IS 4031:1988 Part 7 is the Indian Standard (BIS) for methods of physical tests for hydraulic cement - part 7: determination of soundness by le chatelier method. This standard outlines the testing procedure for determining the soundness of hydraulic cement using the Le Chatelier method, which evaluates the risk of delayed destructive expansion caused by uncombined free lime.
Describes the procedure for determining the soundness of hydraulic cement by the Le Chatelier expansion method.
IS 4031 (Part 7) specifies the method for determining compressive strength of masonry cement — the test for masonry-specific cement variants used in mortar for brickwork + plaster. Masonry cement (per IS 3466) is a special blend optimised for mortar workability + bond rather than concrete strength.
Use IS 4031 Part 7 when: - Source qualification of masonry cement supplier - Routine acceptance testing of delivered masonry cement - Forensic investigation of masonry mortar issues (poor bond, cracking) - Mix design verification for mortar
The IS 4031 series covers all physical tests on cement; Part 7 is specifically for masonry cement, which has different acceptance criteria than ordinary Portland cement (covered by IS 4031 Part 6).
Masonry cement vs OPC: - Masonry cement (IS 3466): pre-blended OPC + lime / fly ash + plasticizer; cheaper, easier to use; lower strength (5-7 N/mm² mortar) but better workability + bond - OPC + lime + sand: traditional cement-lime mortar; higher quality - OPC + sand only: high-strength but harsh, low workability
Masonry cement is popular for high-volume brick / block construction where workability matters more than mortar strength.
Specimens: - 50 × 50 × 50 mm mortar cubes (smaller than concrete cubes per IS 516) - Mix: 1 part masonry cement : 3 parts standard sand (per IS 650:1991) - Water: per consistency (typical w/c ≈ 0.40)
Procedure: 1. Mix per IS 4031 Part 4 consistency, then 1:3 mortar with standard sand. 2. Fill mortar in 50 mm cube moulds in 2 layers; tamp 25 strokes per layer. 3. Demould after 24 hours; cure in water at 27 ± 2 °C. 4. Test at 7 days + 28 days (3 cubes per age). 5. Apply load at 350 ± 35 N/sec rate. 6. Compute: strength (N/mm²) = peak load / 50 × 50 mm² area. 7. Report mean of 3 cubes.
Acceptance criteria (per IS 3466):
| Age | Min compressive strength (N/mm²) | |---|---| | 7 days | ≥ 2.5 | | 28 days | ≥ 5.0 |
Masonry cement is significantly lower strength than OPC (which would be ≥ 33 N/mm² at 28 days). The lower strength is by design — masonry mortar's main job is bond + flexibility, not load-bearing.
Cube dimension tolerance: - 50 mm ± 0.5 mm - Surface flatness: ≤ 0.05 mm under 50 mm straightedge - Surfaces in contact with platens: machined / ground if not flat
Masonry cement composition (per IS 3466): - OPC clinker: 50-70 % - Lime stone / fly ash: 20-40 % - Plasticiser / air-entrainer: 1-3 %
Mortar mixes using masonry cement:
| Application | Mix (masonry cement : sand) | Wall use | |---|---|---| | Brick / block masonry | 1:5 to 1:6 | Standard load-bearing | | Plaster (cement plaster) | 1:5 to 1:6 | Internal walls | | Pointing | 1:3 | Cement pointing on brick | | Backfill | 1:8 | Non-structural |
Masonry mortar's strength: 1-3 N/mm² typical (lower than concrete; matches the masonry strength so brick + mortar fail together rather than mortar being too strong + cracking the brick).
