IS 8758 : 2000Recommendations for fire precautionary measures in the construction of temporary structures and pandals (BI-LINGUAL)

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
International Comparison — Coming Soon
CurrentSpecializedGuidelinesFire Safety · Fire Safety
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues6InternationalTablesFAQ4Related

IS 8758:2000 is the Indian Standard (BIS) for recommendations for fire precautionary measures in the construction of temporary structures and pandals (bi-lingual). This standard provides recommendations for fire safety measures in the construction and management of temporary structures such as pandals, tents, and exhibition stalls. It covers site planning, materials, exit requirements, electrical safety, and firefighting provisions to prevent fire and ensure public safety during events.

Recommendations for fire precautionary measures in the construction of temporary structures and pandals (BI-LINGUAL)

Overview

Status
Current
Usage level
Specialized
Domain
Fire Safety — Fire Safety
Type
Guidelines
Earlier editions
IS 8758:2013IS 8758:1993
Typically used with
IS 1641IS 1642IS 12777
Also on InfraLens for IS 8758
6Key values1Tables4FAQs
Practical Notes
! Ensure all fabrics and decorative materials are treated with fire-retardant chemicals and certified. Keep certificates available for inspection.
! Pay close attention to electrical wiring. Avoid temporary joints, use proper insulation and circuit protection, and ensure the system is correctly earthed.
! Exits, aisles, and gangways must be kept clear of any obstruction at all times. Exit signage should be prominent and illuminated.
Frequently referenced clauses
Cl. 3Materials of ConstructionCl. 4Planning and SitingCl. 5ExitsCl. 6Electrical InstallationsCl. 7Fire Fighting Arrangements
Pulled from IS 8758:2000. Browse the full clause & table index below in Tables & Referenced Sections.
bambootimberfabrictarpaulinfire retardant

International Equivalents

🌐
International Comparison — Coming Soon
We're adding equivalent international standards for this code.

Key Values6

Quick Reference Values
Minimum clearance from adjacent buildings3 m
Maximum travel distance to an exit22.5 m
Minimum width of any exit or staircase1.5 m
Maximum number of seats in a row with one side aisle7
Maximum number of seats in a row with aisles on both sides14
Minimum clearance between rows of seats (back to back)750 mm

Tables & Referenced Sections

Key Tables
Table 1 - Minimum Width for Exits for Pandals
Key Clauses
Clause 3 - Materials of Construction
Clause 4 - Planning and Siting
Clause 5 - Exits
Clause 6 - Electrical Installations
Clause 7 - Fire Fighting Arrangements

Related Resources on InfraLens

Cross-Referenced Codes
IS 1641:1988Code of practice for fire safety of buildings...
→
IS 1642:1989Code of practice for fire safety of buildings...
→
IS 12777:1989Method for Classification of Flame Spread of ...
→
🧮
Mix Design Calculator
IS 10262 · M20–M50

Frequently Asked Questions4

What is the minimum clearance a pandal should have from another building?+
A minimum of 3 meters should be maintained as open space on all sides of the pandal (Clause 4.1).
What kind of materials are recommended for roofing and side walls?+
Materials should have a Class 1 flame spread rating. If flammable materials like cloth are used, they must be treated with a fire-retardant solution (Clause 3).
What is the maximum travel distance to an exit in a pandal?+
The travel distance from any point to the nearest exit should not exceed 22.5 meters (Clause 5.3).
What are the basic firefighting requirements for a pandal?+
At least one 9-litre water type extinguisher and one 4.5 kg CO2/DCP extinguisher should be provided for every 100 m² of floor area, with a minimum of two pairs per pandal (Clause 7.2).

QA/QC Inspection Templates

📋
QA/QC templates coming soon for this code.
Browse all 300 templates →