InfraLensInfraLens
IS CodesIRCProjectsCPHEEOHandbookDCRDesign RulesPMCQA/QCMapsSORToolsAbout Join Channel
Join
IS CodesIRCProjectsCPHEEOHandbookDCRDesign RulesPMCQA/QCBIMSORToolsAbout Join WhatsApp Channel
InfraLensInfraLens
IS CodesIRCProjectsCPHEEOHandbookDCRDesign RulesPMCQA/QCMapsSORToolsAbout Join Channel
Join
IS CodesIRCProjectsCPHEEOHandbookDCRDesign RulesPMCQA/QCBIMSORToolsAbout Join WhatsApp Channel

IS 2309 : 1989Code of practice for protection of buildings and structures from lightning

PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
IEC 62305 Series (Parts 1-4) · NFPA 780 · BS EN 62305 Series
CurrentEssentialCode of PracticeBIMMEP · Electrical Installations
PDFGoogleCompareBIS Portal
Link points to Internet Archive / others. Not hosted by InfraLens. Details
OverviewValues5InternationalTablesFAQ3Related

IS 2309:1989 is the Indian Standard (BIS) for protection of buildings and structures from lightning. This standard provides guidelines for the design, installation, testing, and maintenance of lightning protection systems to safeguard buildings and structures against direct lightning strokes.

Recommendations for the design, installation, and maintenance of lightning protection systems for buildings and structures, often referenced alongside newer standards.

Overview

Status
Current
Usage level
Essential
Domain
MEP — Electrical Installations
Type
Code of Practice
Amendments
Amendment 1 (2006)
International equivalents
IEC 62305 Series (Parts 1-4) · IEC (International)NFPA 780 · NFPA (US)BS EN 62305 Series · BSI (UK / Europe)
Typically used with
IS 3043
Also on InfraLens for IS 2309
5Key values3Tables3FAQs

BIM-relevant code. See the BIM Hub for ISO 19650, IFC, and LOD/LOIN frameworks used alongside it.

Practical Notes
! Do not assume lightning protection is mandatory for all buildings; use the Table 1 risk assessment index to logically justify its requirement.
! The structural reinforcement steel of a building can be used as a down conductor provided electrical continuity is adequately welded and ensured.
! Earth terminations of the lightning protection system must be bonded to the main electrical earthing system of the building to prevent dangerous potential differences.
Frequently referenced clauses
Cl. 6Need for ProtectionCl. 7Zone of ProtectionCl. 8Air TerminationsCl. 9Down ConductorsCl. 10Earth Terminations
Pulled from IS 2309:1989. Browse the full clause & table index below in Tables & Referenced Sections.
Updates & Amendments1 amendment
2006Amendment 1 (2006)
Consolidated list per BIS. For the text of each amendment, refer to the BIS portal link above.
copperaluminumgalvanized ironsteel

