InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel
InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel

IS 5816 : 1999Method of Test Splitting Tensile Strength of Concrete

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
ASTM C496/C496M · EN 12390-6 · BS EN 12390-6
CurrentFrequently UsedTesting MethodMaterials Science · Cement, Concrete, Aggregates and RCC
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues6InternationalEngineer's NotesTablesFAQ4Related

IS 5816:1999 is the Indian Standard (BIS) for method of test splitting tensile strength of concrete. This standard outlines the procedure for determining the splitting tensile strength of hardened concrete specimens. It details the required apparatus, specimen dimensions (cylindrical or cubical), test setup with packing strips, and the calculation formula. This test provides an indirect measurement of the tensile strength of concrete.

Method of Test Splitting Tensile Strength of Concrete

Overview

Status
Current
Usage level
Frequently Used
Domain
Materials Science — Cement, Concrete, Aggregates and RCC
Type
Testing Method
Amendments
Amendment 1 (August 2007); Amendment 2 (June 2013)
International equivalents
ASTM C496/C496M-17 · ASTM International, USAEN 12390-6:2009 · CEN (European Committee for Standardization), EuropeBS EN 12390-6:2009 · BSI (British Standards Institution), UKAS 1012.10:2000 (R2014) · Standards Australia, Australia
Typically used with
IS 456IS 516IS 1199
Also on InfraLens for IS 5816
6Key values4FAQs
Practical Notes
! Ensure packing strips are correctly aligned along the specimen's central axis to ensure a valid split failure.
! The failure must be a clean split along the loading plane; irregular or crushing failures indicate a faulty test.
! The splitting tensile strength is typically used in design calculations where concrete cracking is a concern, such as in massive concrete structures or pavements.
Frequently referenced clauses
Cl. 4ApparatusCl. 5Test SpecimenCl. 6ProcedureCl. 7Calculation of Splitting Tensile Strength
Pulled from IS 5816:1999. Browse the full clause & table index below in Tables & Referenced Sections.
Updates & Amendments2 amendments
Amendment 1 (August 2007)
Amendment 2 (June 2013)
Consolidated list per BIS. For the text of each amendment, refer to the BIS portal link above.
concretecementaggregates

Engineer's Notes

In Practice — Editorial Commentary
When IS 5816 is your governing code

IS 5816 specifies the method for splitting tensile strength of concrete (the 'Brazilian test') — a cylinder is loaded across its diameter until it splits, and the indirect tensile strength is calculated from the failure load.

Unlike compressive cube strength (which dominates RCC design), tensile strength is what governs: - Cracking in slabs, water-tank walls, mass concrete (thermal cracking) - Pavement design (IRC:58 for rigid pavements) - Punching shear capacity in flat slabs around columns - Anchorage / bond length calculations indirectly - Durability assessment — tensile strength correlates with crack-control limits in IS 456 Clause 35.3.2

IS 5816 is run when: - Pavement-quality concrete (PQC) for highways or airports — tensile strength is the design variable - Water-retaining structure design (IS 3370) — crack-control checks - Investigation of cracking in completed structures (cores tested in split tension) - Mix-design qualification for high-strength or fibre-reinforced concrete

For most building structural design, the assumed tensile strength is taken from IS 456 Clause 6.2.2 (f_ct = 0.7 √f_ck). IS 5816 is what you run when you need to *measure* it, not assume it.

The test, briefly

1. Specimen: cylinder 150 mm diameter × 300 mm length (standard), or 100 × 200 mm (small-aggregate concrete). 2. Preparation: cured 28 days in water at 27 ± 2 °C. Surface dry before test. Mark two diametrically opposite generators along the length. 3. Loading: cylinder placed horizontally between platens of a compression testing machine, with two plywood strips (3 mm thick × 25 mm wide × 300 mm long) cushioning the line of contact along the marked generators. 4. Rate: load applied continuously at 1.2-2.4 N/mm² per minute on the cylinder cross-section. 5. Failure: cylinder splits along the loaded diameter. Record peak load P (kN). 6. Calculation:

`f_ct = 2P / (π × L × D)`

where P = peak load (N), L = cylinder length (mm), D = cylinder diameter (mm). Result in N/mm².

Report one f_ct per cylinder; mean of three is the batch result.

