MATERIALS

Thermal Properties of Materials

Thermal conductivity, specific heat, density, and emissivity values that govern heat transfer through building materials

Also calledthermal propertiesthermal properties of materialthermal propertymaterial thermal properties
Related on InfraLens
Definition

Thermal properties of building materials determine how heat flows through walls, roofs, and floors. Four core properties: (1) Thermal conductivity (k or λ) — heat conducted per unit thickness per °C, in W/m·K. (2) Specific heat capacity (c) — heat required to raise 1 kg by 1 °C, in J/kg·K. (3) Density (ρ) — mass per volume, kg/m³. (4) Emissivity (ε) — radiative heat-loss factor (0-1). These properties drive U-value (transmittance), R-value (resistance), and thermal mass calculations that govern ECBC compliance and HVAC sizing.

Typical k values for Indian construction materials (W/m·K): RCC = 1.74; brick masonry = 0.81; AAC block = 0.16-0.22; concrete block (hollow) = 0.55; lime mortar = 0.72; PCC = 1.28; cement plaster = 0.72; glass = 0.78; steel = 50; aluminium = 211; timber (sal) = 0.17; gypsum board = 0.16; rockwool = 0.038; EPS = 0.035; XPS = 0.030; PUR foam = 0.025. The lower the k, the better the insulation. Most masonry materials are 20-50× worse insulators than rockwool — which is why dedicated insulation layers matter on roofs and walls.

Source standards: IS 3346:1980 (Method of determining thermal conductivity), IS 11239 series (Building materials thermal performance), NBC 2016 Part 11 (Approach to Sustainability — thermal envelope), ECBC 2017 (Energy Conservation Building Code).

Typical values
RCC — k1.74 W/m·K
Brick masonry — k0.81 W/m·K
AAC block — k0.16-0.22 W/m·K
Concrete block (hollow) — k0.55 W/m·K
Glass — k0.78 W/m·K
Rockwool — k0.038 W/m·K
EPS — k0.035 W/m·K
PUR foam — k0.025 W/m·K
Steel — k50 W/m·K
Timber (sal) — k0.17 W/m·K
Where used
  • U-value and R-value calculations for ECBC compliance
  • HVAC heat-load estimation for cooling/heating sizing
  • Roof and wall insulation thickness sizing
  • Thermal mass design for passive cooling
  • Comparison of alternate masonry materials (AAC vs brick vs hollow block)
Acceptance / threshold
Per IS 3346 + IS 11239 + ECBC 2017: thermal conductivity values from manufacturer test reports or referenced standards; U-value of building envelope per ECBC zone (cooling-dominated: roof ≤ 0.4, wall ≤ 0.4 W/m²K).
Site example
A 230 mm brick wall (k=0.81) has thermal resistance R = 0.23/0.81 = 0.28 m²K/W. Adding 50 mm EPS (k=0.035) raises R to 0.28 + 0.05/0.035 = 1.71 m²K/W — a 6× improvement. U-value drops from 3.6 to 0.58 W/m²K, hitting ECBC compliance for hot-dry zones. AAC blocks (k=0.18) at 200 mm thickness give R = 1.11 m²K/W without separate insulation — preferred for energy-efficient masonry buildings.
Frequently asked
What are the four main thermal properties of materials?
(1) Thermal conductivity (k or λ) in W/m·K — heat conducted per unit thickness per °C. (2) Specific heat capacity (c) in J/kg·K — heat required to raise 1 kg by 1 °C. (3) Density (ρ) in kg/m³. (4) Emissivity (ε) — radiative-loss factor 0-1. Together they govern U-value, R-value, thermal mass, and surface temperatures.
Which Indian standard covers thermal properties?
Primary: IS 3346:1980 (Method of determining thermal conductivity), IS 11239 series (Building materials thermal performance), NBC 2016 Part 11 (Approach to Sustainability), ECBC 2017 (Energy Conservation Building Code). Manufacturer test reports per IS 3346 are accepted for k-value verification.
Why does AAC block beat brick for thermal performance?
AAC k = 0.18 W/m·K vs brick k = 0.81 — about 4.5× lower conductivity. A 200 mm AAC wall has roughly the same thermal resistance as a 1.0 m brick wall. AAC also has lower density (550-650 kg/m³ vs 1700-1900 kg/m³ for brick), reducing dead load. Common choice for cooling-dominated Indian climates.
Related materials terms