IS 13913

: 1993

Fire Dampers and Smoke Dampers for Air Distribution Systems - Specification

CurrentFrequently UsedSpecificationBIMMEP · HVAC and Air Conditioning
Archive.orgBIS PortalGoogle

This standard specifies the requirements for materials, construction, performance, and testing of fire dampers and smoke dampers used in HVAC air distribution systems. It aims to ensure these devices reliably prevent the spread of fire and smoke through ductwork penetrating fire-rated barriers. The code covers fire resistance ratings, leakage limits, and operational integrity.

Specifies requirements for the construction, performance, and testing of fire and smoke dampers used in air distribution systems.

Quick Reference Values
Fusible Link Operating Temperature74°C
Minimum Fire Resistance Rating90 minutes (1.5 hours)
Maximum Smoke Leakage Rate0.1 m³/s/m² at 250 Pa static pressure
Minimum Casing Sheet Thickness (GI)1.25 mm
Maximum Velocity Rating10 m/s
Maximum Operating Pressure1000 Pa
Practical Notes
Crucially, this 1993 standard has been superseded by IS 13913 (Part 1):2018 for fire dampers and IS 13913 (Part 2):2018 for motorized fire/smoke dampers. Always refer to the latest versions for new projects.
The fire rating of the damper must be selected to match the fire rating of the wall or slab it penetrates, as mandated by the National Building Code.
Correct installation is critical for performance. Ensure installation is done as per manufacturer's guidelines and the approved 'breakaway' connections for ducts are used to prevent structural damage during a fire.