to extend Ld + 600 mm into footing; dowel tie grid as per column schedule.
BAR BENDING SCHEDULE
MarkDiaShapeABL (mm)No.Wt (kg)
F116φ4016036021.14
TOTAL21.14 kg
Preliminary design — verify with detailed analysis per IS 456:2000.infralens.in · Drawing generated 24/4/2026
● Step-by-Step Calculation
1
Footing Size
IS 456 Cl. 34
Service load = Pu/1.5 = 533.3 kN Area = P/SBC = 533.3/150 = 0.00 m² Side = √0.00 = 0.06m
Provide 0.10m × 0.10m square footing
2
Net Soil Pressure
qu = Pu / (L×B) = 800 / (0.10×0.10)
qu = 80000.0 kN/m² (factored)
3
Depth for Shear
IS 456 Cl. 31.6, Cl. 34.2
One-way: τv = -120.00 N/mm² Two-way: τv = -54.78 N/mm² Allowable punching = 0.25√fck = 1.25 N/mm²
Effective depth d = 200mm, Total D = 240mm
4
Reinforcement
IS 456 Cl. 34.2
Mu at face = qu × l² / 2 = 80000.0 × -0.10² / 2 = 400.00 kN·m/m
16mm @ 75mm c/c both ways (Ast = 2681 mm²/m)
Related IS 456 Clauses
Cl. 38.1 · FlexureCl. 39.3 · ColumnCl. 40.1 · ShearCl. 40.4 · StirrupsCl. 43.1 · DeflectionCl. 26.2.1 · LdCl. 26.4 · Cover
Preliminary design only. Verify with detailed analysis per IS 456:2000.
🧮 Mix Design📐 BBS Calc🔩 Steel Tools

How footing design works — IS 456:2000 step by step

Footings transfer the column load safely into the soil. The design has two competing constraints: the footing footprint must keep soil pressure under SBC (a geotechnical limit), and the footing depth must resist punching shear + one-way shear (a structural limit). Punching shear usually governs depth for isolated footings under heavy column loads; bending governs reinforcement.

The calculator above runs the full IS 456 limit-state design for isolated square footings. You enter Pu (factored column load), column dimensions, and SBC; materials come from the Design Context. Output: footing plan size, depth, reinforcement (both directions), one-way shear check (Cl. 34.2.4.1), and two-way punching shear check (Cl. 31.6).

IS 456 clauses applied by the calculator:

  • Footing plan area A = (Pu / 1.5) / SBC × 1.1 (safety margin and conversion from factored to service load).
  • Square footing side: B = √A (rounded up to 50 mm).
  • Net upward soil pressure q = Pu / B² (factored).
  • One-way shear (Cl. 34.2.4.1): shear failure plane at distance d from column face. Check τv ≤ τc (Table 19).
  • Punching shear (Cl. 31.6): check on perimeter d/2 from column face. τv ≤ ks × τc', where τc' = 0.25 × √fck and ks = 0.5 + βc (βc is the column aspect ratio ≤ 1).
  • If punching shear fails → increase depth. This usually governs minimum footing depth for isolated footings.
  • Bending: Mu at column face = q × (B − column_dim)² / 8 per meter width.
  • Bending reinforcement Ast from Mu = 0.87 × fy × Ast × (d − Ast × fy / (0.36 × fck × b)). Distributed both ways for square footing.
  • Nominal cover for footing in contact with soil: 50 mm (mild/moderate), 75 mm (severe) per Cl. 26.4.

Worked example — 800 kN isolated footing

Example inputs

Pu = 800 kN, column 300 × 450 mm, SBC = 150 kN/m², M25 + Fe 500, 50 mm cover. Output: service load ≈ 533 kN. Required area = 533 × 1.1 / 150 = 3.91 m². Side B = 2.0 m → 2.0 × 2.0 m footing. Factored soil pressure q = 800 / 4 = 200 kN/m². One-way shear at d from face: d required ≈ 350 mm. Punching shear check on d/2 perimeter from column face: τv = 0.98 MPa; allowable = ks × 0.25√25 = 1.0 × 1.25 = 1.25 MPa ✓. Depth adopted 400 mm total (350 effective). Bending Mu at face = 200 × (2000 − 300)² / 8000 = 72 kN·m/m. Ast = 580 mm²/m → 12 mm @ 200 mm c/c both ways. Material: 1.6 m³ concrete, 60 kg steel, 2 m² formwork.

Common footing-design mistakes

  • Using assumed SBC without a soil test. Guessing SBC is the single biggest cause of differential settlement. Plate load test or SPT per IS 6403 is mandatory for any building above 2 storeys.
  • Skipping the punching shear check. Bending might pass at 300 mm depth but punching can require 450 mm. Calculator checks both.
  • Using 50 mm cover for footings in direct soil contact when the exposure demands 75 mm. Set Exposure = Severe in Design Context for footings in aggressive soils or high water table.
  • Thin edge (< 150 mm) at the footing tip. IS 456 Cl. 34.1.2: minimum edge depth 150 mm for RCC footings.
  • Ignoring development length. Main bars must develop full Ld from the critical bending section (Cl. 26.2.1). If Ld > footing projection, provide hooks or bend bars up.
  • Centering the column over the footing centroid without accounting for eccentricity. For columns with Mu (biaxial), the footing may need to be rectangular, not square. Calculator handles square only; for eccentric columns use manual calculation.

Footing design FAQs

What SBC should I use for my site?
Never guess — get a geotechnical investigation. Typical: medium-dense sand 150 kN/m², dense sand 200-250, stiff clay 150, hard clay 200, soft rock 450+, soft clay or filled ground 50-100. For any building above 2 storeys, plate load test or SPT per IS 6403 is mandatory. Residential default 150 kN/m².
Why do I need two shear checks?
Per IS 456: One-way shear (Cl. 34.2.4.1) checks shear failure along a vertical plane one effective depth (d) from column face. Two-way / punching shear (Cl. 31.6) checks punching failure along perimeter d/2 from column face. Both must pass — punching usually governs for isolated footings under heavy column loads.
What minimum depth for a footing?
IS 456 Cl. 34.1.2: minimum 150 mm depth at edge for RCC isolated footings. Practical minimum 300 mm total; residential 2-3 storey 400-600 mm; commercial + punching-governed 600-900 mm typical. Calculator computes minimum depth from punching check automatically.
What cover should I use for footing?
IS 456 Cl. 26.4.2: 50 mm for mild/moderate exposure, 75 mm for severe/marine. Footings are buried in direct soil contact, so treat as 'severe' exposure for durability. Design Context auto-applies; override by setting exposure.
Isolated vs combined footing — which do I need?
Isolated works when columns are ≥ 2× footing size apart. If two columns are closer and their footings would overlap, use a combined footing. For weak soils with heavy loads, consider a raft / mat. Combined and raft are on the Tier 2 roadmap.
Is this calculator accurate enough for construction drawings?
Adequate for preliminary design and concept estimates. For final construction drawings submitted to municipal authorities, always run full analysis in software (ETABS + SAFE, STAAD Pro + STAAD Foundation) and have it stamped by a qualified structural engineer.

Related designers, codes, and references

The footing closes the load path that starts at the slab. Check soil properties, verify development length, coordinate with foundation drawings.