InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel
InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel

IS 1646 : 2020Fire Safety of Buildings - General: Electrical Installations - Code of Practice

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
IEC 60364-4-42 · BS 7671 · NFPA 70
CurrentEssentialCode of PracticeBIMFire Safety · HVAC and Air Conditioning
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues4InternationalTablesFAQ4Related

IS 1646:2020 is the Indian Standard (BIS) for fire safety of buildings - general: electrical installations - code of practice. This code outlines fire safety requirements for electrical installations in buildings. It provides guidelines on the safe installation of substations, switchgear, wiring, cables, and emergency power systems to prevent electrical fires and restrict their spread.

Specifies requirements for fire safety concerning electrical installations in buildings, applicable to HVAC electrical components.

Quick Reference — Top IS 1646:2020 Values

Key fire resistance ratings, emergency lighting levels, cable performance criteria, and critical clearances for electrical installations in buildings.

✓ Verified 2026-04-27
ReferenceValueClause
Fire Resistance (Oil Transformer Room)— Applies to walls, floor, ceiling, and doors of the enclosure.≥ 4 hCl. 8.2.1.2
Fire Resistance (Dry Transformer Room)— Applies to walls, floor, ceiling, and doors of the enclosure.≥ 2 hCl. 8.2.2
Fire Resistance (Switchgear/Panel Room)— Doors shall have a fire resistance rating of not less than 1 h.≥ 2 hCl. 8.1.2
Fire Resistance (Generator Room)— For enclosures housing prime mover and generator set.≥ 2 hCl. 8.3.1
Fire Resistance (Battery Room)— To be located on an external wall of the building.≥ 2 hCl. 8.4.1
Fire Resistance (Fire Pump Room)— Cables for fire pumps shall be of the fire survival type.≥ 2 hCl. 8.5.1
Fire Stop Rating (Penetrations)— Fire stop rating must not be less than the fire rating of the penetrated element.≥ Rating of elementCl. 9.1
Emergency Lighting Duration— Minimum duration for battery-supplied emergency lighting.≥ 3 hCl. 8.7.2
Emergency Lighting (Escape Route Axis)— Minimum illumination at floor level along the centre line.≥ 1 luxCl. 8.7.3
Emergency Lighting (Open Area > 60m²)— Excludes a 0.5 m border around the area.≥ 0.5 luxCl. 8.7.3
RCD Sensitivity (Fire Protection)— For protection against fire caused by persistent earth fault currents.≤ 300 mACl. 7.2.1
Generator Day Tank Max Capacity— If >500 L, must be in a separate room with 4h fire resistance.500 litresCl. 8.3.2
Oil Transformer Room Sill Height— To contain oil spillage within the enclosure.≥ 150 mmCl. 8.2.1.2 c)
Battery Room H₂ Concentration Limit— Ventilation must prevent hydrogen build-up to this explosive limit.< 1 % by volumeCl. 8.4.3
Cable Smoke Density (Cat. W)— Tested as per IEC 61034-2 for low smoke properties.Light Transmittance > 60%Cl. 6.2.2.1 (Annex A, Table A.1)
Cable Acidity (Cat. Z)— Tested as per IEC 60754-2 for halogen-free properties.pH > 4.3Cl. 6.2.2.1 (Annex A, Table A.1)
Cable Halogen Acid Gas (Cat. Z)— Tested as per IEC 60754-1 for halogen-free properties.< 0.5 %Cl. 6.2.2.1 (Annex A, Table A.1)
Clearance (Equip. > 500 W to Combustible)≥ 100 mmCl. 6.1.3.1 (Table 1)
Clearance (Equip. 100-500 W to Combustible)≥ 60 mmCl. 6.1.3.1 (Table 1)
Rooftop PV Firefighting Access— Clearance from roof edges and between arrays for firefighter access.≥ 1 m from edgesAnnex E-6
⚠ Verify against the latest BIS/IRC publication and project specifications. Amendment Slips may modify values.

