InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel
InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel

IS 10262 : 2019Concrete Mix Proportioning - Guidelines

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
BS EN 206 · BS 8500-1 · CSA A23.1
CurrentEssentialGuidelinesBIMMaterials Science · Concrete
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues6InternationalClauses8Engineer's NotesTablesFAQ4RelatedQA/QCNew

IS 10262:2019 is the Indian Standard (BIS) for concrete mix proportioning - guidelines. This standard provides guidelines for proportioning concrete mixes to achieve specified requirements for workability, strength, and durability. It details a systematic, step-by-step process for concrete mix design using the properties of the constituent materials, supplemented with illustrative examples.

Provides guidelines for the proportioning of concrete mixes.

Quick Reference — IS 10262:2019 Mix Design Numbers

Target mean strength, water content, CA volume tables, SCM replacement and trial-mix sequencing.

✓ Verified 2026-04-26
ReferenceValueClause
Target mean strength — characteristic σ basisf'ck = fck + 1.65 σCl. 5.1.1
Standard deviation — M10–M153.5 N/mm² (assumed)Cl. 5.1.1 (Table 1)
Standard deviation — M20–M254.0 N/mm² (assumed)Cl. 5.1.1 (Table 1)
Standard deviation — M30–M505.0 N/mm² (assumed)Cl. 5.1.1 (Table 1)
Std. deviation — M55+6.0 N/mm²Cl. 5.1.1 (Table 1)
Free-water content — 20 mm aggregate, slump 50 mm186 kg/m³Cl. 5.3 (Table 4)
Free-water content — 10 mm aggregate, 50 mm slump208 kg/m³Cl. 5.3 (Table 4)
Free-water content — 40 mm aggregate, 50 mm slump165 kg/m³Cl. 5.3 (Table 4)
Water adjustment per 25 mm extra slump+ 3 % waterCl. 5.3 (note 1)
Water adjustment for sub-angular / angular± 5–10 kg/m³ (rounded vs angular)Cl. 5.3 (note 2)
Volume of CA — 20 mm, sand Zone II, w/c 0.500.62 (per unit total agg. vol.)Cl. 5.5 (Table 5)
Volume of CA — 10 mm, sand Zone II, w/c 0.500.48Cl. 5.5 (Table 5)
CA volume adjustment per 0.05 change in w/c± 0.01 (decrease w/c → more CA)Cl. 5.5 (Table 5 note)
Trial mix sequence — number of trialsMin 3 (one at design, ±10% binder)Cl. 6
Acceptance — average of 3 cubes≥ f'ck (target mean)Cl. 6.5
Min cement content — refer durabilityPer IS 456 Table 5Cl. 4.2 / IS 456
Max cement content (excl. SCMs)450 kg/m³Cl. 4.2.4 / IS 456 Cl. 8.2.4.2
SCM (fly ash) replacement — typical limits15–35 % by mass of OPCCl. 4.4 / IS 1489 / IS 456
GGBS replacement — typical25–70 % by mass of OPCCl. 4.4 / IS 16714
Silica fume replacement — typical5–10 % by mass of OPCCl. 4.4 / IS 15388
⚠ 2019 revision tightened durability cross-refs to IS 456:2000 (with amendments). Always anchor durability mix limits to IS 456 Table 5.

Overview

Status
Current
Usage level
Essential
Domain
Materials Science — Concrete
Type
Guidelines
Earlier editions
IS 10262:2009IS 10262:1982
International equivalents
BS EN 206:2013+A2:2021 · CEN (European Union)BS 8500-1:2023 · BSI (UK)CSA A23.1:19 · CSA Group (Canada)
Typically used with
IS 456IS 383IS 2386IS 9103IS 269IS 8112IS 12269
Also on InfraLens for IS 10262
8Clause pages6Key values4Tables2QA/QC templates1Handbook topics1Knowledge articles4FAQs

BIM-relevant code. See the BIM Hub for ISO 19650, IFC, and LOD/LOIN frameworks used alongside it.