Reference values you'll actually use

Typical f_ct vs f_ck (28-day):

| Concrete grade | f_ck (cube) | f_ct typical | f_ct / f_ck ratio | |---|---|---|---| | M20 | 20 MPa | 2.5-3.0 MPa | ~12-15 % | | M25 | 25 MPa | 2.8-3.4 MPa | ~11-14 % | | M30 | 30 MPa | 3.1-3.7 MPa | ~10-12 % | | M40 | 40 MPa | 3.6-4.4 MPa | ~9-11 % | | M50 | 50 MPa | 4.0-4.8 MPa | ~8-10 % | | M60 | 60 MPa | 4.4-5.2 MPa | ~7-9 % |

Comparison with IS 456 Clause 6.2.2 estimate (`f_ct ≈ 0.7 √f_ck`): - M25: 0.7 × √25 = 3.5 MPa → matches measured upper bound - M40: 0.7 × √40 = 4.4 MPa → matches measured upper bound

The formula slightly over-predicts for higher grades (>M50). Always verify by test for high-strength mixes.

Acceptance for PQC (IRC:58): - M40 PQC: 28-day flexural strength ≥ 4.5 MPa (from beam test) — split tensile is the secondary verification, target ~3.5 MPa. - Report at 7-day and 28-day; the 7-day flexural is typically 75-80 % of 28-day.

Companion codes (must pair with)
  • IS 456:2000 Clause 6.2.2 — design tensile strength (the assumed value when you don't test).
  • IS 516 Part 1:2021 — compressive strength on cubes (the most common companion test).
  • IS 516 Part 5 / IS 9013 — flexural strength on beam (the *third* tensile test method; used for PQC).
  • IS 10262:2019 — mix design (high-strength mixes warrant tested f_ct).
  • IS 1199 Part 1:2018 — fresh concrete sampling for the cylinder casting.
  • IS 3370 Part 2:2009 — water-retaining-structure design (crack control depends on tested tensile strength for serviceability).
  • IRC:58:2015 — rigid pavement design (PQC tensile + flexural).
  • IS 13311 Part 1:1992 — UPV and rebound tests (in-situ correlation with split tension on cores).
Common pitfalls / what reviewers flag

1. Using cubes instead of cylinders. The split test is geometry-dependent. Cube split-test results do not equal cylinder split-test results — the formula assumes cylinder geometry. 2. Skipping the plywood cushion strips. Direct steel-on-concrete contact creates stress concentrations that cause premature failure. Strips must be 3 mm × 25 mm × cylinder length, replaced when crushed. 3. Eccentric specimen positioning. Off-axis loading causes a tensile + bending state, not pure split — invalidates the test. Use a marking jig or a centring plate. 4. Loading rate too fast. Above 2.4 N/mm² per minute the apparent tensile strength rises (rate-dependent material response). Calibrate the testing machine for the slow ramp. 5. Comparing test result against IS 456 estimate without realising the formula has 30-40 % scatter. The 0.7 √f_ck rule is a design-side conservative estimate. Real f_ct can be 80-130 % of the formula value. 6. Casting the cylinder vertically and forgetting to invert the generator marking. The two cushion strips must be along generators, not at the cast top/bottom (which has lower strength due to bleed water). Mark before testing. 7. Testing 7-day cylinders and rejecting. PQC and most contracts accept on 28-day. 7-day result is for *prediction*. Don't reject on 7-day alone.

When to test in tension vs assume from compressive strength

Assume from compressive strength (use IS 456 Clause 6.2.2 f_ct = 0.7 √f_ck) for routine RCC building design. This is the default in column / beam capacity calculations.

Test in split tension via IS 5816 when: - Pavement (PQC) — tensile is the design variable, not compressive - Water-retaining structure — crack-width SLS check needs accurate tensile - High-strength concrete (M50+) — formula increasingly conservative; test gives more economy - Forensic investigation of cracking — tested f_ct gives evidence of mix quality - New aggregate source qualification — split tension verifies aggregate-paste bond - Fibre-reinforced concrete — fibres dramatically alter tensile response

Test in flexure via IS 516 Part 5 / IS 9013 when: - Pavement design (typically the *primary* tensile test for PQC, with split tension as backup) - Modulus of rupture is needed (different value than split tension)

Split tension is faster and uses standard cylinder moulds you already have. Flexure is more representative of slab loading but needs longer beams (700 × 150 × 150 mm).

