IS 5216:1982 is the Indian Standard (BIS) for guide for safety procedures and practices in electrical work. This guide outlines fundamental safety procedures and practices for individuals working with or near electrical installations. It covers aspects like safety management, working on live and dead circuits, use of personal protective equipment (PPE), and emergency response like first aid for electric shock and firefighting. The standard aims to prevent electrical accidents and ensure a safe working environment for all personnel.
Provides general guidance on safety procedures and practices to be followed during electrical work.
| Parameter | IS Value | International | Source |
|---|---|---|---|
| Arc Flash Hazard Analysis | Not specified or required. | Mandatory risk assessment required for equipment likely to produce an arc flash. | NFPA 70E-2024 (Art. 130.5) |
| Voltage Threshold for 'High Voltage' | Generally >650V (as per Indian Electricity Rules referenced by the code). | >1000V AC or >1500V DC. | EN 50110-1:2023 |
| Insulating Glove Testing Interval | At least once a year (Clause 19.2.3). | Before first issue and every 6 months thereafter. | NFPA 70E-2024 (Table 130.7(C)(7)(c)) / OSHA 1910.137 |
| Restricted Approach Boundary (480V System) | Not explicitly defined; general clearances are given. | 1 ft (0.3 m) for qualified persons. | NFPA 70E-2024 (Table 130.4(E)(a)) |
| Requirement for Arc-Rated (AR) Clothing | Not specified. Recommends 'clothing of close weave'. | Required based on incident energy analysis or task-based tables. | NFPA 70E-2024 (Art. 130.5) |
| Lockout/Tagout Verification Step | Recommends confirming dead circuits with a voltage detector (Clause 4.3.4). | Mandatory 'Test-Before-Touch' principle; requires verifying tester on a known live source, testing the target, then re-verifying on live source. | NFPA 70E-2024 (Art. 120.5) |