This standard specifies the minimum energy performance requirements for the design, installation, and commissioning of HVAC systems in buildings. It provides a comprehensive framework covering system design, equipment sizing, controls, and insulation to promote energy efficiency in building operations.
Specifies general requirements and methodologies for calculating and evaluating the energy performance of HVAC systems in buildings.
Quick Reference Values
Minimum office ventilation rate (Category II)7.5 l/s per person
Minimum office ventilation rate (per area)0.6 l/s per m²
Typical occupant density in office10 m² per person
Typical ACH for mechanically ventilated classroom3-4 ACH
Standard air density1.2 kg/m³
Specific heat of air1006 J/(kg·K)
Key Formulas
q_v,tot = q_v,pers + q_v,build — Total ventilation rate
P_fan_spec = Δp_tot / η_fan_tot — Specific fan power
Φ_V = ρ_a * c_a * q_v * (θ_supply - θ_outdoor) — Thermal energy for treating ventilation air
Practical Notes
This standard is aligned with international norms (ISO/EN) and is intended for detailed energy simulation and performance analysis, not just basic equipment sizing.
The total required ventilation rate is a sum of the rate for occupants (bio-effluents) and the rate for the building itself (diluting pollutants from materials). Both components must be calculated.
Pay close attention to the 'System Ventilation Efficiency' (Table A.2), a critical factor that represents how effectively fresh air is distributed to occupants.