SEISMIC

Storey Drift

Relative lateral displacement between two adjacent floors under lateral load

Also calledstory driftinter storey driftdrift limitlateral drift
Related on InfraLens
Definition

Storey drift is the relative horizontal displacement between the top and bottom of a storey under lateral (seismic or wind) load, usually expressed as the inter-storey drift ratio = drift / storey height. It is the primary serviceability and damage-control check for lateral systems: excessive drift damages partitions, cladding, services and stairs, causes P-delta amplification and pounding with adjacent buildings, and is a key indicator of inadequate lateral stiffness even when member strength is adequate.

IS 1893 Part 1 Cl. 7.11.1 limits the storey drift under the design seismic force (with partial load factor 1.0) to 0.004 times the storey height for the un-factored case, and IS 16700 imposes wind/seismic drift limits for tall buildings. Drift typically controls the sizing of shear walls, moment frames and bracing in mid- and high-rise buildings far more than member strength does. The check must use the appropriate displacement (including the response-reduction-related amplification where applicable) and account for torsional amplification at the building's flexible edge.

Where used
  • Lateral-system stiffness design (IS 1893)
  • Tall-building wind + seismic drift control (IS 16700)
  • Partition/cladding/services damage limitation
  • P-delta + building-separation/pounding checks
  • Shear-wall, moment-frame + bracing sizing
Acceptance / threshold
Inter-storey drift under the design lateral load within IS 1893 Cl. 7.11.1 (0.004 × storey height for the stated load case) and IS 16700 limits for tall buildings, including torsional amplification; lateral system stiffened if exceeded.
Frequently asked
What is storey drift?
The relative horizontal displacement between two adjacent floors under lateral load, usually given as the inter-storey drift ratio (drift ÷ storey height). It governs lateral stiffness and non-structural damage control.
What is the permissible storey drift as per IS 1893?
IS 1893 Part 1 Cl. 7.11.1 limits storey drift to 0.004 times the storey height under the design seismic force for the specified load case (partial load factor 1.0).
Related terms