InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel
InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel

IS 15105 : 2002Design and Installation of Fixed Automatic Sprinkler Fire Extinguishing Systems - Code of Practice

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
NFPA 13 · BS EN 12845 · AS 2118.1
CurrentEssentialCode of PracticeBIMFire Safety · Fire Fighting
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues7InternationalTablesFAQ4Related

IS 15105:2002 is the Indian Standard (BIS) for design and installation of fixed automatic sprinkler fire extinguishing systems - code of practice. This code provides comprehensive guidelines for the design, installation, and maintenance of fixed automatic sprinkler fire extinguishing systems in buildings. It details the classification of fire hazards, requirements for water supplies, component specifications, system layout principles, and testing procedures to ensure system reliability.

Design and Installation of Fixed Automatic Sprinkler Fire Extinguishing Systems - Code of Practice

Quick Reference — Top IS 15105:2002 Values

Key design parameters including hazard classifications, design densities, sprinkler spacing, area coverage, water supply duration, and system test pressures.

✓ Verified 2026-04-27
ReferenceValueClause
Design Density - Light Hazard— Minimum discharge density over the area of operation.2.25 mm/minCl. 6.2.2 (Table 4)
Assumed Area of Operation - Light Hazard— Maximum area assumed to be operating in a fire scenario.84 m²Cl. 6.2.2 (Table 4)
Design Density - Ordinary Hazard (OH1)— For occupancies like offices, restaurants, and schools.5.0 mm/minCl. 6.2.2 (Table 4)
Assumed Area of Operation - Ordinary Hazard (OH1)— Increases for other OH groups (up to 360 m²).72 m²Cl. 6.2.2 (Table 4)
Design Density - High Hazard Process (HHP1)— For occupancies like aircraft hangars and chemical plants.7.5 mm/minCl. 6.2.2 (Table 4)
Assumed Area of Operation - High Hazard Process (HHP1)260 m²Cl. 6.2.2 (Table 4)
Water Supply Duration - Light Hazard30 minCl. 5.2 (Table 3)
Water Supply Duration - Ordinary Hazard60 - 90 minCl. 5.2 (Table 3)
Water Supply Duration - High Hazard90 minCl. 5.2 (Table 3)
Max. Area per Sprinkler - Light Hazard— For standard spray sprinklers.21 m²Cl. 6.4 (Table 5)
Max. Area per Sprinkler - Ordinary Hazard— For standard spray sprinklers.12 m²Cl. 6.4 (Table 5)
Max. Area per Sprinkler - High Hazard— For standard spray sprinklers.9 m²Cl. 6.4 (Table 5)
Max. Sprinkler Spacing - Light/Ordinary Hazard4.6 mCl. 6.3.2 (Table 5)
Max. Sprinkler Spacing - High Hazard3.7 mCl. 6.3.2 (Table 5)
Min. Sprinkler Spacing— To prevent cold soldering (sprinklers cooling each other).2.0 mCl. 6.3.4
Max. Distance from Wall/Partition— e.g., 2.3 m for Light/Ordinary Hazard.0.5 x Max. SpacingCl. 6.3.3
Min. Distance from Wall/Partition100 mmCl. 6.3.3
Min. Clearance below Sprinkler Deflector— To allow for proper water distribution pattern.300 mmCl. 6.5.2
Sprinkler Temp Rating - Ordinary— Colour Code: Red (Glass Bulb) or Uncoloured (Fusible Link).68 °CCl. 4.6 (Table 2)
Sprinkler Temp Rating - Intermediate— Colour Code: Blue (Glass Bulb) or White (Fusible Link).93 °CCl. 4.6 (Table 2)
Min. Running Pressure at any Sprinkler— Unless higher pressure is required to meet design density.0.35 bar (5 psi)Annex C, C-2.1
Hydrostatic Test Pressure— Whichever is higher. Pw = Max. working pressure.15 bar or (Pw + 5 bar)Cl. 9.2.2.1
Hydrostatic Test Duration24 hoursCl. 9.2.2.1
⚠ Verify against the latest BIS/IRC publication and project specifications. Amendment Slips may modify values.

