IS 12437:2018 is the Indian Standard (BIS) for chilled water distribution systems - code of practice for design and installation. This code of practice outlines the requirements for designing and installing chilled water distribution systems for air conditioning. It covers essential aspects like pipe sizing, material selection, pump configuration, thermal insulation, and procedures for testing and commissioning to ensure system efficiency, reliability, and performance.
Provides guidelines for the design, installation, testing, and commissioning of chilled water distribution systems for air conditioning.
BIM-relevant code. See the BIM Hub for ISO 19650, IFC, and LOD/LOIN frameworks used alongside it.
| Parameter | IS Value | International | Source |
|---|---|---|---|
| Design Pressure Drop | 150 to 400 Pa/m | 100 to 400 Pa/m (1.0 to 4.0 ft/100 ft) | ASHRAE Handbook—Fundamentals |
| General Design Water Velocity | 1.5 to 3.5 m/s | 1.2 to 3.7 m/s (4 to 12 fps), with lower values for smaller pipes to control noise | ASHRAE Handbook—HVAC Systems and Equipment |
| Typical Chilled Water ΔT | 5°C to 7°C | 6.7°C to 11°C (12°F to 20°F) in modern high-efficiency designs | ASHRAE Design Guide for CHW Plants |
| Hydrostatic Test Pressure | 1.5 x max operating pressure or 1000 kPa, whichever is higher | 1.5 x working pressure, but not less than 690 kPa (100 psi) | IAPMO/ANSI UMC 1-2021 |
| Hydrostatic Test Duration | 24 hours | 15 minutes after stabilization | IAPMO/ANSI UMC 1-2021 |
| Minimum Pipe Slope for Drainage | 1:500 | 1:480 (0.25 inch per 10 ft) | ASHRAE / General Industry Practice |