IS 12400 Part 3

: 2018

Thermal Insulating Materials - Mineral Wool - Pipe Section Type - Specification

CurrentFrequently UsedSpecificationBIMMEP · HVAC and Air Conditioning
Archive.orgBIS PortalGoogle

This standard specifies the requirements for pre-formed, rigid mineral wool (rock and slag wool) pipe sections used for thermal insulation in various applications. It covers material properties like density and thermal conductivity, dimensions, tolerances, and testing methods to ensure product quality and performance.

Specifies requirements for mineral wool pipe section type thermal insulating materials used for insulating pipes in various applications.

Quick Reference Values
Standard length of pipe section1000 mm
Length tolerance± 5 mm
Thickness tolerance± 3 mm or ±10%, whichever is greater
Max thermal conductivity (density ≥ 100 kg/m³ at 50°C mean temp)0.040 W/m.K
Max thermal conductivity (density ≥ 100 kg/m³ at 100°C mean temp)0.048 W/m.K
Maximum service temperature (density 100 to <140 kg/m³)650 °C
Maximum service temperature (density ≥ 140 kg/m³)750 °C
Practical Notes
Ensure the correct density is specified for the required maximum service temperature as per Table 3.
The outer diameter of the insulation must match the pipe's outer diameter, and sections must be tightly butted to avoid thermal bridges.