Overview

Status
Current
Usage level
Essential
Domain
Fire Safety — Fire Fighting
Type
Code of Practice
International equivalents
NFPA 13-22 · NFPA (US)BS EN 12845:2015+A1:2019 · BSI (UK) / CEN (Europe)AS 2118.1:2017 · Standards Australia (AU)FMDS 2-0 · FM Global (US)
Typically used with
IS 1648IS 9668IS 1239IS 1520IS 13039
Also on InfraLens for IS 15105
7Key values5Tables4FAQs

BIM-relevant code. See the BIM Hub for ISO 19650, IFC, and LOD/LOIN frameworks used alongside it.

Practical Notes
! This 2002 version has been superseded by IS 15105:2021. The 2021 version should be used for all new projects and contains significant updates.
! Hydraulic calculations are mandatory for Ordinary Hazard (OH) and High Hazard (HH) systems. Pipe schedule tables can only be used for small Light Hazard (LH) systems.
! Careful coordination with architects and other MEP (Mechanical, Electrical, Plumbing) services is essential to ensure correct sprinkler placement and avoid clashes with ducts, lights, and structural members.
Frequently referenced clauses
Cl. 5Classification of OccupanciesCl. 7Water SuppliesCl. 8Spacing, Location and Position of SprinklersCl. 11Pipe Sizing and ArrangementCl. 15Alarms and Alarm DevicesCl. 19Maintenance
Pulled from IS 15105:2002. Browse the full clause & table index below in Tables & Referenced Sections.
steel pipesCPVC pipessprinkler headswatervalves

International Equivalents

Similar International Standards
NFPA 13-22NFPA (US)
HighCurrent
Standard for the Installation of Sprinkler Systems
Both standards provide comprehensive guidelines for the design, installation, and maintenance of automatic fire sprinkler systems.
BS EN 12845:2015+A1:2019BSI (UK) / CEN (Europe)
HighCurrent
Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance
Both codes cover the design, installation, and maintenance requirements for automatic sprinkler systems in buildings.
AS 2118.1:2017Standards Australia (AU)
HighCurrent
Automatic fire sprinkler systems, Part 1: General systems
Both standards detail requirements for the design and installation of general-purpose automatic fire sprinkler systems.
FMDS 2-0FM Global (US)
HighCurrent
Installation Guidelines for Automatic Sprinklers
Both provide detailed design and installation criteria, though FMDS is an insurance standard often with more stringent requirements.
Key Differences
≠Hazard Classification: IS 15105 categorizes high hazards into three groups (HHI, HHII, HHIII). NFPA 13 uses two groups for its equivalent 'Extra Hazard' classification (Group 1 and Group 2) and has separate, extensive chapters for various storage commodities, which are more detailed than the high hazard groups in the IS code.
≠Seismic Protection: NFPA 13 contains extensive, mandatory requirements for the seismic bracing and design of sprinkler systems in seismically active areas. IS 15105:2002 has significantly less detailed provisions for seismic protection, often deferring to general structural codes without specific guidance for sprinkler piping.
≠Residential Sprinklers: NFPA 13 provides specific criteria for residential sprinklers within a combined standard, and references NFPA 13R and 13D for other residential occupancies. IS 15105:2002 does not have a distinct or detailed classification and design criteria specifically for residential sprinklers, treating them under the 'Light Hazard' category.
≠Design Density/Area Curves: The specific values and shapes of the design density vs. area of operation curves differ. For a given hazard, NFPA 13 often requires a higher density over a smaller, more concentrated area compared to the curves provided in IS 15105.
Key Similarities
≈Hazard-Based Design Philosophy: Both standards are fundamentally based on classifying the occupancy hazard level (e.g., Light, Ordinary, High/Extra) to determine the required system performance, including water density and area of application.
≈Hydraulic Calculation Method: Both codes accept and are predominantly based on hydraulic calculations using the Hazen-Williams formula to determine pipe sizes and ensure adequate pressure and flow at the most remote sprinklers.
≈Core System Components: Both standards mandate a similar set of fundamental components for a complete system, including an approved water supply, control valves, a network of pipes, automatic sprinklers, and alarm devices (water flow and tamper switches).
≈Water Supply Duration: The required minimum duration for which the water supply must be available is similar for comparable hazard levels in both codes, typically ranging from 30 minutes for light hazard to 60-120 minutes for ordinary and high hazards.
Parameter Comparison
ParameterIS ValueInternationalSource
Design Density (Ordinary Hazard - Group 2/II)Typically 7.5 mm/min (from curve)0.20 gpm/ft² (approx. 8.1 mm/min)NFPA 13-22
Design Area (Ordinary Hazard - Group 2/II)144 - 360 m² (from curve)1500 ft² (approx. 139 m²)NFPA 13-22
Maximum Sprinkler Spacing (Light Hazard, Standard Spray)4.6 m15 ft (4.6 m)NFPA 13-22
Hose Stream Allowance (Ordinary Hazard)450 - 900 L/min250 gpm (approx. 946 L/min)NFPA 13-22
Water Supply Duration (Ordinary Hazard)60 to 90 minutes60 to 90 minutesNFPA 13-22
Minimum Pipe Size (Steel, hydraulically calculated)25 mm (1 in)1 in (25 mm)NFPA 13-22
Distance of Sprinkler from Wall (max)2.3 m (for 4.6 m spacing)7.5 ft / 2.3 m (Half of max spacing)NFPA 13-22
⚠ Verify details from original standards before use