Overview

Status
Current
Usage level
Essential
Domain
Fire Safety — HVAC and Air Conditioning
Type
Code of Practice
Earlier editions
IS 1646:1997IS 1646:1982
International equivalents
IEC 60364-4-42:2010 · IEC (International)BS 7671:2018+A2:2022 · BSI / IET (UK)NFPA 70:2023 · NFPA (US)AS/NZS 3000:2018 · Standards Australia / Standards New Zealand (AU/NZ)
Typically used with
IS 732IS 3043IS 1641IS 1642IS 2189
Also on InfraLens for IS 1646
4Key values4FAQs

BIM-relevant code. See the BIM Hub for ISO 19650, IFC, and LOD/LOIN frameworks used alongside it.

Practical Notes
! Always seal electrical shafts at every floor level with approved fire-stopping materials to prevent the chimney effect during a fire.
! FRLS (Fire Retardant Low Smoke) or LSZH (Low Smoke Zero Halogen) cables are mandatory in public buildings, basements, and escape routes.
! Ensure adequate oil containment (soak pits) and fire separation (blast walls) for indoor and outdoor oil-filled transformers.
Frequently referenced clauses
Cl. 4Sub-StationsCl. 5Installation of SwitchgearCl. 6Cables and WiringCl. 7Emergency Power SupplyCl. 8Fire Alarm and Extinguishing Systems
Pulled from IS 1646:2020. Browse the full clause & table index below in Tables & Referenced Sections.
electrical cablesswitchgearconduitsfire retardant materials

International Equivalents

Similar International Standards
IEC 60364-4-42:2010IEC (International)
HighCurrent
Low-voltage electrical installations - Part 4-42: Protection for safety - Protection against thermal effects
Focuses specifically on protecting persons and property from fire caused by electrical equipment and installations.
BS 7671:2018+A2:2022BSI / IET (UK)
HighCurrent
Requirements for Electrical Installations, IET Wiring Regulations
A comprehensive national code for electrical installations, with Chapter 42 directly addressing fire protection based on IEC 60364-4-42.
NFPA 70:2023NFPA (US)
MediumCurrent
National Electrical Code (NEC)
A prescriptive code for safe electrical installation, where fire prevention is a core objective integrated throughout the document.
AS/NZS 3000:2018Standards Australia / Standards New Zealand (AU/NZ)
MediumCurrent
Electrical installations (known as the Australian/New Zealand Wiring Rules)
Sets out requirements for electrical installations to ensure safety from fire and electric shock, with specific rules on fire risk mitigation.
Key Differences
≠Arc Fault Detection Devices (AFDDs): BS 7671:2018+A2:2022 mandates the use of AFDDs on socket-outlet circuits in high-risk locations like Houses in Multiple Occupation (HMOs) and student accommodation. IS 1646:2020 recommends AFDDs as a protective measure against arc faults but does not have such specific, mandatory location-based requirements.
≠Cable Supports in Escape Routes: BS 7671 has a very prescriptive requirement (Regulation 521.10.202) that cables in escape routes must be supported to prevent premature collapse in a fire, effectively mandating metallic fixings. IS 1646 is more performance-oriented, stating that wiring should not impede evacuation, and emphasizes fire-resistant cables, but is less prescriptive about the support method itself.
≠Risk Classification System: IS 1646 is tightly integrated with the National Building Code of India (NBC) and uses its building occupancy classifications (e.g., Assembly, Institutional, Residential) to determine requirements. International standards like BS 7671 use the IEC's 'Conditions of External Influence' classification system (e.g., BD conditions for evacuation) which is a different framework for risk assessment.
≠Harmonization and References: IS 1646 is harmonized with a suite of other Indian Standards (IS) for cables, switchgear, and building construction. BS 7671 is harmonized with European Norms (EN) and IEC standards. This leads to differences in referenced standards for components and testing methods.
Key Similarities
≈Fundamental Principle of Fire Prevention: Both IS 1646 and its international counterparts share the same core objective: to design, install, and maintain electrical systems in a manner that minimizes the risk of ignition of combustible materials and limits the spread of fire.
≈Overcurrent and Overheating Protection: All standards mandate robust protection against overcurrent using circuit breakers or fuses sized correctly for the conductor's ampacity. This is a universally recognized first line of defense against electrical fires caused by overheating cables.
≈RCDs for Fire Protection: Both IS 1646 and IEC 60364-4-42 recognize the use of Residual Current Devices (RCDs) with a sensitivity of ≤ 300 mA as a valid method of protection against fire in situations where fault currents are insufficient to trip overcurrent devices but sufficient to cause ignition.
≈Segregation and Protection of Safety Circuits: A common principle across all standards is the requirement to protect and segregate wiring for essential fire safety systems (e.g., fire alarms, emergency lighting, smoke extraction fans) from general-purpose circuits to ensure they remain operational during a fire event.
Parameter Comparison
ParameterIS ValueInternationalSource
RCD Sensitivity for Fire ProtectionRecommends RCD with sensitivity of ≤ 300 mA for protection against fire (Annex B).Requires protection by RCDs with a rated residual current ≤ 300 mA in locations with specific fire risks (BD2, BD3 conditions).IEC 60364-4-42:2010
Mandate for AFDDsRecommended as a measure for protection but not mandated for specific circuits/locations.Required on AC final circuits for socket-outlets ≤ 32A in specific high-risk residential buildings.BS 7671:2018+A2:2022
Fire Resistance of Safety Circuit CablesCables for fire safety installations shall have a fire resistance of not less than 2 hours (Clause 7.2.2).Requires 'appropriate fire resistance' based on the specific application and national building regulations, without specifying a universal duration in the wiring code itself.BS 7671:2018+A2:2022
Cable Supports in Escape RoutesWiring shall not impede evacuation; emphasizes use of fire-resistant cables.Cabling systems shall be supported so they are not liable to 'premature collapse' in a fire (interpreted as requiring non-combustible/metallic supports).BS 7671:2018+A2:2022
Selection of Fire Performance CablesSpecifies use of Fire Retardant Low Smoke (FRLS) or Low Smoke Zero Halogen (LSZH) cables for public areas and escape routes.Selection based on risk assessment for the whole installation and compliance with other building regulations, often leading to LSZH use.BS 7671:2018+A2:2022
Minimum Separation from Heat SourcesWiring shall be run at a sufficient distance from heat sources. Provides specific guidance on clearances from non-electrical services.A wiring system shall not be installed in the vicinity of a heat source so that it is adversely affected. Requires segregation from non-electrical services that may cause a risk.IEC 60364-5-52:2009
⚠ Verify details from original standards before use