International Equivalents

Similar International Standards
IEC 62305 Series (Parts 1-4)IEC (International)
HighCurrent
Protection against lightning
Directly corresponds to the modern, risk-based approach for lightning protection, superseding the principles of IS 2309:1989.
NFPA 780NFPA (US)
MediumCurrent
Standard for the Installation of Lightning Protection Systems
Covers installation of LPS but uses a different risk assessment methodology and component specifications than the IEC series.
BS EN 62305 SeriesBSI (UK / Europe)
HighCurrent
Protection against lightning
The European adoption of the IEC 62305 series, making it functionally identical to the primary international standard.
IS 2309:1989 (Withdrawn)BIS (India)
HighWithdrawn
Code of practice for protection of buildings and structures from lightning
This is the original Indian standard, now superseded by the direct adoption of the IEC 62305 international standard.
Key Differences
≠IS 2309:1989 uses a prescriptive, points-based system to determine if protection is necessary. The modern equivalent, IEC 62305-2, uses a comprehensive quantitative risk management approach to determine the required Lightning Protection Level (LPL).
≠The concept of four distinct Lightning Protection Levels (LPL I, II, III, IV), which dictates all design parameters in IEC 62305, is absent in IS 2309:1989. The older code provides more generalized specifications.
≠IS 2309:1989 offers very limited guidance on protecting internal electronics. IEC 62305 has a dedicated part (Part 4) detailing the design of a coordinated Surge Protection Device (SPD) system to protect against Lightning Electromagnetic Impulse (LEMP).
≠The calculation for separation distance to prevent side-flashing is much simpler in IS 2309:1989 compared to the more detailed formula in IEC 62305-3, which accounts for the LPL, conductor length, and material insulation.
Key Similarities
≈Both standards define an external Lightning Protection System (LPS) using the same fundamental components: an air-termination system, a down-conductor system, and an earth-termination system.
≈Both codes recognize the necessity of equipotential bonding, requiring that metallic services (like water, gas pipes) entering the structure are bonded to the main earthing terminal.
≈The accepted methods for designing the air-termination system, including the use of vertical rods (Franklin method), catenary wires, and meshed conductors, are conceptually similar in both standards.
≈Both standards emphasize the critical role of a low-resistance earth termination system to safely dissipate lightning current and recommend using a combination of vertical rods and ring conductors.
Parameter Comparison
ParameterIS ValueInternationalSource
Risk Assessment MethodPrescriptive points-based system to determine need for LPS.Quantitative risk analysis to determine the required Lightning Protection Level (LPL I-IV).IEC 62305-2
Air-Termination Design MethodPrimarily uses the 'Cone of Protection' method with a 45° angle for structures up to 20m.Primarily uses the 'Rolling Sphere Method' with radii dependent on LPL (20m for LPL I, up to 60m for LPL IV).IEC 62305-3
Typical Down-Conductor SpacingMaximum spacing of 30m, with additional conductors based on ground area.Average spacing is determined by LPL: 10m (LPL I/II), 15m (LPL III), 20m (LPL IV).IEC 62305-3
Roof Conductor Mesh SizeRecommends a grid of 10m x 20m.Maximum mesh size is determined by LPL: 5x5m (LPL I), 10x10m (LPL II), 15x15m (LPL III), 20x20m (LPL IV).IEC 62305-3
Minimum Earth ResistanceThe combined resistance of the earthing system should ideally not exceed 10 Ohms.A value below 10 Ohms is recommended, but the primary requirement focuses on minimum electrode length (e.g., 5m) and configuration (Type A/B).IEC 62305-3
Min. Cross-Section (Copper Conductor)50 mm² (e.g., 20mm x 2.5mm tape).50 mm² (minimum thickness 2mm for tape).IEC 62305-3
⚠ Verify details from original standards before use

Key Values5

Quick Reference Values
Maximum earth resistance of lightning protection system10 Ohms
Standard spacing of down conductors20 m
Spacing of down conductors for structures >20m high10 m
Minimum cross-section for copper strip down conductor20 x 3 mm
Minimum cross-section for galvanized iron strip down conductor20 x 3 mm
Key Formulas
Risk index = A + B + C + D + E + F + G — Overall assessment of risk

Tables & Referenced Sections

Key Tables
Table 1 - Overall Assessment of Risk
Table 2 - Materials and Minimum Dimensions of Air Terminations
Table 3 - Materials and Minimum Dimensions of Down Conductors
Key Clauses
Clause 6 - Need for Protection
Clause 7 - Zone of Protection
Clause 8 - Air Terminations
Clause 9 - Down Conductors
Clause 10 - Earth Terminations

Related Resources on InfraLens

Cross-Referenced Codes
IS 3043:1987Code of practice for earthing
→

Frequently Asked Questions3

What is the maximum permissible earth resistance for a lightning protection system?+
The resistance of the earth termination system as a whole should not exceed 10 Ohms (Clause 10.1.2).
How do you determine if a building requires lightning protection?+
By calculating the overall risk index using factors like structure use, construction type, height, and location. If the risk index is above the acceptable threshold, protection is needed (Clause 6.1.1).
Can structural steel columns be used as down conductors?+
Yes, provided the structural steel is electrically continuous from the roof to the earth termination.

QA/QC Inspection Templates

📋
QA/QC templates coming soon for this code.
Browse all 300 templates →