International Equivalents

Similar International Standards
ASTM C496/C496M-17ASTM International, USA
HighCurrent
Standard Test Method for Splitting Tensile Strength of Cylindrical Concrete Specimens
Defines the procedure for determining splitting tensile strength specifically for cylindrical specimens.
EN 12390-6:2009CEN (European Committee for Standardization), Europe
HighCurrent
Testing hardened concrete - Part 6: Tensile splitting strength of test specimens
Covers the determination of splitting tensile strength for both cylindrical and cubical concrete specimens.
BS EN 12390-6:2009BSI (British Standards Institution), UK
HighCurrent
Testing hardened concrete. Tensile splitting strength of test specimens
The UK's adoption of EN 12390-6, specifying the same method for cubes and cylinders.
AS 1012.10:2000 (R2014)Standards Australia, Australia
HighCurrent
Methods of testing concrete - Method 10: Determination of indirect tensile strength of concrete cylinders ('Brazil' or splitting test)
Specifies the method for the 'Brazil' or splitting test on concrete cylinder specimens.
Key Differences
≠IS 5816 specifies a loading rate to produce a stress increase of 1.2 to 2.4 N/mm²/min, whereas EN 12390-6 specifies 0.04 to 0.06 N/mm²/s (2.4 to 3.6 N/mm²/min), and ASTM C496 specifies 0.7 to 1.4 N/mm²/min.
≠While IS 5816 focuses on cylindrical specimens, EN 12390-6 explicitly provides procedures for both cubical and cylindrical specimens, a flexibility not detailed in the Indian standard.
≠The material and dimensions of the bearing strips differ. IS 5816 specifies 3 mm thick plywood strips, while EN 12390-6 uses 4 mm thick hardboard strips, and ASTM C496 uses 3.2 mm (1/8 in) thick plywood strips.
≠The width of the bearing strip in IS 5816 is 15 mm. This contrasts with ASTM C496, which specifies a wider strip of 25.4 mm (1 in).
Key Similarities
≈All standards are based on the same fundamental principle of the indirect tensile test (or 'Brazilian test'), where a diametral compressive load induces transverse tensile failure.
≈The formula for calculating the splitting tensile strength for cylindrical specimens is identical across all standards: f_ct = 2P / (πLD), where P is max load, L is length, and D is diameter.
≈The basic apparatus requirement is a standard compression testing machine capable of applying a controlled, continuous load without shock.
≈All standards require specimens to be properly cured under standard conditions and tested in a saturated surface-dry condition to ensure consistency.
≈The type of fracture and the appearance of the concrete are required to be recorded in the test report, in addition to the numerical results.
Parameter Comparison
ParameterIS ValueInternationalSource
Primary Specimen ShapeCylinder (150 mm dia x 300 mm long)Cylinder or CubeEN 12390-6:2009
Loading Rate (Stress)1.2 - 2.4 N/mm²/min0.7 - 1.4 N/mm²/min (100-200 psi/min)ASTM C496/C496M-17
Loading Rate (Stress)1.2 - 2.4 N/mm²/min2.4 - 3.6 N/mm²/min (0.04 - 0.06 MPa/s)EN 12390-6:2009
Bearing Strip MaterialPlywoodHardboardEN 12390-6:2009
Bearing Strip Thickness3 mm4 mm ±1 mmEN 12390-6:2009
Bearing Strip Width15 mm25 mm ±1 mm (1 in)ASTM C496/C496M-17
Calculation Formula (Cylinder)f_ct = 2P / (πLD)f_ct = 2P / (πLD)ASTM C496/C496M-17
Specimen Tolerance (Diameter)Not explicitly stated in main clauseDiameter measured to the nearest 0.1% of its valueEN 12390-6:2009
⚠ Verify details from original standards before use

Key Values6

Quick Reference Values
Standard cylinder specimen diameter150 mm
Standard cylinder specimen length300 mm
Standard cube specimen side150 mm
Packing strip width15 mm
Packing strip thickness3 mm
Rate of increase of splitting tensile stress1.2 to 2.4 N/mm²/min
Key Formulas
f_ct = 2P / (π * L * D) — Splitting Tensile Strength, where P is max load, L is length, D is diameter/width

Tables & Referenced Sections

Key Tables
No tables data
Key Clauses
Clause 4 - Apparatus
Clause 5 - Test Specimen
Clause 6 - Procedure
Clause 7 - Calculation of Splitting Tensile Strength

Related Resources on InfraLens

Cross-Referenced Codes
IS 456:2000Plain and Reinforced Concrete - Code of Pract...
→
IS 516:2021Methods of Tests for Strength of Concrete - P...
→
IS 1199:2018Fresh Concrete - Methods of Sampling and Test...
→

Frequently Asked Questions4

What specimen shapes are allowed for this test?+
Both cylindrical (150mm diameter x 300mm length) and cubical (150mm side) specimens can be used (Clause 5).
What is the formula for calculating splitting tensile strength for a cylinder?+
f_ct = 2P / (πLD), where P is the maximum applied load, L is the length, and D is the diameter of the specimen (Clause 7.1).
Why are packing strips used in this test?+
To distribute the compressive load evenly over the length of the specimen and prevent high localized stresses under the loading platens (Clause 4.3).
What should be the loading rate?+
The load must be applied continuously such that the rate of increase of splitting tensile stress is within the range of 1.2 N/mm²/min to 2.4 N/mm²/min (Clause 6.3).

QA/QC Inspection Templates

📋
QA/QC templates coming soon for this code.
Browse all 300 templates →