InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel
InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel

IS 13039 : 1991External hydrant systems - provision and maintenance - Code of practice

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
NFPA 24: 2022 · BS 9990 · NFPA 25: 2023
CurrentFrequently UsedCode of PracticeBIMFire Safety · Fire Fighting
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues7InternationalTablesFAQ4Related

IS 13039:1991 is the Indian Standard (BIS) for external hydrant systems - provision and maintenance - code of practice. This code of practice provides guidelines for the design, provision, installation, and maintenance of external fire hydrant systems. It covers hazard classification, water supply capacity, pump requirements, pipeline network design, and the placement of hydrants to ensure effective initial-stage firefighting for external risks at buildings and industrial sites.

External hydrant systems - provision and maintenance - Code of practice

Overview

Status
Current
Usage level
Frequently Used
Domain
Fire Safety — Fire Fighting
Type
Code of Practice
International equivalents
NFPA 24: 2022 · National Fire Protection Association (NFPA), USABS 9990:2015 · British Standards Institution (BSI), UKNFPA 25: 2023 · National Fire Protection Association (NFPA), USANFPA 14: 2024 · National Fire Protection Association (NFPA), USA
Typically used with
IS 3844IS 5290IS 903IS 636IS 15105
Also on InfraLens for IS 13039
7Key values3Tables4FAQs

BIM-relevant code. See the BIM Hub for ISO 19650, IFC, and LOD/LOIN frameworks used alongside it.

Practical Notes
! Always use this code in conjunction with the National Building Code (NBC) of India, Part 4, as the NBC often provides more comprehensive or updated requirements.
! The classification of hazard (Light, Ordinary, High) as per Table 1 is the most critical first step as it dictates all subsequent design parameters like water capacity, pressure, and hydrant spacing.
! Pay close attention to the pump configuration (Jockey, Main, Standby) and ensure a reliable alternate power source (like a diesel engine for the main or standby pump) is provided for system reliability.
Frequently referenced clauses
Cl. 3Classification of HazardCl. 4Provision of HydrantsCl. 5Water Supplies and PumpsCl. 6Hydrant MainsCl. 9Maintenance
Pulled from IS 13039:1991. Browse the full clause & table index below in Tables & Referenced Sections.
steel pipescast iron pipeswaterpumpshydrants

