InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel
InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel

IS 15397 : 2003Portable Fire Extinguisher Mechanical Foam Type (Stored Pressure) -Specification

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
EN 3-7 · ISO 7165 · AS/NZS 1841.4
CurrentFrequently UsedSpecificationBIMFire Safety · Fire Fighting
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues6InternationalTablesFAQ4Related

IS 15397:2003 is the Indian Standard (BIS) for portable fire extinguisher mechanical foam type (stored pressure) -specification. This standard specifies the requirements for portable, stored pressure, mechanical foam type fire extinguishers, primarily of 9-litre capacity. It covers materials, construction details, anti-corrosive treatments, performance requirements, and testing methods for extinguishers intended for Class A and Class B fires.

Portable Fire Extinguisher Mechanical Foam Type (Stored Pressure) -Specification

Overview

Status
Current
Usage level
Frequently Used
Domain
Fire Safety — Fire Fighting
Type
Specification
International equivalents
EN 3-7:2004+A1:2007 · CEN (European Committee for Standardization), EuropeISO 7165:2017 · ISO (International Organization for Standardization), InternationalAS/NZS 1841.4:2007 · Standards Australia / Standards New Zealand, Australia/New ZealandNFPA 10, 2022 Edition · NFPA (National Fire Protection Association), USA
Typically used with
IS 4989IS 2190IS 15683IS 3224IS 10658
Also on InfraLens for IS 15397
6Key values2Tables4FAQs

BIM-relevant code. See the BIM Hub for ISO 19650, IFC, and LOD/LOIN frameworks used alongside it.

Practical Notes
! These extinguishers are highly effective on flammable liquid (Class B) fires and are also suitable for solid combustible (Class A) fires, but should NOT be used on electrical fires.
! Ensure the pressure gauge needle is within the green 'operable' zone during routine inspections as per IS 2190.
! The foam concentrate used must be compliant with IS 4989 and compatible with the extinguisher's construction materials.
Frequently referenced clauses
Cl. 4CapacityCl. 5Principal MaterialsCl. 6ConstructionCl. 9Performance RequirementsCl. 10Marking
Pulled from IS 15397:2003. Browse the full clause & table index below in Tables & Referenced Sections.
foam concentratesteelnitrogenAFFF

