IS 5612

: 2000

Specification for hose clamps and hose bandages for fire brigade use, Part 2: Hose bandages

CurrentSpecializedSpecificationFire Safety · Fire Fighting
Download PDFBIS PortalGoogle

This standard specifies the requirements for materials, dimensions, construction, workmanship, and performance of hose bandages. These are used by fire brigades for the temporary repair of leaking or burst fire hoses during an emergency.

Specification for hose clamps and hose bandages for fire brigade use, Part 2: Hose bandages

Quick Reference Values
Hydraulic pressure test (no leakage)2.1 MN/m² (21 kgf/cm²) for 2.5 min
Applicable hose nominal bore sizes63 mm and 70 mm
Material for Clamp BodyMalleable cast iron (IS 2108) or Carbon steel forging (IS 2004)
Material for ScrewSteel with minimum tensile strength of 400 MPa
Protective CoatingHot-dip galvanized or zinc plated as per IS 1573
Practical Notes
Ensure the clamp is marked with the BIS Standard Mark (ISI mark) for quality assurance.
Always use the correct size clamp for the hose diameter to ensure an effective seal without damaging the hose.
Regularly inspect clamps for corrosion or physical damage, especially the screw mechanism, to ensure they are functional in an emergency.