IS 3844:1989 is the Indian Standard (BIS) for installation and maintenance of internal hydrants and hose reels on premises. This code covers the requirements for the design, installation, water supply, and periodic maintenance of internal fire hydrants and first-aid hose reels inside buildings to facilitate early-stage fire suppression.
Covers requirements for the design, installation, testing, and maintenance of internal hydrant and hose reel systems in buildings.
Key reference values — verify against the current code edition / project specification.
| Reference | Value | Clause |
|---|---|---|
| Subject | Internal hydrants & hose reels in buildings | Scope |
| Hose reel | First-aid hose reel near exits/each floor | Provision |
| Landing valve | Wet/dry riser landing valves per floor | Provision |
| Pressure/flow | Min residual pressure & flow at topmost outlet | Performance |
| Read with | NBC Part 4 / IS 1646 / IS 13039 | Cross-ref |
BIM-relevant code. See the BIM Hub for ISO 19650, IFC, and LOD/LOIN frameworks used alongside it.
IS 3844:1989 is the Code of Practice for Installation and Maintenance of Internal Fire Hydrants and Hose Reels in Buildings. It is the foundational standard for the wet riser + hose reel system that NBC 2016 Part 4 Fire and Life Safety requires in most multi-storey Indian buildings.
Use it for: - Wet riser specification, sizing, and routing in residential, commercial, hospital, hotel buildings - Internal hydrant (landing valve) placement at each floor - Hose reel installation (rubber hose, drum, nozzle) - Pump and tank capacity sizing for the fire-protection system - Periodic inspection and maintenance schedule
Not used for: - Sprinkler systems → IS 15105 - Foam systems → IS 12835 / NFPA 11 - Industrial hydrants (outdoor) → IS 13039 - Fire alarm and detection → IS 2189 + NBC Part 4
Most design offices reference IS 3844 alongside NBC 2016 Part 4 Chapter 5 (which gives occupancy-based mandates) and TAC (Tariff Advisory Committee) Rules for insurance compliance. The TAC rules sometimes impose stricter standards than IS 3844.
Wet riser sizing (Clause 4): - Wet riser pipe: minimum 100 mm internal diameter for buildings up to 24 m height; 150 mm for taller - Pressure at the most-remote landing valve: minimum 3.5 kg/cm² (350 kPa) at design flow - Design flow at single hydrant: 2,250 L/min for wet riser; 900 L/min for hose-reel only - Two hydrants assumed running simultaneously for tall buildings (> 30 m)
Landing valve (internal hydrant) placement (Clause 5): - Located in protected staircase lobby or fire-resistant shaft - One per floor minimum; additional valves so no point on the floor is > 30 m from a landing valve - Outlet: 63 mm instantaneous coupling (standard fire-brigade-compatible) - Mounting height: 1.0 m above finished floor level (firefighter-accessible)
Hose reel (Clause 6): - 30 m long, 25 mm bore rubber hose on swinging drum - Permanently charged with water - Operable by single person (untrained occupant) — for first-aid firefighting before brigade arrives - Nozzle: 6 mm orifice, jet/spray adjustable
Water storage (Clause 7): - Dedicated fire-water tank capacity: minimum 20,000 L for buildings up to 15 m; 75,000 L for 15-24 m; 100,000 L for 24-45 m; 150,000+ L beyond - Pump room: jockey pump (10 L/s, maintains pressure), main electric pump (full design flow), diesel standby pump (for power failure) - All pumps housed in fire-rated enclosure with independent ventilation
Weekly checks: - Visual inspection of all landing valves — no leaks, no obstruction, all caps in place - Hose reel — rotates freely, nozzle accessible - Jockey pump — operational, pressure gauge reading - Fire-water tank level
Monthly: - Pump run-test (15 minutes): verify rated flow and pressure at the test point - Diesel pump self-start on simulated power failure - Hose reel — pull out 5 m, test water flow - Pressure-relief and air-release valves on riser
Quarterly: - Full system flush — open the test point at top of riser, let flow stabilise - Hydrant valve operation at every floor (open/close 3 times) - Verify pump room ventilation, fuel level (diesel), battery health (electric)
Annually: - Hose pressure test (hydrostatic test at 1.5× working pressure, 10 minutes) - Pump performance certification (re-test against manufacturer curve) - Full system commissioning re-validation - Issue maintenance certificate (required for fire NOC renewal in most municipalities)
1. Skipping diesel-pump self-start test — most fires happen during power outages (overheated wiring, short circuits). If the diesel pump doesn't self-start, the entire system is dead. This single check is the most common 'gotcha' on annual fire-NOC audits.