Practical Notes
! The mix design process is iterative. Always conduct trial mixes to verify and adjust proportions to achieve the required fresh and hardened concrete properties.
! The values in tables (e.g., water content, aggregate volume) are initial estimates for specific conditions. They must be adjusted based on the actual material properties, desired workability (slump), and use of admixtures.
! Ensure the final mix design not only meets strength targets but also complies with the durability requirements (min. cement, max. w/c ratio) specified in IS 456 for the intended exposure condition.
concretecementaggregatesadmixtureswaterfly ash

Engineer's Notes

In Practice — Editorial Commentary
When IS 10262 is your governing code

IS 10262:2019 is the Indian Standard for concrete mix proportioning — it governs how you derive the cement, water, fine aggregate, and coarse aggregate quantities needed to produce concrete of a specified grade.

Per IS 456:2000 Clause 9, design mix per IS 10262 is mandatory for M20 and above. Nominal mix (1:1.5:3 for M20, 1:1:2 for M25) is permitted only up to M20 in small works.

You use IS 10262 whenever you specify: - Structural RCC of any grade M20 or higher (buildings, bridges, foundations) - High-strength concrete (M60+) with SCM adjustments (fly ash, GGBS, silica fume) - Pumpable mix design for RMC delivery - Self-consolidating concrete (covered in IS 10262 Clause 5.7 added in 2019 revision)

Exceptions where IS 10262 alone is not enough: - Water-retaining structures — pair with IS 3370 Part 2 for crack control durability adjustments - Bridge concrete — supplement with IRC 21 or IRC 112 which specify additional bridge-specific durability requirements

Method — 8-step design mix procedure

IS 10262:2019 Annex A defines the design mix procedure. The 2019 revision expanded the table range to M80, added SCM guidance, and included stepped procedures for SCC and high-performance concrete.

Step 1 — Target mean strength (Clause 4.2): f_target = f_ck + 1.65 × σ, where σ is standard deviation from Table 2 (5 MPa for M30, 6 MPa for M45, 7 MPa for M55+).

Step 2 — Water-cement ratio (Table 1): bounded by the exposure class per IS 456 Table 5 (Mild 0.55, Moderate 0.50, Severe 0.45, Very Severe 0.45, Extreme 0.40).

Step 3 — Water content (Clause A-4): 186 litres/m³ for 20 mm MSA nominal mix, adjusted for workability (slump) and admixture dosage.

Step 4 — Cement content: Cement = Water / W-C ratio. Cross-check minimum cement per IS 456 Table 5 (300 kg/m³ Mild, 320 Moderate, 340 Severe, etc.).

Step 5 — Aggregate proportions (Table A-3 in 2019): volume of coarse aggregate per unit volume of total aggregate, by zone and MSA.

Step 6 — Fine aggregate volume from mass-volume balance.

Step 7 — Trial batch + strength test: 3 trial mixes, 28-day cube test per IS 516.

Step 8 — Adjust and finalise — if mean strength exceeds target by >10%, reduce cement to economise; if under target, increase cement or reduce W-C ratio.

Worked example — M30 mix design for moderate exposure

Problem: M30 concrete for a residential RCC building in moderate exposure. OPC 43 grade, 20 mm MSA, Zone II fine aggregate, 100 mm slump, no SCM.

Step 1 — Target: f_target = 30 + 1.65 × 5 = 37.25 MPa

Step 2 — W/C ratio (Table 1): For M30 and moderate exposure, max W/C = 0.50. Use 0.45 for safety margin.

Step 3 — Water content: For 20 mm MSA, 100 mm slump: base 186 litres + 3% per 25 mm slump above 50 = 186 × 1.06 = 197 litres/m³. With superplasticizer at 0.8%, reduce by 20% → 158 litres/m³.

Step 4 — Cement: 158 / 0.45 = 351 kg/m³. Check minimum per IS 456 Table 5 (moderate = 300) — 351 > 300 ✓

Step 5 — Aggregate volume: For 20 mm MSA and Zone II fine aggregate, coarse volume = 62% of total aggregate volume (Table A-3 for 2019 revision).

