HandbookColumn Load Capacity Tables

Column Load Capacity Tables

IS 456:2000 · Clause 39.3 — Short Axially Loaded Members in Compression
Axial load carrying capacity of short RCC columns per IS 456:2000 Clause 39.3. Formula Pu = 0.4·fck·Ac + 0.67·fy·Asc applies only to short columns where effective length divided by least lateral dimension does not exceed 12. Tables below cover M20 + M25 concrete grades with Fe415 + Fe500 reinforcement steel — the four combinations that account for over 90% of Indian RCC building columns. Each table gives ultimate (factored) load carrying capacity in kN at standard steel percentages from 0.8% to 4.0% across rectangular column sizes from 230×230 mm up to 600×600 mm. For slender columns where the slenderness ratio exceeds 12, additional moment is induced due to lateral deflection and the capacity must be reduced per IS 456 Clause 39.7 — those reduction factors are not in this table. The minimum reinforcement percentage is 0.8% per IS 456 Cl. 26.5.3.1 to ensure ductile behaviour; the maximum is 6% (overall) or 4% in laps. Most economical design typically falls in the 1.0%-2.0% steel range — beyond 2.5%, marginal capacity gain per kg of steel diminishes.
IS 456Try RCC Design Suite
Formula (IS 456 Clause 39.3)
Pu = 0.4 × fck × Ac + 0.67 × fy × Asc
Where Pu = ultimate axial load (kN), fck = characteristic compressive strength of concrete (MPa), Ac = area of concrete = Ag − Asc, fy = yield strength of steel (MPa), Asc = area of steel reinforcement
Select Concrete + Steel Grade
Select Column Size (b × D mm)
Load Capacity — 230×230 mm (M20 + Fe415)
0.8%
358
kN
1%
377
kN
1.2%
396
kN
1.4%
415
kN
1.6%
435
kN
1.8%
454
kN
2%
473
kN
2.5%
520
kN
3%
568
kN
3.5%
615
kN
4%
663
kN
Working load ≈ Pu / 1.5 · Economical: 1.0% to 2.0% — economical for most buildings
Full Table — M20 + Fe415 (Pu in kN)
Size0.8%1%1.2%1.4%1.6%1.8%2%2.5%3%3.5%4%
230×230358377396415435454473520568615663
230×300467492517542567592616679741803865
230×3505455756046336626917207938669391012
230×40062365668972375678982290598810701153
230×4507017387768138508879251018111112041297
230×50077982086290394598610271131123413381441
230×600935984103410841134118312331357148116061730
300×30061064267470773977280488596610471128
300×400813856899942986102910721180128813961504
300×450914963101210601109115712061328144915711692
300×50010161070112411781232128613401475161017451880
300×60012191284134914141478154316081770193220942256
300×75015241605168617671848192920102213241526182820
400×40010841142119912571314137214301574171818622006
400×50013551427149915711643171517871967214723272508
400×60016251712179918851972205821452361257727933009
450×45013711444151715901664173718101993217623592543
450×60018281926202421212219231724152659290331473391
500×50016941784187419642054214422342459268429093134
600×60024382568269828282958308832183543386841934518
Design Notes
Values for short columns only — effective length divided by least lateral dimension must not exceed 12. Beyond this slenderness ratio, columns are 'slender' and develop additional moments due to lateral deflection (P-delta effect) that the capacity formula does not account for.
For slender columns, apply additional moment reduction factor per IS 456 Clause 39.7 — typically reduces capacity by 10-30% depending on slenderness ratio. For very slender columns (ratio > 60), a full second-order analysis is required.
Minimum 4 bars for rectangular / square columns (one in each corner). Minimum 6 bars for circular columns equally spaced around the perimeter. Bundled bars (2-bar or 3-bar bundles) are permitted but each bundle is treated as a single bar for tie spacing.
Minimum bar diameter is 12 mm (8 mm permitted only in tied non-load-bearing situations). For seismic detailing per IS 13920 in Zones III/IV/V, use diameter ≥ 12 mm and ensure all bars are within distance of 150 mm from the nearest stirrup corner.
Maximum spacing of lateral ties / stirrups is the least of: (a) least lateral dimension of column, (b) 16 times the smallest longitudinal bar diameter, (c) 300 mm. Tie diameter is the larger of: (a) one-fourth of the longitudinal bar diameter, (b) 6 mm. Closer spacing is required in confining zones near beam-column joints per IS 13920.
Factor of safety of approximately 1.5 is applied — to get working (service) load capacity, divide Pu values in the tables by 1.5. The 0.4·fck·Ac term applies partial safety factor of 1.5 for concrete; the 0.67·fy·Asc term applies partial safety factor of 1.15 for steel. The 0.4 + 0.67 coefficients are NOT the same as direct stress fractions — they are derived from limit-state ultimate strain assumptions per IS 456 Cl. 39.3.
Tables assume the column is axially loaded only (no moment). For columns subjected to moment (most real-life columns), the capacity reduces and an interaction diagram per IS 456 Cl. 39.5 must be used. Most peripheral building columns develop biaxial moment from beam framing — the interaction analysis is mandatory for these.
Concrete cover to longitudinal reinforcement is typically 40 mm for moderate exposure (IS 456 Table 16). The Ac (area of concrete) in the formula = Gross area Ag minus Asc (area of steel) — for accurate small-section calculations, the cover does not change Ag but affects the gross-to-effective area ratio.
Steel percentages above 4% should be detailed carefully — laps create high local steel ratios that can exceed the 6% absolute maximum at lap zones. Avoid laps at locations of high stress (top of column, beam-column joints).

Also useful

38 related items across IS codes, knowledge articles, design rules, maps and tools

Related Design Rules· 4 of 33

Related Engineering Maps· 3 of 5

← Previous
Concrete Mix Ratios
Next →
Development Length & Lap Length
Generated by InfraLens · infralens.in