QA/QC  › Material Test Certificates (MTC)  › Electrical Cable Material
Test-report · QC-MTC-TST-008
Electrical Cable Material Test Certificate (MTC) Receipt Verification
20 checkpoints across 7 sections. At every cable drum receipt before cutting and installation
20 Checkpoints
7 Sections
Per drum / per batch
QC Engineer, MEP Engineer

Checklist Preview

S.No.CheckpointIS RequirementStatus
A. MTC IDENTIFICATION AND AUTHENTICITY
A1Verify MTC on manufacturer letterhead with unique certificate number and authorized signatory
Acceptance: Letterhead, cert no., date, signatory, seal all present
Cl. 18 — Certification
OK
NC
NA
HOLD
A2Verify BIS ISI mark and CM/L licence number on drum label and MTC
Acceptance: ISI mark and CM/L number valid; licence currency verified on BIS portal
Cl. 18 — BIS marking
OK
NC
NA
HOLD
A3Verify drum/coil marking: manufacturer, IS number, cores × size, voltage, length, batch
Acceptance: All statutory details printed on drum tag and embossed/printed on outer sheath
Cl. 17 — Marking
OK
NC
NA
HOLD
B. CONDUCTOR AND DIMENSIONAL VERIFICATION
B1Verify conductor material (copper / aluminium), class (1/2/5), and construction per IS 8130
Acceptance: Annealed plain copper (Class 1/2/5) or Al; stranding and nominal area conform to IS 8130
Cl. 5 — Conductor
OK
NC
NA
HOLD
B2Verify conductor resistance (DCR) at 20°C on MTC against IS 8130 Table
Acceptance: E.g. 1.5 sqmm Cu Cl 1 ≤ 12.1 Ω/km; 2.5 ≤ 7.41; 4.0 ≤ 4.61 Ω/km; reported values within limit
Table 1 — DCR
OK
NC
NA
HOLD
B3Verify insulation thickness, sheath thickness, overall diameter per IS table on MTC
Acceptance: Insulation and sheath thickness meet IS minimum; mean value and minimum at any point checked
Table 2 — Dimensions
OK
NC
NA
HOLD
C. ELECTRICAL AND MECHANICAL PROPERTIES
C1Verify high-voltage (AC withstand) test result reported on MTC
Acceptance: 3 kV AC for 5 min (1100 V grade) withstood without breakdown per IS 10810 Part 45
Cl. 14 — HV test
OK
NC
NA
HOLD
C2Verify insulation resistance (IR) at 20°C and 70°C/90°C on MTC
Acceptance: IR per IS 10810 Part 43 meets minimum volume resistivity; reported >> minimum
Cl. 14 — IR
OK
NC
NA
HOLD
C3Verify tensile strength and elongation of insulation and sheath before/after ageing
Acceptance: PVC: tensile ≥ 12.5 MPa, elongation ≥ 150%; variation after ageing ≤ 25%; XLPE per IS 7098
Table 3 — Mechanical
OK
NC
NA
HOLD
C4Verify flammability / oxygen index / smoke density (for FR/FRLS/LSOH grades)
Acceptance: FRLS: oxygen index ≥ 29%; temperature index ≥ 250°C; smoke density ≤ 60%; acid gas ≤ 20%
Cl. 14 — Fire
OK
NC
NA
HOLD
C5For XLPE — verify hot set test, water absorption, shrinkage on MTC
Acceptance: Hot set: elongation ≤ 175%, permanent set ≤ 15% at 200°C; within IS 7098 limits
Table 2 — XLPE
OK
NC
NA
HOLD
Showing 11 of 20 checkpoints ·
A. MTC IDENTIFICATION AND AUTHENTICITY
A1Verify MTC on manufacturer letterhead with unique certificate number and authorized signatory
Cl. 18 — Certification (IS 694)
Letterhead, cert no., date, signatory, seal all present
OKNCNAHOLD
A2Verify BIS ISI mark and CM/L licence number on drum label and MTC
Cl. 18 — BIS marking (IS 694)
ISI mark and CM/L number valid; licence currency verified on BIS portal
OKNCNAHOLD
A3Verify drum/coil marking: manufacturer, IS number, cores × size, voltage, length, batch
Cl. 17 — Marking (IS 1554)
All statutory details printed on drum tag and embossed/printed on outer sheath
OKNCNAHOLD
B. CONDUCTOR AND DIMENSIONAL VERIFICATION
B1Verify conductor material (copper / aluminium), class (1/2/5), and construction per IS 8130
Cl. 5 — Conductor (IS 8130)
Annealed plain copper (Class 1/2/5) or Al; stranding and nominal area conform to IS 8130
OKNCNAHOLD
B2Verify conductor resistance (DCR) at 20°C on MTC against IS 8130 Table
Table 1 — DCR (IS 8130)
E.g. 1.5 sqmm Cu Cl 1 ≤ 12.1 Ω/km; 2.5 ≤ 7.41; 4.0 ≤ 4.61 Ω/km; reported values within limit
OKNCNAHOLD
B3Verify insulation thickness, sheath thickness, overall diameter per IS table on MTC
Table 2 — Dimensions (IS 694)
Insulation and sheath thickness meet IS minimum; mean value and minimum at any point checked
OKNCNAHOLD
C. ELECTRICAL AND MECHANICAL PROPERTIES
C1Verify high-voltage (AC withstand) test result reported on MTC
Cl. 14 — HV test (IS 694)
3 kV AC for 5 min (1100 V grade) withstood without breakdown per IS 10810 Part 45
OKNCNAHOLD
C2Verify insulation resistance (IR) at 20°C and 70°C/90°C on MTC
Cl. 14 — IR (IS 10810)
IR per IS 10810 Part 43 meets minimum volume resistivity; reported >> minimum
OKNCNAHOLD
C3Verify tensile strength and elongation of insulation and sheath before/after ageing
Table 3 — Mechanical (IS 694)
PVC: tensile ≥ 12.5 MPa, elongation ≥ 150%; variation after ageing ≤ 25%; XLPE per IS 7098
OKNCNAHOLD
C4Verify flammability / oxygen index / smoke density (for FR/FRLS/LSOH grades)
Cl. 14 — Fire (IS 10810)
FRLS: oxygen index ≥ 29%; temperature index ≥ 250°C; smoke density ≤ 60%; acid gas ≤ 20%
OKNCNAHOLD
C5For XLPE — verify hot set test, water absorption, shrinkage on MTC
Table 2 — XLPE (IS 7098)
Hot set: elongation ≤ 175%, permanent set ≤ 15% at 200°C; within IS 7098 limits
OKNCNAHOLD
Showing 11 of 20 ·