Step 6 — Mass-volume balance: Volume of concrete = 1.000 m³ Volume of cement = 351 / (3.15 × 1000) = 0.111 m³ Volume of water = 158 / 1000 = 0.158 m³ Volume of air (entrained) = 0.010 m³ Volume of aggregates = 1.000 − 0.111 − 0.158 − 0.010 = 0.721 m³ Coarse aggregate volume = 0.721 × 0.62 = 0.447 m³ → mass = 0.447 × 2700 = 1,207 kg/m³ Fine aggregate volume = 0.721 × 0.38 = 0.274 m³ → mass = 0.274 × 2650 = 726 kg/m³

Final mix (kg/m³): Cement 351 · Water 158 · Coarse Aggregate 1,207 · Fine Aggregate 726 · Superplasticizer 2.8 (0.8% of cement).

Mix ratio by mass: 1 : 2.07 : 3.44 · W/C 0.45

Trial batch 28-day strength target ≥ 37.25 MPa. If first trial gives 42 MPa, reduce cement to 335 kg and retest.

Common mistakes engineers make with IS 10262

1. Using nominal mix for M25+. IS 456 Clause 9.3 permits nominal mix only up to M20. M25 and above require design mix. Many site engineers still use nominal M25 as 1:1:2 — non-compliant, and 28-day cube tests often fail.

2. Ignoring minimum cement per IS 456 Table 5. Design mix may give you 280 kg/m³ for M25 in mild exposure, but IS 456 Table 5 requires minimum 300 kg/m³. Durability trumps economy. Always cross-check.

3. Wrong aggregate specific gravity assumptions. Default 2.7 for coarse and 2.65 for fine are approximations. For accurate mix design on a real project, test your source aggregates per IS 383 Clause 8 — specific gravity varies from 2.55 (granite) to 2.95 (basalt) and affects mix proportions by ~5-10%.

4. Skipping the trial batch. Design mix on paper is not enough. IS 10262 Clause 4.6 mandates trial batches with 28-day cube testing. Skipping this and going straight to site pour is how mix failures happen — often discovered only after a slab has set.

5. Not accounting for SCM interactions in 2019 revision. The 2019 update added explicit SCM adjustment factors (Clause 5.6). If you use fly ash at 20% replacement, the effective W-C ratio and strength development curves differ from pure OPC. Using the 2009 edition calculator for an SCM mix under-proportions the cement.

Cross-references in the Indian code stack
  • IS 456:2000 — the parent code requiring design mix for M20+; minimum cement and W/C ratios per exposure class
  • IS 269:2015 — OPC 33 properties; siblings IS 8112 (OPC 43) and IS 12269 (OPC 53)
  • IS 383:2016 — aggregate grading zones, specific gravity, deleterious limits
  • IS 516 Part 1:2021 — 28-day cube compressive strength test
  • IS 1199 — methods for sampling and analysis of concrete (slump, workability)
  • IS 9103:1999 — concrete admixtures (superplasticizers, retarders)
  • IS 3812 / IS 16715 — fly ash and GGBS specifications for SCM use
  • SP 23 — Design Aids for Concrete Mix Design (companion publication)
Practitioner view

IS 10262:2019 is a significant revision over the 2009 edition. Key improvements: expanded M80 range, explicit SCM provisions, SCC mix design procedure, and updated aggregate proportion tables.

In field practice, the 2019 tables are noticeably more conservative than 2009 for M30-M50 mixes — expect ~5-10% higher cement content for the same grade and exposure. This reflects lessons from durability failures (chloride ingress, ASR) in projects designed per 2009 mixes.

Most Indian RMC plants transitioned to 2019-compliant mixes during 2020-2022. If you are reviewing a design signed before 2020, verify which edition was used — pre-2019 mixes may need revision for current projects, especially in Severe+ exposure zones (coastal, industrial).

For high-strength concrete M60+, IS 10262:2019 Clause 5.6 is a starting point but not sufficient — pair with ACI 211.1 or fib Model Code 2020 for detailed HSC mix design. Indian HSC projects (Delhi Metro, infrastructure PPPs) typically cite both IS 10262 and ACI 211.1 in their DBRs.

Amendment No. 1 (2023) added clarifications on fly ash and GGBS blending limits. Check for the latest amendment before design freeze.

