IS 8758 : 2013Recommendations for fire precautionary measures in the construction of temporary structures and pandals

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
International Comparison — Coming Soon
CurrentSpecializedCode of PracticeFire Safety · Fire Safety
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues6InternationalTablesFAQ4Related

IS 8758:2013 is the Indian Standard (BIS) for recommendations for fire precautionary measures in the construction of temporary structures and pandals. This code provides recommendations for fire precautionary measures in the design, construction, and management of temporary structures like pandals and exhibition stalls. It covers site layout, material selection, electrical safety, exit requirements, and firefighting provisions to ensure public safety during events.

Recommendations for fire precautionary measures in the construction of temporary structures and pandals

Overview

Status
Current
Usage level
Specialized
Domain
Fire Safety — Fire Safety
Type
Code of Practice
Earlier editions
IS 8758:2000IS 8758:1993
Typically used with
IS 1644IS 2190IS 1553
Also on InfraLens for IS 8758
6Key values4FAQs
Practical Notes
! All fabrics, plastics, and decorative materials must be treated with certified fire-retardant chemicals.
! Electrical wiring is a primary fire hazard; ensure it is installed by a licensed electrician, properly insulated, and not overloaded.
! Maintain clear and unobstructed access for fire tenders and ensure all exit routes are well-lit, marked, and free from blockages at all times.
Frequently referenced clauses
Cl. 4Site, Layout and Open SpacesCl. 5Materials of ConstructionCl. 6Electrical Installations and WiringsCl. 7Fire Fighting ArrangementsCl. 9Exits
Pulled from IS 8758:2013. Browse the full clause & table index below in Tables & Referenced Sections.
bambootimberfabricplasticsscaffolding

International Equivalents

🌐
International Comparison — Coming Soon
We're adding equivalent international standards for this code.

Key Values6

Quick Reference Values
minimum open space around pandal3 m
minimum distance of kitchen enclosure3 m
maximum travel distance to an exit30 m
minimum exit width1.5 m
exit width per 100 persons50 cm
extinguisher provision per area1 per 500 sq.m
Key Formulas
Cumulative Exit Width (cm) = (Number of Occupants / 100) * 50

Tables & Referenced Sections

Key Tables
No tables data
Key Clauses
Clause 4 - Site, Layout and Open Spaces
Clause 5 - Materials of Construction
Clause 6 - Electrical Installations and Wirings
Clause 7 - Fire Fighting Arrangements
Clause 9 - Exits

Related Resources on InfraLens

Cross-Referenced Codes
IS 1644:1989Code of practice for fire safety of buildings...
→
IS 2190:2010Selection, Installation and maintenance of fi...
→
IS 1553:1989Design of Library Buildings - Recommendations...
→
🧮
Mix Design Calculator
IS 10262 · M20–M50

Frequently Asked Questions4

What is the minimum open space required around a temporary structure?+
A clear open space of at least 3 meters must be maintained around the pandal or structure (Clause 4.1.1).
Are cooking arrangements allowed inside a pandal?+
No, cooking is strictly prohibited inside the main pandal. Kitchens must be in a separate enclosure, at least 3m away, with its own fire safety measures (Clause 8).
How is the required exit width calculated?+
The cumulative width of all exits should be calculated at a rate of 50 cm per 100 persons. The minimum width for any single exit is 1.5 meters (Clause 9.3).
What is the requirement for fire extinguishers?+
At least two 9-litre water type extinguishers are required, and one extinguisher should be provided for every 500 sq.m of floor area (Clause 7.1.3).