IS 8758

: 2013

Recommendations for fire precautionary measures in the construction of temporary structures and pandals

CurrentSpecializedCode of PracticeFire Safety · Fire Safety
Download PDFBIS PortalGoogle

This code provides recommendations for fire precautionary measures in the design, construction, and management of temporary structures like pandals and exhibition stalls. It covers site layout, material selection, electrical safety, exit requirements, and firefighting provisions to ensure public safety during events.

Recommendations for fire precautionary measures in the construction of temporary structures and pandals

Quick Reference Values
minimum open space around pandal3 m
minimum distance of kitchen enclosure3 m
maximum travel distance to an exit30 m
minimum exit width1.5 m
exit width per 100 persons50 cm
extinguisher provision per area1 per 500 sq.m
Key Formulas
Cumulative Exit Width (cm) = (Number of Occupants / 100) * 50
Practical Notes
All fabrics, plastics, and decorative materials must be treated with certified fire-retardant chemicals.
Electrical wiring is a primary fire hazard; ensure it is installed by a licensed electrician, properly insulated, and not overloaded.
Maintain clear and unobstructed access for fire tenders and ensure all exit routes are well-lit, marked, and free from blockages at all times.