Clauses8

8 detailed clauses with interactive calculators, reference tables, and practical notes.
Cl. 4.1
Target Mean Strength
Clause 4.1 establishes the target mean compressive strength (f'ck) that the mix must be designed to achieve. The target …
Calc1T→
Cl. 4.2
Selection of Water-Cement Ratio
Clause 4.2 covers the selection of the free water-cement ratio. The W/C ratio is first selected based on the generalized…
2T→
Cl. 4.3
Estimation of Water Content
Clause 4.3 provides the estimated water content required per cubic metre of concrete for the desired workability. Table …
2T→
Cl. 4.4
Calculation of Cement Content
Clause 4.4 determines the cement content from the free water content (Clause 4.3) and the selected water-cement ratio (C…
1T→
Cl. 4.5
Proportion of Coarse Aggregate and Fine Aggregate
Clause 4.5 determines the proportion of coarse aggregate (CA) and fine aggregate (FA) in the mix. Table 3 provides the v…
2T→
Cl. 4.6
Mix Calculations
Clause 4.6 brings together all the preceding steps into a complete mix calculation using the absolute volume method. The…
2T→
Cl. 4.7
Trial Mixes and Adjustments
Clause 4.7 mandates that the designed mix proportions must be verified through laboratory trial mixes before use in actu…
1T→
Cl. 5
Mix Design with Mineral Admixtures
Clause 5 extends the mix design procedure of Clause 4 to incorporate mineral admixtures such as fly ash (pulverised fuel…
2T→
View full clause reference page →

International Equivalents

Similar International Standards
ACI 211.1-91 (R2002)ACI (US)
HighWithdrawn
Standard Practice for Selecting Proportions for Normal, Heavyweight, and Mass Concrete
Provides a prescriptive step-by-step method for mix proportioning based on absolute volumes, very similar to the IS code's approach.
BS EN 206:2013+A2:2021CEN (European Union)
MediumCurrent
Concrete - Specification, performance, production and conformity
A performance-based standard defining requirements for concrete, which mix designs must satisfy, rather than a 'how-to' design guide.
BS 8500-1:2023BSI (UK)
MediumCurrent
Concrete - Complementary British Standard to BS EN 206 - Part 1: Method of specifying and guidance for the specifier
Provides the UK national provisions for applying BS EN 206, linking specified properties to mix design requirements and durability.
CSA A23.1:19CSA Group (Canada)
MediumCurrent
Concrete materials and methods of concrete construction
Comprehensive standard covering materials and construction, including performance and prescriptive requirements for mix proportioning.
Key Differences
≠Fine Aggregate Characterization
≠Target Strength Basis
≠Coarse Aggregate Volume Calculation
≠Initial Air Content Assumption
Key Similarities
≈Both standards are fundamentally based on the absolute volume principle, where the sum of the absolute volumes of all ingredients (cement, water, aggregates, air) must equal a unit volume of concrete (e.g., 1 m³).
≈Both methodologies require the mix to be designed for a 'Target Mean Strength', calculated by adding a margin to the 'Specified Characteristic Strength'. This margin accounts for expected site variability (f'ck = fck + k*s).
≈Both use slump as the primary indicator for workability and use it as a key input to estimate the required water content for the mix. Water content is estimated from tables based on slump and aggregate size.
≈Both codes explicitly state that the calculated mix proportions are only a first estimate. They mandate conducting laboratory trial mixes to verify and adjust the proportions to ensure the fresh and hardened properties of the concrete meet the project specifications.
≈Both include detailed procedures for adjusting the batch weights of aggregates and the amount of mixing water to account for the free moisture present in the fine and coarse aggregates.
Parameter Comparison
ParameterIS ValueInternationalSource
Target Strength Formula (Typical)f'ck = fck + 1.65 * s (where s = standard deviation)f'cr = fc' + 1.34 * s (for >30 consecutive tests)ACI 318-19
Est. Water Content (20mm NMSA, 50mm slump)186 kg/m³ (for 25-50mm slump)Approx. 193 kg/m³ (for 25-50mm slump, non-air entrained)ACI 211.1-91
Est. Entrapped Air (20mm NMSA)1.0%1.5% (Typical value for non-air-entrained)ACI 211.1-91
Basis for Fine Aggregate ProportioningGrading Zones (I, II, III, IV) per IS 383Fineness Modulus (FM)ACI 211.1-91
Coarse Aggregate Volume (20mm NMSA)0.62 (vol of CA / vol of total agg.) for Zone II FA, w/c=0.50.64 (bulk vol of CA / vol of concrete) for FM=2.80ACI 211.1-91
Water Adjustment for SlumpIncrease water content by ~3% for every 25 mm slump increase above 50 mm.Tables provide direct water content values for different slump ranges (e.g. 25-50mm, 75-100mm).ACI 211.1-91
⚠ Verify details from original standards before use

