InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel
InfraLensInfraLens
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRRulesAbout Join Channel
Join
IS CodesIRCToolsSORHandbookQA/QCPMCFormatsCPHEEOMapsProjectsDCRDesign RulesBIMAbout Join WhatsApp Channel

IS 12559 : 1988Code of practice for selection, installation and maintenance of electrical equipment for building construction sites

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
IEC 60364-7-704 · BS 7671 · AS/NZS 3012
CurrentSpecializedCode of PracticeMEP · Electrical Installations
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues6InternationalTablesFAQ4Related

IS 12559:1988 is the Indian Standard (BIS) for selection, installation and maintenance of electrical equipment for building construction sites. This code provides guidelines for the selection, installation, and maintenance of temporary electrical systems on building construction sites. It emphasizes personnel safety from electrical hazards, covering supply systems, circuit protection, equipment installation, earthing, inspection, and maintenance procedures.

Provides recommendations for safety related to electrical installations, selection, installation, and maintenance of electrical equipment on construction sites.

Overview

Status
Current
Usage level
Specialized
Domain
MEP — Electrical Installations
Type
Code of Practice
International equivalents
IEC 60364-7-704:2017 · International Electrotechnical Commission (IEC), InternationalBS 7671:2018+A2:2022 (Section 704) · British Standards Institution (BSI) / IET, United KingdomAS/NZS 3012:2019 · Standards Australia / Standards New Zealand, Australia/New ZealandNFPA 70:2023 (Article 590) · National Fire Protection Association (NFPA), USA
Typically used with
IS 732IS 3043IS 1646IS 2309
Also on InfraLens for IS 12559
6Key values1Tables4FAQs
Practical Notes
! The harsh environment of construction sites necessitates robust mechanical protection for all cables and equipment.
! Effective earthing and the mandatory use of ELCBs/RCCBs (30mA sensitivity) on all socket-outlet circuits are critical for preventing electric shock.
! Regular inspection and testing by a competent person is essential as site conditions, layouts, and electrical loads change frequently.
Frequently referenced clauses
Cl. 4System of Supply and DistributionCl. 6ProtectionCl. 7InstallationCl. 9Inspection and TestingCl. 10Maintenance
Pulled from IS 12559:1988. Browse the full clause & table index below in Tables & Referenced Sections.
cablesswitchgeardistribution boardstemporary lightingearthing conductors