Key Values4

Quick Reference Values
Fire resistance of electrical shaft doors2 hours
Minimum emergency power supply duration90 minutes
Max earth leakage current for fire protection tripping (RCCB)300 mA
Clearance of oil-filled transformer (>2000L) from building without fire wall15 m

Tables & Referenced Sections

Key Tables
No tables data
Key Clauses
Clause 4 - Sub-Stations
Clause 5 - Installation of Switchgear
Clause 6 - Cables and Wiring
Clause 7 - Emergency Power Supply
Clause 8 - Fire Alarm and Extinguishing Systems

Related Resources on InfraLens

Cross-Referenced Codes
IS 732:1989Code of practice for electrical wiring instal...
→
IS 3043:1987Code of practice for earthing
→
IS 1641:1988Code of practice for fire safety of buildings...
→
IS 1642:1989Code of practice for fire safety of buildings...
→
IS 2189:1999Code of Practice for Selection, Installation ...
→

Frequently Asked Questions4

Are oil-filled transformers allowed indoors?+
Allowed only with strict provisions like 2-hour fire-rated enclosures, oil soak pits, and automatic fire suppression.
What is the requirement for electrical duct sealing?+
Ducts and shafts must be sealed at every floor level with fire-retardant materials matching the floor's fire resistance rating.
What type of RCCB is recommended for fire safety?+
An RCCB/ELCB with a maximum sensitivity of 300 mA should be installed at the main incomer to prevent fire caused by tracking currents.
What cables must be used for emergency services?+
Fire-survival (FS) cables that can maintain circuit integrity during a fire for at least 90 minutes.

QA/QC Inspection Templates

📋
QA/QC templates coming soon for this code.
Browse all 300 templates →