Key Values6

Quick Reference Values
Target Strength Formulaf'ck = fck + 1.65 S
Assumed Std. Deviation for M25 concrete4.0 N/mm² (for good quality control)
Max Water Content for 20mm aggregate186 kg/m³ (for 50-75 mm slump)
Volume of Coarse Aggregate (20mm, Zone II Sand)0.62 per unit volume of total aggregate
Minimum Cement Content for Moderate Exposure (PCC)240 kg/m³ (as per IS 456)
Max W/C Ratio for Severe Exposure (RCC)0.45 (as per IS 456)
Key Formulas
f'ck = fck + 1.65 × S — Target Mean Compressive Strength
V = [W + (C/Sc) + (fa/Sfa) + (ca/Sca)] / 1000 — Absolute volume of fresh concrete

Tables & Referenced Sections

Key Tables
Table 2 - Assumed Standard Deviation
Table 3 - Approximate Air Content
Table 4 - Maximum Water Content per Cubic Metre of Concrete for Nominal Maximum Size of Aggregate
Table 5 - Volume of Coarse Aggregate per Unit Volume of Total Aggregate
Key Clauses
Clause 4 - Data for Mix Proportioning
Clause 5 - Target Strength for Mix Proportioning
Clause 6 - Selection of Water-Cement Ratio
Clause 8 - Selection of Water Content and Admixture
Clause 10 - Estimation of Coarse and Fine Aggregate Proportions
Annex A - Illustrative Example of Concrete Mix Proportioning

Related Resources on InfraLens

Cross-Referenced Codes
IS 456:2000Plain and Reinforced Concrete - Code of Pract...
→
IS 383:2016Coarse and Fine Aggregates for Concrete - Spe...
→
IS 2386:1963Methods of Test for Aggregates for Concrete -...
→
IS 9103:1999Admixtures for Concrete - Specification
→
IS 269:2015Ordinary Portland Cement - Specification
→
IS 8112:1989Ordinary Portland Cement, 43 Grade - Specific...
→
IS 12269:1987Ordinary Portland Cement, 53 Grade - Specific...
→
Handbook & Design Rules
Handbook Topics
📖Concrete Mix Ratios
→
Articles & Guides
📖IS 10262 vs ACI 211: Concrete Mix Design Methods Compared
→
🧮
Mix Design Calculator
IS 10262 · M20–M50

Frequently Asked Questions4

How is target mean strength calculated?+
It's the characteristic strength plus a margin: f'ck = fck + 1.65 × S, where S is the assumed standard deviation from Table 2 (Clause 5.3).
What is the starting point for determining water content?+
Table 4 gives an approximate water content for a given nominal maximum aggregate size to achieve a slump of 50-75 mm. This is adjusted for different slumps or admixtures.
How is the volume of coarse and fine aggregate determined?+
First, the volume of coarse aggregate per unit volume of total aggregate is estimated from Table 5. Then, using absolute volume calculations, the remaining volume is filled by the fine aggregate.
Does this standard replace IS 456 for mix design?+
No, it provides the detailed 'how-to' procedure for mix design, which must satisfy the 'what-to-do' requirements (like min. cement, max. w/c ratio) laid out in IS 456.

QA/QC Inspection Templates

Code-Specific Templates for IS 10262
📝
Concrete Mix Design Worksheet
form
Excel / PDF
📝
Concreting Method Statement
form
Excel / PDF