IS 12835

: 2000

Design and installation of fixed foam fire extinguishing system - Code of Practice, Part 1: Low expansion foam

CurrentSpecializedCode of PracticeBIMFire Safety · Fire Fighting
Download PDFBIS PortalGoogle

This standard provides the code of practice for the design, installation, testing, and maintenance of fixed low-expansion foam fire extinguishing systems. It specifies requirements for system components, design criteria like application rates for flammable liquid hazards, water supply needs, and acceptance testing to ensure system readiness.

Design and installation of fixed foam fire extinguishing system - Code of Practice, Part 1: Low expansion foam

Quick Reference Values
Expansion Ratio of Low-Expansion FoamUp to 20:1
Minimum Application Rate (Cone Roof Hydrocarbon Tank)4.1 L/min/m²
Minimum Discharge Time (Cone Roof Hydrocarbon Tank)20 minutes
Foam Concentrate Proportioning ToleranceNot less than nominal, and not more than +30% of nominal or 1 percentage point, whichever is less restrictive.
Minimum Water Temperature for Foam Generation4°C
Annual Foam Concentrate Sample TestingRequired as per Clause 12.5
Key Formulas
Foam Solution Flow Rate (L/min) = Protected Area (m²) × Application Rate (L/min/m²)
Practical Notes
Ensure foam concentrate is listed for use with the specific proportioning and discharge equipment being installed.
Water supply is the most critical element; hydraulic calculations must verify adequate pressure and flow at the most remote discharge device.
During commissioning, the proportioning test is vital to confirm the correct foam-to-water ratio is being achieved, as incorrect concentration makes the system ineffective.