IS 8758

: 2000

Recommendations for fire precautionary measures in the construction of temporary structures and pandals (BI-LINGUAL)

CurrentSpecializedGuidelinesFire Safety · Fire Safety
Download PDFBIS PortalGoogle

This standard provides recommendations for fire safety measures in the construction and management of temporary structures such as pandals, tents, and exhibition stalls. It covers site planning, materials, exit requirements, electrical safety, and firefighting provisions to prevent fire and ensure public safety during events.

Recommendations for fire precautionary measures in the construction of temporary structures and pandals (BI-LINGUAL)

Quick Reference Values
Minimum clearance from adjacent buildings3 m
Maximum travel distance to an exit22.5 m
Minimum width of any exit or staircase1.5 m
Maximum number of seats in a row with one side aisle7
Maximum number of seats in a row with aisles on both sides14
Minimum clearance between rows of seats (back to back)750 mm
Practical Notes
Ensure all fabrics and decorative materials are treated with fire-retardant chemicals and certified. Keep certificates available for inspection.
Pay close attention to electrical wiring. Avoid temporary joints, use proper insulation and circuit protection, and ensure the system is correctly earthed.
Exits, aisles, and gangways must be kept clear of any obstruction at all times. Exit signage should be prominent and illuminated.