International Equivalents

Similar International Standards
EN 3-7:2004+A1:2007CEN (European Committee for Standardization), Europe
HighCurrent
Portable fire extinguishers — Part 7: Characteristics, performance requirements and test methods
Specifies rules of design, construction, and performance requirements for portable fire extinguishers, including foam types.
ISO 7165:2017ISO (International Organization for Standardization), International
HighCurrent
Fire fighting — Portable fire extinguishers — Performance and construction
Provides a global framework for the construction and performance of portable extinguishers, including foam types.
AS/NZS 1841.4:2007Standards Australia / Standards New Zealand, Australia/New Zealand
HighCurrent
Portable fire extinguishers - Part 4: Specific requirements for foam type extinguishers
Details the specific requirements for portable foam fire extinguishers, mirroring the focused scope of IS 15397.
NFPA 10, 2022 EditionNFPA (National Fire Protection Association), USA
MediumCurrent
Standard for Portable Fire Extinguishers
Covers selection, installation, and maintenance, but references UL 8 for the specific construction and performance of foam extinguishers.
Key Differences
≠IS 15397 uses a fire rating system like '2A, 21B'. EN 3-7 uses a different scale for test fires, resulting in ratings like '8A, 113B'. The test methodologies and sizes are not directly comparable.
≠IS 15397 specifies a cream color band (RAL 1015) on a red cylinder body. EN 3-7 requires the entire cylinder body to be red (RAL 3000), with agent identification via text and pictograms, not a color band.
≠The standard operating temperature range in IS 15397 is +5°C to +55°C. EN 3-7 specifies a standard range up to +60°C and explicitly provides for special low-temperature foam extinguishers tested for use down to -30°C.
≠IS 15397 requires a 240-hour external salt spray corrosion test, whereas EN 3-7 mandates a more stringent 480-hour test.
Key Similarities
≈Both IS 15397 and its international counterparts are based on the stored-pressure principle, where the foam solution and expellant gas (typically nitrogen) are stored together in the main cylinder.
≈All standards specify the use of synthetic foam concentrates like AFFF (Aqueous Film-Forming Foam) designed for extinguishing both Class A (solid combustibles) and Class B (flammable liquids) fires.
≈Performance testing for Class B fires is conceptually identical, involving extinguishing a standardized circular tray fire containing a flammable liquid like n-heptane to assign a fire rating.
≈General construction requirements are similar, mandating the use of corrosion-resistant materials for the cylinder (e.g., steel), valve assembly (e.g., brass), and other components to ensure safety and longevity.
≈All standards mandate a minimum effective discharge time to ensure the extinguisher provides a sufficient duration of agent application to effectively control a fire.
Parameter Comparison
ParameterIS ValueInternationalSource
Cylinder Color CodeFire Red body with a 100 mm Cream (RAL 1015) bandEntire body is Fire Red (RAL 3000); no color band specifiedEN 3-7:2004+A1:2007
Operating Temperature Range (Standard)+5 °C to +55 °CTypically +5 °C to +60 °C (or as marked on the extinguisher)EN 3-7:2004+A1:2007
Minimum Discharge Time (9 L Extinguisher)Not less than 25 secondsDepends on rating; ≥15 seconds for a 113B ratingEN 3-7:2004+A1:2007
Hydrostatic Pressure Test3.5 MPa or 2.5 x Working Pressure (whichever is higher)Test Pressure (PT) ≥ 1.43 x Max Allowable Pressure (PS)EN 3-8:2006
Burst Pressure Test≥ 5.5 MPa or 4.5 x Working Pressure (whichever is higher)≥ 2.7 x Max Allowable Pressure (PS), with an absolute minimum of 5.5 MPaEN 3-8:2006
External Corrosion Test (Salt Spray)240 hours480 hoursEN 3-7:2004+A1:2007
Range of Throw (Jet)Not less than 4 metresNot specified as a fixed value; determined by performance on test firesEN 3-7:2004+A1:2007
⚠ Verify details from original standards before use

Key Values6

Quick Reference Values
Standard Capacity9 litres
Minimum Fire Rating (9L)2A and 21B
Hydrostatic Test Pressure3.5 MPa
Minimum Effective Discharge Time (9L)25 seconds
Minimum Percentage of Discharge95 percent
Service Pressure1.5 MPa

Tables & Referenced Sections

Key Tables
Table 1: Performance Requirements
Table 2: Periodicity of Hydrostatic Pressure Testing of Welded Mild Steel Bodies
Key Clauses
Clause 4: Capacity
Clause 5: Principal Materials
Clause 6: Construction
Clause 9: Performance Requirements
Clause 10: Marking

Related Resources on InfraLens

Cross-Referenced Codes
IS 4989:2000multipurpose aqueous film forming foam liquid...
→
IS 2190:2010Selection, Installation and maintenance of fi...
→
IS 15683:2006Fixed Fire Fighting Systems - General Require...
→
IS 3224:2002Specification for Corrugated Fibre Cement She...
→
IS 10658:1999Specification for Higher Capacity Dry Powder ...
→

Frequently Asked Questions4

What is the standard capacity specified in this code?+
The standard specifies a 9-litre capacity extinguisher (Clause 4.1).
What is the minimum fire rating for a 9L foam extinguisher?+
It must achieve a minimum fire rating of 2A and 21B (Table 1).
What is the hydrostatic test pressure for the extinguisher body?+
The body must be hydrostatically tested to 3.5 MPa (or 35 kgf/cm²) for a minimum of 2.5 minutes (Clause 9.2).
What is the minimum effective discharge time?+
For a 9-litre extinguisher, the minimum effective discharge time is 25 seconds (Table 1).

QA/QC Inspection Templates

📋
QA/QC templates coming soon for this code.
Browse all 300 templates →