International Equivalents

Similar International Standards
NFPA 24: 2022National Fire Protection Association (NFPA), USA
HighCurrent
Standard for the Installation of Private Fire Service Mains and Their Appurtenances
Covers design and installation of underground water mains, hydrants, and valves for fire protection.
BS 9990:2015British Standards Institution (BSI), UK
HighCurrent
Non-automatic fire-fighting systems in buildings. Code of practice
Provides recommendations for the design, installation, and maintenance of fire hydrants and fire mains.
NFPA 25: 2023National Fire Protection Association (NFPA), USA
HighCurrent
Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
Specifically covers the inspection, testing, and maintenance (ITM) aspect of IS 13039.
NFPA 14: 2024National Fire Protection Association (NFPA), USA
MediumCurrent
Standard for the Installation of Standpipe and Hose Systems
Covers standpipe systems which are often supplied by external hydrants and shares pressure/flow requirements.
Key Differences
≠IS 13039 specifies a minimum running pressure of 3.5 kg/cm² (~50 psi) at the topmost hydrant, whereas NFPA standards often require higher pressures, such as 100 psi (6.9 bar) at the hydraulically remote hose connection for a Class I system (NFPA 14).
≠The hydrostatic test pressure in IS 13039 is held for 24 hours, while in NFPA 24 it is held for only 2 hours. This represents a significant difference in testing methodology and duration.
≠IS 13039 specifies a relatively prescriptive hydrant spacing of 45 meters. In contrast, NFPA 24 is more performance-based, focusing on ensuring complete coverage of the building exterior, with typical spacing not exceeding 250 ft (~76 m).
≠IS 13039 recommends hydrants be located between 6 m and 15 m from a building, whereas NFPA 24 requires a minimum distance of 40 ft (12.2 m) to protect firefighters and equipment from structural collapse or heat.
≠Component and material specifications in IS 13039 refer to Indian Standards (IS), while international codes refer to their respective national or regional standards like ASTM, AWWA (for NFPA) or EN, BS (for British Standards).
Key Similarities
≈All standards share the fundamental objective of providing a reliable and accessible water supply for manual firefighting operations by the fire brigade.
≈The core system components are consistent across all standards, including a dedicated water source, fire pumps (main and jockey), a piping network, isolation valves, and hydrant outlets.
≈All codes recommend or prefer a ring main (looped) piping configuration to enhance reliability and hydraulic performance by allowing water to flow from two directions.
≈All standards mandate that the system be hydraulically calculated to ensure specified minimum flow rates and pressures are achieved at the most demanding points of the system.
≈There is a shared emphasis on the critical importance of regular inspection, testing, and maintenance (ITM) to ensure the system remains operational and effective, with IS 13039 including a section on maintenance and NFPA having a dedicated code (NFPA 25).
Parameter Comparison
ParameterIS ValueInternationalSource
Hydrant spacingMaximum 45 meters between hydrantsNot to exceed 250 ft (~76 m), focused on complete building coverageNFPA 24
Minimum distance of hydrant from buildingRecommended 6 m to 15 m; minimum 2 mNot less than 40 ft (12.2 m)NFPA 24
Minimum running pressure at remote hydrant3.5 kg/cm² (approx. 3.5 bar / 50 psi)100 psi (6.9 bar) at remote hose connection (Class I)NFPA 14
Minimum pipe size for main150 mm nominal bore6 inches (~150 mm) for mains supplying hydrantsNFPA 24
Minimum water supply duration (High Hazard)120 minutes90-120 minutes (based on combined sprinkler and hose stream demand)NFPA 13/14
Hydrostatic test pressure15 kg/cm² (~14.7 bar) or 1.5 x working pressure, for 24 hours200 psi (13.8 bar) or working pressure + 50 psi, for 2 hoursNFPA 24
Flow rate per hydrant outlet900 LPM250 GPM (~946 LPM) per hose connectionNFPA 14
⚠ Verify details from original standards before use

Key Values7

Quick Reference Values
Minimum pressure at most remote hydrant3.5 kg/cm² (350 kPa)
Maximum hydrant spacing for Ordinary/High Hazard30 m
Maximum hydrant spacing for Light Hazard45 m
Minimum hydrant main pipe diameter150 mm
Minimum water supply duration for Ordinary Hazard120 minutes
Minimum water supply duration for High Hazard180 minutes
Distance of hydrant from buildingMinimum 2m and Maximum 15m

Tables & Referenced Sections

Key Tables
Table 1 - Classification of Hazard
Table 2 - Water Supply Requirement for Hydrant Systems
Table 3 - Minimum Pressure Requirements for External Hydrant System
Key Clauses
Clause 3 - Classification of Hazard
Clause 4 - Provision of Hydrants
Clause 5 - Water Supplies and Pumps
Clause 6 - Hydrant Mains
Clause 9 - Maintenance

Related Resources on InfraLens

Cross-Referenced Codes
IS 3844:1989Code of Practice for Installation and Mainten...
→
IS 5290:1993Specification for landing valves
→
IS 903:1993Specification for Fire Hose Delivery Coupling...
→
IS 636:1988Non-Ferrous Metals and Alloy Ingots for Sand ...
→
IS 15105:2002Design and Installation of Fixed Automatic Sp...
→

Frequently Asked Questions4

What is the required spacing between external hydrants for an industrial plant?+
For an Ordinary or High Hazard plant, the spacing is 30 metres. For a Light Hazard, it is 45 metres (Clause 4.2.1).
What is the minimum running pressure required at the furthest hydrant?+
The pressure at the highest or most remote hydrant shall not be less than 3.5 kg/cm² or 350 kPa (Clause 5.3.3).
What is the minimum water storage capacity required for an Ordinary Hazard property?+
The water supply should have a flow rate of 2850 litres/minute for a duration of 120 minutes, totaling 3,42,000 litres of minimum storage (Table 2).
What is the minimum pipe size for the hydrant ring main?+
The diameter of the external hydrant mains shall not be less than 150 mm (Clause 6.1.1).

QA/QC Inspection Templates

📋
QA/QC templates coming soon for this code.
Browse all 300 templates →