Key Values7

Quick Reference Values
Max floor area per sprinkler (Light Hazard)21 m²
Max distance between sprinklers (Light Hazard & Ordinary Hazard)4.6 m
Design density for Ordinary Hazard Group I (OH-1)5 mm/min
Assumed area of operation for Ordinary Hazard Group I (OH-1)72 m²
Minimum water supply duration for Ordinary Hazard Group II (OH-2)90 min
Minimum pressure at highest sprinkler0.35 bar (or as specified by manufacturer)
Maximum floor area controlled by one installation valve (Light Hazard)4650 m²
Key Formulas
p = (6.05 x 10^5 * Q^1.85) / (C^1.85 * d^4.87) — Hazen-Williams formula for pressure loss (in bar per metre)

Tables & Referenced Sections

Key Tables
Table 1 - Classification of Occupancy Hazard
Table 2 - Water Supply Duration
Table 3 - Summary of Sprinkler Spacing, Area Coverage and Design Density
Table 4 - Distance of Sprinklers from Walls
Table 7 - Pipe Schedule for Light Hazard Systems
Key Clauses
Clause 5 - Classification of Occupancies
Clause 7 - Water Supplies
Clause 8 - Spacing, Location and Position of Sprinklers
Clause 11 - Pipe Sizing and Arrangement
Clause 15 - Alarms and Alarm Devices
Clause 19 - Maintenance

Related Resources on InfraLens

Cross-Referenced Codes
IS 1648:2018Aluminium Alloy Die Castings for Engineering ...
→
IS 9668:2019Provisions for Safety of Workers — Code of Pr...
→
IS 1239:2004Mild steel tubes, tubulars and other wrought ...
→
IS 1520:1994Horizontal Steel Tanks for Storage of Petrole...
→
IS 13039:1991External hydrant systems - provision and main...
→
Handbook & Design Rules
Design Rules (NBC 2016)
📐Fire Sprinkler Coverage
→

Frequently Asked Questions4

What are the three main hazard classifications?+
Light Hazard (LH), Ordinary Hazard (OH) divided into Groups I, II, and III, and High Hazard (HH) divided into Process and Storage categories. (Clause 5 & Table 1)
What is the maximum area a single sprinkler can cover in an Ordinary Hazard occupancy?+
12 m². (Table 3)
What is the minimum required duration for the water supply in a High Hazard (Process) system?+
120 minutes. (Table 2)
Can pipe schedules be used for designing a system for an office building?+
Generally no. Office buildings are typically classified as Ordinary Hazard, which requires hydraulic calculations. Pipe schedules are only for Light Hazard systems. (Clause 11.2)

QA/QC Inspection Templates

📋
QA/QC templates coming soon for this code.
Browse all 300 templates →