International Equivalents

Similar International Standards
IEC 60364-7-704:2017International Electrotechnical Commission (IEC), International
HighCurrent
Low-voltage electrical installations - Part 7-704: Requirements for special installations or locations - Construction and demolition site installations
Direct international equivalent covering temporary electrical installations on construction and demolition sites.
BS 7671:2018+A2:2022 (Section 704)British Standards Institution (BSI) / IET, United Kingdom
HighCurrent
Requirements for Electrical Installations, IET Wiring Regulations (Section 704: Construction and demolition site installations)
The UK's national wiring code, with a specific section that aligns very closely with the scope of IS 12559.
AS/NZS 3012:2019Standards Australia / Standards New Zealand, Australia/New Zealand
HighCurrent
Electrical installations - Construction and demolition sites
A dedicated standard for construction sites, covering similar principles of temporary power, distribution, and safety.
NFPA 70:2023 (Article 590)National Fire Protection Association (NFPA), USA
MediumCurrent
National Electrical Code (NEC) (Article 590: Temporary Installations)
Covers temporary electrical installations, but with different voltage standards, terminology, and system philosophies.
Key Differences
≠IS 12559:1988 is advisory on the use of Residual Current Devices (RCDs/RCCBs), recommending them 'wherever practicable'. Modern standards like IEC 60364-7-704 mandate 30 mA RCD protection for almost all final circuits and socket outlets.
≠While IS 12559 recommends reduced voltage systems (e.g., 110V) for safety, UK practice (BS 7671) is far more prescriptive, strongly favoring a 110V centre-tapped-to-earth (CTE) system, providing a maximum of 55V to earth under fault conditions.
≠Modern international standards specify stringent periodic inspection and testing regimes (e.g., 3-monthly tests for portable equipment under AS/NZS 3012). IS 12559 only calls for 'regular inspection' without defining specific intervals or tests.
≠IEC 60364-7-704 and BS 7671 mandate minimum ingress protection ratings for enclosures (e.g., IP44 for distribution assemblies), whereas IS 12559 uses general terms like 'robustly constructed' and 'weatherproof' without specifying IP codes.
Key Similarities
≈All standards emphasize the fundamental requirement of protecting persons from electric shock through measures like earthing, bonding, and automatic disconnection of supply.
≈There is a common principle across all standards that temporary wiring and cables must be adequately protected from mechanical damage, either by their construction (e.g., armoured) or by their installation method (e.g., routing, containment).
≈All the compared standards require the provision of clearly marked and readily accessible means for emergency switching of the installation or parts thereof.
≈A core similarity is the mandatory use of a separate protective conductor (earth wire) run to all equipment and distribution points to ensure an effective fault path, aligning with the TN-S system recommended by IS 12559.
Parameter Comparison
ParameterIS ValueInternationalSource
Shock Protection for Socket OutletsUse of Earth Leakage Circuit Breakers (RCCB) is recommended 'wherever practicable'. No trip rating is mandated.Mandatory protection by a 30 mA RCD for all socket-outlets with rated current up to 32 A.IEC 60364-7-704:2017
Reduced Voltage System for Hand ToolsUse of a reduced voltage system (e.g. 110 V or 24 V) is recommended for safety.Use of a 110 V centre-tapped to earth (55 V to earth) system is the preferred method for portable tools.BS 7671 (Section 704)
Minimum Protection for Distribution BoardsEnclosures shall be 'robustly constructed' and 'weather-proof'.Assemblies for distribution (ASs) shall have a degree of protection of at least IP44.IEC 60364-7-704:2017
Periodic Inspection IntervalA system of 'regular inspection and maintenance' shall be carried out. (Frequency not specified).Transportable equipment must be inspected and tested at least every 6 months. Hand-held equipment every 3 months.AS/NZS 3012:2019
Separation of Neutral & Protective ConductorRecommends a 5-wire system from the source, implying separate Neutral and Protective conductors (TN-S).On the construction site, the protective conductor and the neutral conductor shall be separate (TN-S system).IEC 60364-7-704:2017
Minimum Conductor Size (Flexible Cords)For portable and transportable apparatus, not less than 1.5 mm² copper.Flexible cables for general use shall have a minimum cross-sectional area of 1.5 mm² copper.BS 7671 (Section 704)
⚠ Verify details from original standards before use

Key Values6

Quick Reference Values
Maximum voltage for portable hand lamps24 V
Maximum voltage for portable tools240 V (with ELCB/RCCB protection)
Recommended sensitivity for ELCB/RCCB30 mA
Minimum clearance of lowest conductor (overhead line) from ground across a street5.8 m
Minimum clearance of lowest conductor (overhead line) along a street5.5 m
Minimum depth for underground cables (direct buried)0.6 m

Tables & Referenced Sections

Key Tables
Table 1 - Recommended Minimum Clearances for Overhead Lines
Key Clauses
Clause 4 - System of Supply and Distribution
Clause 6 - Protection
Clause 7 - Installation
Clause 9 - Inspection and Testing
Clause 10 - Maintenance

Related Resources on InfraLens

Cross-Referenced Codes
IS 732:1989Code of practice for electrical wiring instal...
→
IS 3043:1987Code of practice for earthing
→
IS 1646:1997Code of Practice for Fire Safety of Buildings...
→
IS 2309:1989Code of practice for protection of buildings ...
→

Frequently Asked Questions4

What is the maximum permissible voltage for a portable hand lamp on a construction site?+
24V, to ensure safety in potentially damp, confined, or rough environments (Clause 7.4.2.2).
Are Earth Leakage Circuit Breakers (ELCBs/RCCBs) required for temporary installations?+
Yes, their use is strongly recommended for all socket outlets to provide protection against direct and indirect contact shocks (Clause 6.3).
How should electrical cables be run across a site?+
Cables should be run overhead with adequate clearance or be buried/placed in protected channels to prevent mechanical damage from site traffic and activities (Clause 7.1).
What is the minimum clearance for an overhead power line on a construction site?+
For lines crossing a street, the minimum clearance is 5.8 meters from the ground to the lowest conductor (Table 1).

QA/QC Inspection Templates

📋
QA/QC templates coming soon for this code.
Browse all 300 templates →