Comparison vs OPC + lime mortar:
| Mortar type | Workability | Bond | 28d strength (N/mm²) | Cost | |---|---|---|---|---| | OPC + sand 1:6 | Poor | Moderate | 3-4 | Low | | OPC + lime + sand 1:1:6 | Good | Good | 2-3 | Higher (lime added) | | Masonry cement 1:6 | Excellent | Excellent | 1.5-2.5 | Lowest (single bag) | | Pre-mixed dry mortar | Excellent | Excellent | per spec | Highest |
Project cost impact: - Masonry cement: ₹350-450 per 50 kg bag - OPC: ₹400-450 per 50 kg bag (similar) - Lime: ₹180-300 per 50 kg bag - Pre-mix mortar: ₹500-800 per 50 kg bag - Time savings with masonry cement / pre-mix: 10-20 % faster laying
Failure modes if cement strength deficient: - Mortar < 1 N/mm² at 28 days: masonry has poor cohesion; cracks under minor settlement / vibration - Mortar > 5 N/mm²: too rigid; brick cracks before mortar yields (counter-productive in seismic zones) - Goldilocks: 1.5-3 N/mm² for typical brick masonry — flexible enough to accommodate movement, strong enough to transfer load
1. Test on too few specimens. 1-2 cubes; can't establish statistical mean. Use 3 minimum. 2. Wrong sand for test. Project sand vs standard sand (IS 650) — different result. Test with standard sand for IS 4031 acceptance. 3. Loading rate too fast. Stress-rate dependent; reads higher. Stick to 350 N/sec. 4. Specimens not water-cured. Air-cured cubes test 30 % low. Water cure at 27 ± 2 °C. 5. Substandard masonry cement supplier. Local 'masonry cement' may not meet IS 3466. Demand ISI marked + IS 4031 Part 7 certificate. 6. Old cement (> 6 months). Reactivity drops; mortar weak. FIFO; use within shelf life. 7. Damp storage. Cement absorbs moisture; lump formation; weak mortar. Dry storage. 8. No cube identification. Tracking lost; can't assign result to consignment. Mark each cube. 9. Mortar mix on site without trial. Site mortar may not match design; weak. Trial mix verification. 10. Excess water in mortar. Reduces strength; over-workable. Stick to design w/c. 11. Use of masonry cement in concrete. Insufficient strength; concrete fails. Use OPC (IS 8112 / IS 12269) for concrete. 12. Masonry cement in load-bearing structural mortar > 6 m height. Per IS 1905:1987, structural masonry > 6 m needs cement-sand mortar with adequate compressive strength; masonry cement may be inadequate.
Masonry construction cascade:
1. Design (IS 1905:1987) — wall load, mortar strength target. 2. Mortar specification: - Masonry cement (cheap, fast) for non-structural / low-rise - Cement-sand 1:6 for routine load-bearing - Cement-lime-sand 1:1:6 for breathable / heritage - High-strength cement-sand 1:4 for heavy load 3. Cement source qualification (IS 4031 Part 7 — this code for masonry cement; Part 6 for OPC). 4. Mix design — cement + sand + water proportions. 5. Trial mix — verify mortar strength + workability. 6. Procurement — ISI marked, batch-tested cement. 7. Mortar mixing on site: - Dry-mix cement + sand thoroughly - Add water gradually to achieve workability - Use within 30-60 minutes of mixing 8. Brick / block laying: - Pre-soak bricks - 10 mm joint thickness - English / Flemish bond - Plumb + level + line check daily 9. Curing: - 7-14 days water curing - Avoid drying winds, direct sun on fresh masonry 10. Quality acceptance: - Joint thickness uniformity - Plumb / level - Crack-free (≤ 0.3 mm cracks acceptable) - Mortar cube tests at 7 + 28 days
IS 4031 Part 7 ensures masonry cement quality — the foundational input to masonry mortar that determines wall durability + load capacity.
| Parameter | IS Value | International | Source |
|---|---|---|---|
| Test Temperature | 27 ± 2 °C | 23.0 ± 2.0 °C | ASTM C191-21 |
| Test Humidity (for specimens) | ≥ 90% RH | ≥ 95% RH | ASTM C191-21 |
| Initial Set Needle Cross-Section | 1 mm square | 1 mm diameter (circular) | ASTM C191-21 |
| Criterion for Initial Setting Time | Penetration to 5.0 ± 0.5 mm from mould bottom | Penetration to 25 ± 0.5 mm from surface | ASTM C191-21 |
| Criterion for Final Setting Time | Needle makes an impression, but annular attachment does not | Needle does not sink visibly into the paste | ASTM C191-21 |
| Mass of Cement for Test Paste | 400 g | 650 g | ASTM C191-21 |
| Mould Height | 40 ± 0.2 mm | 40 ± 1 mm | ASTM C191-21 |