2. Hose reel rusted in place — non-operation for years causes the drum bearing to seize. By the time it's needed, occupants can't pull the hose out. Monthly operation drill keeps it functional.
3. Inadequate water-tank reserve — fire-water tank is sometimes shared with domestic supply. NBC 2016 and IS 3844 require dedicated and isolated fire reserve. If a faulty float valve drops domestic water consumption into the fire reserve, the fire system runs dry.
4. Pressure too low at top floor — design assumes 3.5 kg/cm² at the most-remote valve. Long horizontal runs, undersized pipes, and friction losses often reduce this to 1.5-2.0 kg/cm² in tall buildings. Verify with a real test, not just hydraulic calculation.
5. Wrong coupling type — internal hydrants must use 63 mm instantaneous coupling (BIS/India fire-brigade standard). Some imported fittings come with NH (US) or Storz (European) couplings — incompatible with Indian fire-engine hoses. Brigade can't connect; system is useless.
6. No risk-mapping to floor layout — IS 3844 requires no point > 30 m from a landing valve. In long open-plan offices or warehouses, a single landing valve per floor often doesn't cover the layout. Multiple valves needed.
IS 3844:1989 is 36 years old and shows it. NBC 2016 Part 4 — which superseded NBC 2005 — incorporates IS 3844 by reference but adds modern provisions (high-rise pressure boosting, fireman's lifts, refuge areas, sprinkler triggers) that IS 3844 alone doesn't cover. Use NBC 2016 Part 4 as the primary design document; use IS 3844 for component specification and maintenance protocols.
A major update is overdue. The 2024 draft amendment to NBC Part 4 (currently in BIS consultation) is expected to mandate: - Performance-based design as an alternative to prescriptive (currently IS 3844 is prescriptive-only) - Tighter ventilation requirements in stairwells - Mandatory third-party commissioning certification - Maintenance log books inspected at fire-NOC renewal
For current Indian projects: use IS 3844 + NBC 2016 + TAC Rules + Local Fire Service requirements (each city has slight variations — Delhi DF&ES, Maharashtra MFB, Karnataka KSFRS — read their checklists). For PPP / international projects (smart city, metro depots): supplement with NFPA 13 (sprinklers), NFPA 14 (standpipe/hydrant), NFPA 20 (pumps) — these are globally accepted and more current than IS.
Fire safety has lowest design margin tolerance of any system — under-design literally kills people. When in doubt, over-specify.
| Parameter | IS Value | International | Source |
|---|---|---|---|
| Min. Pressure at Highest Hydrant (Firefighter use) | 3.5 kgf/cm² (343 kPa) | 6.9 bar (690 kPa / 100 psi) | NFPA 14:2019 |
| Hydrant Outlet Connection (Firefighter use) | 63 mm instantaneous coupling (Female) | 2.5 inch (65 mm) NPSH thread | NFPA 14:2019 |
| Min. Flow Rate (First Riser/Standpipe) | 900 LPM (as per NBC of India which IS 3844 complements) | 1893 LPM (500 GPM) | NFPA 14:2019 |
| Pipe Sizing Design Method | Prescriptive tables based on building height | Hydraulic calculations based on performance | NFPA 14:2019 |
| Min. Pressure at Hose Reel Nozzle | Not explicitly defined at nozzle, system pressure of 3.5 kgf/cm² is specified. | 2.0 bar (200 kPa) | EN 671-1:2012 |
| Minimum Wet Riser Pipe Diameter | 100 mm | 100 mm (4 inches) | BS 9990:2015 |
| Maximum Hose Reel Length | 30 meters | Typically 30 meters | EN 671-1:2012 |